Chapter 6 — WATER SUPPLY AND DISTRIBUTION
610.6 Friction and Pressure Loss. Except where the type
California Plumbing Code (Title 24, Part 5) · 2022 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
of pipe used and the water characteristics are such that no decrease in capacity due to the length of service (age of system) is expected, friction-loss data shall be obtained from the “Fairly Rough” or “Rough” charts in Appendix A of this code. Friction or pressure losses in a water meter, valve, and fittings shall be obtained from the same sources. Pressure losses through water-treating equipment, backflow prevention devices, or other flow-restricting devices shall be computed in accordance with Section 610.2.
156 2022 CALIFORNIA PLUMBING CODE
WATER SUPPLY AND DISTRIBUTION
TABLE 610.3 WATER SUPPLY FIXTURE UNITS (WSFU) AND MINIMUM FIXTURE BRANCH PIPE SIZES 3
| APPLIANCES, APPURTENANCES OR FIXTURES2 | MINIMUM FIXTURE BRANCH PIPE SIZE1,4 (inches) |
PRIVATE | PUBLIC | ASSEMBLY6 |
|---|---|---|---|---|
| Bathtub or Combination Bath/Shower (fill) | 1⁄2 | 4.0 | 4.0 | –– |
| 3⁄4 inch Bathtub Fill Valve | 3⁄4 | 10.0 | 10.0 | –– |
| Bidet | 1⁄2 | 1.0 | –– | –– |
| Clothes Washer | 1⁄2 | 4.0 | 4.0 | –– |
| Dental Unit, cuspidor | 1⁄2 | –– | 1.0 | –– |
| Dishwasher, domestic | 1⁄2 | 1.5 | 1.5 | –– |
| Drinking Fountain or Water Cooler | 1⁄2 | 0.5 | 0.5 | 0.75 |
| Hose Bibb | 1⁄2 | 2.5 | 2.5 | –– |
| Hose Bibb, each additional8 | 1⁄2 | 1.0 | 1.0 | –– |
| Lavatory | 1⁄2 | 1.0 | 1.0 | 1.0 |
| Lawn Sprinkler, each head5 | –– | 1.0 | 1.0 | –– |
| Mobilehome or Manufactured Home, each (minimum) | –– | 6.0 | –– | –– |
| Sinks | –– | –– | –– | –– |
| Bar | 1⁄2 | 1.0 | 2.0 | –– |
| Clinical Faucet | 1⁄2 | –– | 3.0 | –– |
| Clinical Flushometer Valve with or without faucet | 1 | –– | 8.0 | –– |
| Kitchen, domestic with or without dishwasher | 1⁄2 | 1.5 | 1.5 | –– |
| Laundry | 1⁄2 | 1.5 | 1.5 | –– |
| Service or Mop Basin | 1⁄2 | 1.5 | 3.0 | –– |
| Washup, each set of faucets | 1⁄2 | –– | 2.0 | –– |
| Shower, per head | 1⁄2 | 2.0 | 2.0 | –– |
| Urinal, 1.0 GPF Flushometer Valve | 3⁄4 | See Footnote7 | See Footnote7 | –– |
| Urinal, greater than 1.0 GPF Flushometer Valve | 3⁄4 | See Footnote7 | See Footnote7 | –– |
| Urinal, flush tank | 1⁄2 | 2.0 | 2.0 | 3.0 |
| Urinal with Drain Cleansing Action | 1⁄2 | 1.0 | 1.0 | 1.0 |
| Wash Fountain, circular spray | 3⁄4 | –– | 4.0 | –– |
| Water Closet, 1.6 GPF Gravity Tank | 1⁄2 | 2.5 | 2.5 | 3.5 |
| Water Closet, 1.6 GPF Flushometer Tank | 1⁄2 | 2.5 | 2.5 | 3.5 |
| Water Closet, 1.6 GPF Flushometer Valve | 1 | See Footnote7 | See Footnote7 | –– |
| Water Closet, greater than 1.6 GPF Gravity Tank | 1⁄2 | 3.0 | 5.5 | 7.0 |
| Water Closet, greater than 1.6 GPF Flushometer Valve | 1 | See Footnote7 | See Footnote7 | –– |
For SI units: 1 inch = 25 mm Notes: 1 Size of the cold branch pipe, or both the hot and cold branch pipes. 2 Appliances, appurtenances, or fixtures not referenced in this table shall be permitted to be sized by reference to fixtures having a similar flow rate and frequency of use. 3 The listed fixture unit values represent their load on the cold water building supply. The separate cold water and hot water fixture unit value for fixtures having both hot and cold water connections shall be permitted to be each taken as three-quarter of the listed total value of the fixture. 4 The listed minimum supply branch pipe sizes for individual fixtures are the nominal (I.D.) pipe size. 5 For fixtures or supply connections likely to impose continuous flow demands, determine the required flow in gallons per minute (gpm) (L/s), and add it separately to the demand in gpm (L/s) for the distribution system or portions thereof. 6 Assembly [Public Use (See Table 422.1)]. 7 Where sizing flushometer systems, see Section 610.10. 8 Reduced fixture unit loading for additional hose bibbs is to be used where sizing total building demand and for pipe sizing where more than one hose bibb is supplied by a segment of water distribution pipe. The fixture branch to each hose bibb shall be sized on the basis of 2.5 fixture units. 9 For water supply fixture unit values related to lots within mobilehome parks in all parts of the State of California, see California Code of Regulations, Title 25, Division 1, Chapter 2, Article 5, Section 1278. For water supply fixture unit values related to lots within special occupancy parks in all parts of the State of California, see California Code of Regulations, Title 25, Division 1, Chapter 2.2, Article 5, Section 2278.
2022 CALIFORNIA PLUMBING CODE 157
WATER SUPPLY AND DISTRIBUTION
| TABLE 610.4 FIXTURE UNIT TABLE FOR DETERMINING WATER PIPE AND METER SIZES | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| METER AND STREET SERVICE (inches) |
BUILDING SUPPLY AND BRANCHES (inches) |
MAXIMUM ALLOWABLE LENGTH (feet) |
MAXIMUM ALLOWABLE LENGTH (feet) |
MAXIMUM ALLOWABLE LENGTH (feet) |
MAXIMUM ALLOWABLE LENGTH (feet) |
MAXIMUM ALLOWABLE LENGTH (feet) |
MAXIMUM ALLOWABLE LENGTH (feet) |
MAXIMUM ALLOWABLE LENGTH (feet) |
MAXIMUM ALLOWABLE LENGTH (feet) |
MAXIMUM ALLOWABLE LENGTH (feet) |
MAXIMUM ALLOWABLE LENGTH (feet) |
MAXIMUM ALLOWABLE LENGTH (feet) |
MAXIMUM ALLOWABLE LENGTH (feet) |
MAXIMUM ALLOWABLE LENGTH (feet) |
MAXIMUM ALLOWABLE LENGTH (feet) |
MAXIMUM ALLOWABLE LENGTH (feet) |
| METER AND STREET SERVICE (inches) |
BUILDING SUPPLY AND BRANCHES (inches) |
40 | 60 | 80 | 100 | 150 | 200 | 250 | 300 | 400 | 500 | 600 | 700 | 800 | 900 | 1000 |
| PRESSURE RANGE – 30 to 45 psi1 | PRESSURE RANGE – 30 to 45 psi1 | PRESSURE RANGE – 30 to 45 psi1 | PRESSURE RANGE – 30 to 45 psi1 | PRESSURE RANGE – 30 to 45 psi1 | PRESSURE RANGE – 30 to 45 psi1 | PRESSURE RANGE – 30 to 45 psi1 | PRESSURE RANGE – 30 to 45 psi1 | PRESSURE RANGE – 30 to 45 psi1 | PRESSURE RANGE – 30 to 45 psi1 | PRESSURE RANGE – 30 to 45 psi1 | PRESSURE RANGE – 30 to 45 psi1 | PRESSURE RANGE – 30 to 45 psi1 | PRESSURE RANGE – 30 to 45 psi1 | PRESSURE RANGE – 30 to 45 psi1 | PRESSURE RANGE – 30 to 45 psi1 | PRESSURE RANGE – 30 to 45 psi1 |
| 3⁄4 |
1⁄22 |
6 | 5 | 4 | 3 | 2 | 1 | 1 | 1 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
| 3⁄4 |
3⁄4 | 16 | 16 | 14 | 12 | 9 | 6 | 5 | 5 | 4 | 4 | 3 | 2 | 2 | 2 | 1 |
| 3⁄4 | 1 | 29 | 25 | 23 | 21 | 17 | 15 | 13 | 12 | 10 | 8 | 6 | 6 | 6 | 6 | 6 |
| 1 |
1 |
36 | 31 | 27 | 25 | 20 | 17 | 15 | 13 | 12 | 10 | 8 | 6 | 6 | 6 | 6 |
| 3⁄4 | 11⁄4 |
36 | 33 | 31 | 28 | 24 | 23 | 21 | 19 | 17 | 16 | 13 | 12 | 12 | 11 | 11 |
| 1 |
11⁄4 |
54 | 47 | 42 | 38 | 32 | 28 | 25 | 23 | 19 | 17 | 14 | 12 | 12 | 11 | 11 |
| 11⁄2 | 11⁄4 |
78 | 68 | 57 | 48 | 38 | 32 | 28 | 25 | 21 | 18 | 15 | 12 | 12 | 11 | 11 |
| 1 |
11⁄2 |
85 | 84 | 79 | 65 | 56 | 48 | 43 | 38 | 32 | 28 | 26 | 22 | 21 | 20 | 20 |
| 11⁄2 | 11⁄2 |
150 | 124 | 105 | 91 | 70 | 57 | 49 | 45 | 36 | 31 | 26 | 23 | 21 | 20 | 20 |
| 2 | 11⁄2 | 151 | 129 | 129 | 110 | 80 | 64 | 53 | 46 | 38 | 32 | 27 | 23 | 21 | 20 | 20 |
| 1 |
2 | 85 | 85 | 85 | 85 | 85 | 85 | 82 | 80 | 66 | 61 | 57 | 52 | 49 | 46 | 43 |
| 11⁄2 | 2 | 220 | 205 | 190 | 176 | 155 | 138 | 127 | 120 | 104 | 85 | 70 | 61 | 57 | 54 | 51 |
| 2 | 2 |
370 | 327 | 292 | 265 | 217 | 185 | 164 | 147 | 124 | 96 | 70 | 61 | 57 | 54 | 51 |
| 2 | 21⁄2 | 445 | 418 | 390 | 370 | 330 | 300 | 280 | 265 | 240 | 220 | 198 | 175 | 158 | 143 | 133 |
| PRESSURE RANGE – 46 to 60 psi1 | PRESSURE RANGE – 46 to 60 psi1 | PRESSURE RANGE – 46 to 60 psi1 | PRESSURE RANGE – 46 to 60 psi1 | PRESSURE RANGE – 46 to 60 psi1 | PRESSURE RANGE – 46 to 60 psi1 | PRESSURE RANGE – 46 to 60 psi1 | PRESSURE RANGE – 46 to 60 psi1 | PRESSURE RANGE – 46 to 60 psi1 | PRESSURE RANGE – 46 to 60 psi1 | PRESSURE RANGE – 46 to 60 psi1 | PRESSURE RANGE – 46 to 60 psi1 | PRESSURE RANGE – 46 to 60 psi1 | PRESSURE RANGE – 46 to 60 psi1 | PRESSURE RANGE – 46 to 60 psi1 | PRESSURE RANGE – 46 to 60 psi1 | PRESSURE RANGE – 46 to 60 psi1 |
| 3⁄4 |
1⁄22 |
7 | 7 | 6 | 5 | 4 | 3 | 2 | 2 | 1 | 1 | 1 | 0 | 0 | 0 | 0 |
| 3⁄4 |
3⁄4 | 20 | 20 | 19 | 17 | 14 | 11 | 9 | 8 | 6 | 5 | 4 | 4 | 3 | 3 | 3 |
| 3⁄4 | 1 | 39 | 39 | 36 | 33 | 28 | 23 | 21 | 19 | 17 | 14 | 12 | 10 | 9 | 8 | 8 |
| 1 |
1 |
39 | 39 | 39 | 36 | 30 | 25 | 23 | 20 | 18 | 15 | 12 | 10 | 9 | 8 | 8 |
| 3⁄4 | 11⁄4 |
39 | 39 | 39 | 39 | 39 | 39 | 34 | 32 | 27 | 25 | 22 | 19 | 19 | 17 | 16 |
| 1 |
11⁄4 |
78 | 78 | 76 | 67 | 52 | 44 | 39 | 36 | 30 | 27 | 24 | 20 | 19 | 17 | 16 |
| 11⁄2 | 11⁄4 |
78 | 78 | 78 | 78 | 66 | 52 | 44 | 39 | 33 | 29 | 24 | 20 | 19 | 17 | 16 |
| 1 |
11⁄2 |
85 | 85 | 85 | 85 | 85 | 85 | 80 | 67 | 55 | 49 | 41 | 37 | 34 | 32 | 30 |
| 11⁄2 | 11⁄2 |
151 | 151 | 151 | 151 | 128 | 105 | 90 | 78 | 62 | 52 | 42 | 38 | 35 | 32 | 30 |
| 2 | 11⁄2 | 151 | 151 | 151 | 151 | 150 | 117 | 98 | 84 | 67 | 55 | 42 | 38 | 35 | 32 | 30 |
| 1 |
2 | 85 | 85 | 85 | 85 | 85 | 85 | 85 | 85 | 85 | 85 | 85 | 85 | 85 | 83 | 80 |
| 11⁄2 | 2 | 370 | 370 | 340 | 318 | 272 | 240 | 220 | 198 | 170 | 150 | 135 | 123 | 110 | 102 | 94 |
| 2 | 2 |
370 | 370 | 370 | 370 | 368 | 318 | 280 | 250 | 205 | 165 | 142 | 123 | 110 | 102 | 94 |
| 2 | 21⁄2 | 654 | 640 | 610 | 580 | 535 | 500 | 470 | 440 | 400 | 365 | 335 | 315 | 285 | 267 | 250 |
| PRESSURE RANGE – Over 60 psi1 | PRESSURE RANGE – Over 60 psi1 | PRESSURE RANGE – Over 60 psi1 | PRESSURE RANGE – Over 60 psi1 | PRESSURE RANGE – Over 60 psi1 | PRESSURE RANGE – Over 60 psi1 | PRESSURE RANGE – Over 60 psi1 | PRESSURE RANGE – Over 60 psi1 | PRESSURE RANGE – Over 60 psi1 | PRESSURE RANGE – Over 60 psi1 | PRESSURE RANGE – Over 60 psi1 | PRESSURE RANGE – Over 60 psi1 | PRESSURE RANGE – Over 60 psi1 | PRESSURE RANGE – Over 60 psi1 | PRESSURE RANGE – Over 60 psi1 | PRESSURE RANGE – Over 60 psi1 | PRESSURE RANGE – Over 60 psi1 |
| 3⁄4 |
1⁄22 |
7 | 7 | 7 | 6 | 5 | 4 | 3 | 3 | 2 | 1 | 1 | 1 | 1 | 1 | 0 |
| 3⁄4 |
3⁄4 | 20 | 20 | 20 | 20 | 17 | 13 | 11 | 10 | 8 | 7 | 6 | 6 | 5 | 4 | 4 |
| 3⁄4 | 1 | 39 | 39 | 39 | 39 | 35 | 30 | 27 | 24 | 21 | 17 | 14 | 13 | 12 | 12 | 11 |
| 1 |
1 |
39 | 39 | 39 | 39 | 38 | 32 | 29 | 26 | 22 | 18 | 14 | 13 | 12 | 12 | 11 |
| 3⁄4 | 11⁄4 |
39 | 39 | 39 | 39 | 39 | 39 | 39 | 39 | 34 | 28 | 26 | 25 | 23 | 22 | 21 |
| 1 |
11⁄4 |
78 | 78 | 78 | 78 | 74 | 62 | 53 | 47 | 39 | 31 | 26 | 25 | 23 | 22 | 21 |
| 11⁄2 | 11⁄4 |
78 | 78 | 78 | 78 | 78 | 74 | 65 | 54 | 43 | 34 | 26 | 25 | 23 | 22 | 21 |
| 1 |
11⁄2 |
85 | 85 | 85 | 85 | 85 | 85 | 85 | 85 | 81 | 64 | 51 | 48 | 46 | 43 | 40 |
| 11⁄2 | 11⁄2 |
151 | 151 | 151 | 151 | 151 | 151 | 130 | 113 | 88 | 73 | 51 | 51 | 46 | 43 | 40 |
| 2 | 11⁄2 | 151 | 151 | 151 | 151 | 151 | 151 | 142 | 122 | 98 | 82 | 64 | 51 | 46 | 43 | 40 |
| 1 |
2 | 85 | 85 | 85 | 85 | 85 | 85 | 85 | 85 | 85 | 85 | 85 | 85 | 85 | 85 | 85 |
| 11⁄2 | 2 | 370 | 370 | 370 | 370 | 360 | 335 | 305 | 282 | 244 | 212 | 187 | 172 | 153 | 141 | 129 |
| 2 | 2 |
370 | 370 | 370 | 370 | 370 | 370 | 370 | 340 | 288 | 245 | 204 | 172 | 153 | 141 | 129 |
| 2 | 21⁄2 | 654 | 654 | 654 | 654 | 654 | 650 | 610 | 570 | 510 | 460 | 430 | 404 | 380 | 356 | 329 |
For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm, 1 pound-force per square inch = 6.8947 kPa Notes: 1 Available static pressure after head loss. 2 Building supply, not less than 3 ⁄ 4 of an inch (20 mm) nominal size.
158 2022 CALIFORNIA PLUMBING CODE
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Plumbing Code (Title 24, Part 5)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
- Chapter 5 — WATER HEATERS
▸Chapter 6 — WATER SUPPLY AND DISTRIBUTION
Overview- 601.1 Applicability. This chapter shall govern the materials,
- 601.2 Water Supply and Flushing. Each plumbing fixture shall b…
- 601.3 Identification of a Potable and Nonpotable
- 601.4 [CA] Schools of Cosmetology and Cosmeto-
- 601.5 [AGR] Meat and Poultry Processing Plants.
- 601.6 [AGR] Collection Centers and Facilities.
- 601.7 [AGR] Renderers. This area shall be provided with
- 601.8 [AGR] Horse Meat and Pet Food Establishments.
- 602.1 Prohibited Installation. No installation of potable
- 602.2 Cross-Contamination. No person shall make a connection o…
- 602.3 Backflow Prevention. No plumbing fixture, device,
- 602.4 Approval by Authority. No water piping supplied
- 603.1 General. Cross-connection control shall be provided
- 603.2 Approval of Devices or Assemblies. Before a
- 603.3 Backflow Prevention Devices, Assemblies, and
- 603.4 General Requirements. Assemblies shall comply
- 603.5 Specific Requirements. Specific requirements for
- 604.1 Pipe, Tube, and Fittings. Pipe, tube, fittings, solvent …
- 604.2 Lead Content. The maximum allowable lead content in pipe…
- 604.3 Copper or Copper Alloy Tube. Copper or copper
- 604.4 Hard-Drawn Copper or Copper Alloy Tubing.
- 604.5 Flexible Connectors. Flexible water connectors
- 604.6 Cast-Iron Fittings. Cast-iron fittings up to and
- 604.7 Malleable Iron Fittings. Malleable iron water fittings s…
- 604.8 Previously Used Piping and Tubing. Piping and
- 604.9 Epoxy Coating. The epoxy coating used on existing, under…
- 604.10 Plastic Materials. Approved plastic materials shall
- 604.11 Solder. Solder shall comply with the requirements of
- 604.12 Flexible Corrugated Connectors. Flexible corrugated con…
- 604.13 Water Heater Connectors. Flexible metallic (copper and …
- 605.1 Copper or Copper Alloy Pipe, Tubing, and
- 605.2 CPVC Plastic Pipe and Joints. CPVC plastic pipe
- 605.3 CPVC/AL/CPVC Plastic Pipe and Joints. Chlorinated polyvi…
- 605.4 Ductile Iron Pipe and Joints. Ductile iron pipe
- 605.5 Galvanized Steel Pipe and Joints. Galvanized
- 605.6 PE Plastic Pipe/Tubing and Joints. PE plastic
- 605.7 PE-AL-PE Plastic Pipe/Tubing and Joints. PEAL-PE plastic…
- 605.8 PE-RT. Polyethylene of raised temperature (PE-RT)
- 605.9 PEX Plastic Tubing and Joints. PEX plastic tubing and fi…
- 605.10 PEX-AL-PEX Plastic Tubing and Joints. PEXAL-PEX plastic…
- 605.11 Polypropylene (PP) Piping and Joints. PP pipe
- 605.12 PVC Plastic Pipe and Joints. PVC plastic pipe
- 605.13 Stainless Steel Pipe and Joints. Joining methods for st…
- 605.14 Slip Joints. In water piping, slip joints shall be perm…
- 605.15 Dielectric Unions. Dielectric unions where
- 605.16 Joints Between Various Materials. Joints
- 606.1 General. Valves up to and including 2 inches (50
- 606.2 Fullway Valve. A fullway valve controlling outlets
- 606.3 Multidwelling Units. In multidwelling units, one or
- 606.4 Multiple Openings. Valves used to control two or
- 606.5 Control Valve. A control valve shall be installed
- 606.6 Accessible. Required shutoff or control valves shall
- 606.7 Multiple Fixtures. A single control valve shall be
- 606.8 [OSHPD 1, 1R, 2, 3, 4 & 5] Each riser or branch
- 606.9 Check Valve Required. All systems that circulate
- 606.10 Leak Detection Devices. Where leak detection
- 607.1 General. Potable water supply tanks shall be installed
- 607.2 Potable Water Tanks. Potable water supply tanks,
- 607.3 Venting. Tanks used for potable water shall be tightly
- 607.4 Overflow. Tanks shall have not less than a 16 square
- 607.5 Valves. Pressurized tanks shall be provided with a
- 608.1 Inadequate Water Pressure. Where the water pressure in t…
- 608.2 Excessive Water Pressure. Where static water
- 608.3 Expansion Tanks, and Combination Tempera-
- 608.4 Pressure Relief Valves. Each pressure relief valve
- 608.5 Discharge Piping. The discharge piping serving a
- 608.6 Water-Heating Devices. A water-heating device
- 608.7 Vacuum Relief Valves. Where a hot-water storage
- 609.1 Installation. Water piping shall be adequately supported…
- 609.2 Trenches. Water pipes shall not be run or laid in the
- 609.3 Under Concrete Slab. Water piping installed within
- 609.4 Testing. Upon completion of a section or of the entire
- 609.5 Unions. Unions shall be installed in the water supply
- 609.6 Location. Except as provided in Section 609.7, no
- 609.7 Abutting Lot. Nothing contained in this code shall
- 609.8 Pumps. Pumps shall be installed in accordance with
- 609.9 Low-Pressure Cutoff Required on Booster
- 609.10 Disinfection of Potable Water System. New or
- 609.11 Water Hammer. [Not adopted by HCD] Building
- 609.12 Pipe Insulation. Insulation of domestic hot water
- 610.1 Size. The size of each water meter and each potable
- 610.2 Pressure Loss. Where a water filter, water softener,
- 610.3 Quantity of Water. The quantity of water required to
- 610.4 Sizing Water Supply and Distribution Systems.
- 610.5 Sizing per Appendices A and C. Except as provided in Sec…
- 610.6 Friction and Pressure Loss. Except where the type
- 610.7 Conditions for Using Table 610.4. On a proposed
- 610.8 Size of Meter and Building Supply Pipe Using
- 610.9 Size of Branches. Where Table 610.4 is used, the
- 610.10 Sizing for Flushometer Valves. Where using
- 610.11 Sizing Systems for Flushometer Tanks. The size
- 610.12 Sizing for Velocity. Water piping systems shall not
- 610.13 Exceptions. The provisions of this section relative
- 611.1 Application. Drinking water treatment units shall
- 611.2 Air Gap Discharge. Discharge from drinking water
- 611.3 Connection Tubing. The tubing to and from drinking water…
- 611.4 Sizing of Residential Softeners. Residential-use
- 612.1 Installation. Residential Sprinkler Systems shall be
- 613.1 The domestic water-heating equipment and distribu-
- 613.2 At least two pieces of hot-water-heating equipment shall
- 613.3 Instantaneous heaters are permitted for supplying hot
- 613.4 Water storage tanks shall be fabricated of corrosion-
- 613.5 Temperature control valves shall be provided to auto-
- 613.6 Hot-water distribution system serving patient care
- 613.7 At fixtures where water exceeding 125°F (52°C) is acces-
- 613.8 Sectionalizing valves shall be provided as required by
- 614.1 [OSHPD 1, 1R, 2, 3, 4 & 5] Dialysis water feedlines
- 614.2 All piping for multistation or central dialysis units sh…
- 614.3 All valves shall be located in accessible locations.
- 614.4 Piping and valves shall be identified according to their
- 614.5 A means of preventing backwashing or flushing of the
- 614.6 A continuous audible alarm shall sound at the nurses’
- 614.7 Water used for dialysis treatment shall meet the latest
- 614.8 A diagram of all piping as installed shall be posted at …
- 615.1 Uses Not Permitted.
- 615.2 [OSHPD 1, 1R, 2, 3, 4 & 5] Non-potable water sys-
- 615.3 [OSHPD 1, 1R, 2, 3, 4 & 5] Outlets for non-potable
- 615.4 [OSHPD 1] Emergency Water Supply.
- Chapter 7 — SANITARY DRAINAGE
- Chapter 8 — INDIRECT WASTES
- Chapter 9 — VENTS
- Chapter 10 — TRAPS AND INTERCEPTORS
- Chapter 11 — STORM DRAINAGE
- Chapter 12 — FUEL GAS PIPING
- Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
- Chapter 14 — FIRESTOP PROTECTION
- Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
- Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
- Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
- Appendix C — ALTERNATE PLUMBING SYSTEMS
- Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
- Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
- Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
- Appendix G — SIZING OF VENTING SYSTEMS
- Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
- Appendix I — INSTALLATION STANDARDS
- Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
- Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
- Appendix L — SUSTAINABLE PRACTICES
- Appendix M — PEAK WATER DEMAND CALCULATOR
- Appendix N — IMPACT OF WATER TEMPERATURE ON THE POTENTIAL FOR …