Chapter 6 — WATER SUPPLY AND DISTRIBUTION
610.8 Size of Meter and Building Supply Pipe Using Table 610.4.
California Plumbing Code (Title 24, Part 5) · 2022 edition · updated 2026-09-12 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
Table 610.4. The size of the meter and the building supply pipe shall be determined as follows: (1) Determine the available pressure at the water meter or
other source of supply. (2) Add or subtract depending on positive or negative ele vation change, 1 ⁄ 2 psi (3.4 kPa) for each foot (305 mm) of difference in elevation between such source of supply and the highest water supply outlet in the building or on the premises. (3) Use the “pressure range” group within which this pres sure will fall using Table 610.4. (4) Select the “length” column that is equal to or longer than
the required length. (5) Follow down the column to a fixture unit value equal to
or exceeding the total number of fixture units required by the installation. (6) Having located the proper fixture unit value for the
required length, sizes of meter and building supply pipe as found in the two left-hand columns shall be applied. No building supply pipe shall be less than 3 ⁄ 4 of an inch (20 mm) in diameter.