Chapter 6 — WATER SUPPLY AND DISTRIBUTION

603.2 Approval of Devices or Assemblies.

California Plumbing Code (Title 24, Part 5) · 2022 edition · updated 2026-09-12 · California

CBSC: official editions, supplements and errata

Italicized text is a California amendment to the model code, as printed in the official publication.

Before a device or an assembly is installed for the prevention of backflow, it shall have first been approved by the Authority Having Jurisdiction. Devices or assemblies shall be tested in accordance with recognized standards or other standards acceptable to the Authority Having Jurisdiction. Backflow prevention devices and assemblies shall comply with Table 603.2, except for specific applications and provisions as stated in Section 603.5.1 through Section 603.5.21.

2022 CALIFORNIA PLUMBING CODE 139

WATER SUPPLY AND DISTRIBUTION

TABLE 603.2 BACKFLOW PREVENTION DEVICES, ASSEMBLIES, AND METHODS
DEGREE OF HAZARD DEGREE OF HAZARD DEGREE OF HAZARD DEGREE OF HAZARD DEGREE OF HAZARD DEGREE OF HAZARD DEGREE OF HAZARD
DEVICE, ASSEMBLY,
OR METHOD1
APPLICABLE
STANDARDS
POLLUTION
(LOW HAZARD)
POLLUTION
(LOW HAZARD)
CONTAMINATION
(HIGH HAZARD)
CONTAMINATION
(HIGH HAZARD)
INSTALLATION2,3
DEVICE, ASSEMBLY,
OR METHOD1
APPLICABLE
STANDARDS
BACK-
SIPHONAGE
BACK-
PRESSURE
BACK-
SIPHONAGE
BACK-
PRESSURE
BACK-
PRESSURE
Air gap ASME
A112.1.2
X –– X –– See Table 603.3.1 in this chapter.
Air gap fittings for use
with plumbing fixtures,
appliances, and appurte-
nances
ASME
A112.1.3
X –– X –– Air gap fitting is a device with an internal air
gap, and typical installation includes
plumbing fixtures, appliances, and
appurtenances. The critical level shall not be
installed below the flood level rim.
Atmospheric vacuum
breaker (consists of a
body, checking member
and atmospheric port)
ASSE 1001 or
CSA B64.1.1
X –– X –– Upright position. No valve downstream.
Minimum of 6 inches or listed distance
above all downstream piping and flood level
rim of receptor.4,5
Antisiphon fill valve
(ballcocks) for gravity
water closet flush tanks
and urinal tanks
ASSE 1002/
ASME
A112.1002/
CSA B125.12
X –– X –– Installation of gravity water closet flush tank
and urinal tanks with the fill valve installed
with the critical level not less than 1 inch
above the opening of the overflow pipe.4,5
Vacuum breaker wall
hydrants, hose bibbs,
freeze resistant, auto-
matic draining type
ASSE 1019 or
CSA B64.2.1.1
X –– X –– Installation includes wall hydrants and hose
bibbs. Such devices are not for use under con-
tinuous pressure conditions (means of shutoff
downstream of device is prohibited).4,5
Hose connection vacuum
breakers
ASSE 1011 X –– X –– Such devices are not for use under
continuous pressure conditions. No valve
downstream.4,6
Hose connection back-
flow preventers
ASSE 1052 X –– X –– Such devices are not for use under
continuous pressure conditions.4,6
Dual check backflow
preventer
ASSE 1024 X X — — Installation does not include carbonated
drink dispensers.
Dual check backflow
preventer wall hydrants,
freeze resistant
ASSE 1053 X –– X –– Such devices are not for use under
continuous pressure conditions.4
Freeze resistant sanitary
yard hydrants
ASSE 1057 X –– X –– Such devices are not for use under
continuous pressure conditions.4
Backflow preventer with
intermediate atmospheric
vent

ASSE 1012
X X — — Installation of potable water connections to
water boilers. No high-hazard chemicals
shall be introduced into the system using
such devices. Designed to operate under con-
tinuous pressure conditions. May discharge
water.
Backflow preventer with
intermediate atmospheric
vent and pressure reduc-
ing valve
ASSE 1081 X X — — Installation of potable water connections to
water boilers. No high-hazard chemicals
shall be introduced into the system using
such devices. Designed to operate under con-
tinuous pressure conditions. May discharge
water.
Backflow preventer for
Carbonated Beverage
Dispensers (two inde-
pendent check valves
with a vent to the atmos-
phere)
ASSE 1022 X –– –– –– Installation includes carbonated beverage
machines or dispensers. These devices
operate under intermittent or continuous
pressure conditions.
Spill-Resistant Pressure
Vacuum Breaker (single
check valve with air inlet
vent and means of field
testing)
ASSE 1056 X –– X –– Upright position. Minimum of 12 inches or
listed distance above all downstream piping
and flood-level rim of receptor.5

140 2022 CALIFORNIA PLUMBING CODE

WATER SUPPLY AND DISTRIBUTION

TABLE 603.2 BACKFLOW PREVENTION DEVICES, ASSEMBLIES, AND METHODS (continued)
DEGREE OF HAZARD DEGREE OF HAZARD DEGREE OF HAZARD DEGREE OF HAZARD DEGREE OF HAZARD DEGREE OF HAZARD DEGREE OF HAZARD
DEVICE, ASSEMBLY,
OR METHOD1
APPLICABLE
STANDARDS
POLLUTION
(LOW HAZARD)
POLLUTION
(LOW HAZARD)
CONTAMINATION
(HIGH HAZARD)
CONTAMINATION
(HIGH HAZARD)
INSTALLATION2,3
DEVICE, ASSEMBLY,
OR METHOD1
APPLICABLE
STANDARDS
BACK-
SIPHONAGE
BACK-
PRESSURE
BACK-
SIPHONAGE
BACK-
PRESSURE
BACK-
PRESSURE
Double Check Valve
Backflow Prevention
Assembly (two inde-
pendent check valves
and means of field test-
ing)
ASSE 1015;
AWWA C510;
CSA B64.5 or
CSA B64.5.1
X X –– –– Horizontal unless otherwise listed. Access
and clearance shall be in accordance with the
manufacturer’s instructions, and not less
than a 12 inch clearance at the bottom for
maintenance. May need platform/ladder for
test and repair.
Does not discharge water.
Double Check Detector
Fire Protection Backflow
Prevention Assembly
(two independent check
valves with a parallel
detector assembly con-
sisting of a water meter
and a double check valve
backflow prevention
assembly and means for
field testing)
ASSE 1048 X X –– –– Horizontal unless otherwise listed. Access
and clearance shall be in accordance with the
manufacturer’s instructions, and not less
than a 12 inch clearance at the bottom for
maintenance. May need platform/ladder for
test and repair. Does not discharge water.
Installation includes a fire protection system
and is designed to operate under continuous
pressure conditions.
Pressure Vacuum
Breaker Backflow Pre-
vention Assembly
(loaded air inlet valve,
internally loaded check
valve and means for field
testing)
ASSE 1020 or
CSA B64.1.2
X –– X –– Upright position. May have valves down-
stream. Minimum of 12 inches above all
downstream piping and flood-level rim of
the receptor. May discharge water.
Reduced Pressure Princi-
ple Backflow Prevention
Assembly (two independ-
ently acting loaded check
valves, a differential
pressure relief valve and
means for field testing)
ASSE 1013;
AWWA C511;
CSA B64.4 or
CSA B64.4.1
X X X X Horizontal unless otherwise listed. Access
and clearance shall be in accordance with the
manufacturer’s instructions, and not less
than a 12 inch clearance at the bottom for
maintenance. May need platform/ladder for
test and repair. May discharge water.
Reduced Pressure Detec-
tor Fire Protection Back-
flow Prevention
Assembly (two inde-
pendently acting loaded
check valves, a differen-
tial pressure relief valve,
with a parallel detector
assembly consisting of a
water meter and a
reduced-pressure princi-
ple backflow prevention
assembly, and means for
field testing)
ASSE 1047 X X X X Horizontal unless otherwise listed. Access
and clearance shall be in accordance with the
manufacturer’s instructions, and not less
than a 12 inch clearance at the bottom for
maintenance. May need platform/ladder for
test and repair. May discharge water.
Installation includes a fire protection system
and is designed to operate under continuous
pressure conditions.
Laboratory faucet back-
flow preventer
ASSE 1035 –– –– X X Installation includes laboratory faucets. Such
devices are not for use under continuous
pressure conditions. No valve downstream.4

For SI units: 1 inch = 25.4 mm Notes: 1 See the description of devices and assemblies in this chapter. 2 Installation in pit or vault requires previous approval by the Authority Having Jurisdiction. 3 Refer to the general and specific requirement for installation. 4 Not to be subjected to operating pressure for more than 12 hours in a 24 hour period. 5 For deck-mounted and equipment-mounted vacuum breaker, see Section 603.5.13. 6 Shall be installed in accordance with Section 603.5.7.

2022 CALIFORNIA PLUMBING CODE 141

WATER SUPPLY AND DISTRIBUTION

Devices or assemblies installed in a potable water supply system for protection against backflow shall be maintained in good working condition by the person or persons having control of such devices or assemblies. Such devices or assemblies shall be tested at the time of installation, repair, or relocation and not less than on an annual schedule thereafter, or more often where required by the Authority Having Jurisdiction. Where found to be defective or inoperative, the device or assembly shall be repaired or replaced. No device or assembly shall be removed from use or relocated or other device or assembly substituted, without the approval of the Authority Having Jurisdiction.

Testing or maintenance shall be performed by a certified backflow assembly tester or repairer in accordance with ASSE Series 5000 or otherwise approved by the Authority Having Jurisdiction.