Chapter 6 — WATER SUPPLY AND DISTRIBUTION
610.12 Sizing for Velocity.
California Plumbing Code (Title 24, Part 5) · 2022 edition · updated 2026-09-12 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
Water piping systems shall not exceed the maximum velocities listed in this section or Appendix A.
610.12.1 Copper Tube Systems. Maximum velocities in copper and copper alloy tube and fitting systems shall not exceed 8 feet per second (ft/s) (2.4 m/s) in cold water and 5 ft/s (1.5 m/s) in hot water. 610.12.2 Tubing Systems Using Copper Fittings. Maximum velocities through copper fittings in tubing other than copper shall not exceed 8 ft/s (2.4 m/s) in cold water and 5 ft/s (1.5 m/s) in hot water.