Chapter 6 — WATER SUPPLY AND DISTRIBUTION

603.2 Approval of Devices or Assemblies. Before a

California Plumbing Code (Title 24, Part 5) · 2022 edition · updated 2026-09-10 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

device or an assembly is installed for the prevention of backflow, it shall have first been approved by the Authority Having Jurisdiction. Devices or assemblies shall be tested in accordance with recognized standards or other standards acceptable to the Authority Having Jurisdiction. Backflow prevention devices and assemblies shall comply with Table 603.2, except for specific applications and provisions as stated in Section 603.5.1 through Section 603.5.21.

2022 CALIFORNIA PLUMBING CODE 139

WATER SUPPLY AND DISTRIBUTION

TABLE 603.2 BACKFLOW PREVENTION DEVICES, ASSEMBLIES, AND METHODS
DEGREE OF HAZARD DEGREE OF HAZARD DEGREE OF HAZARD DEGREE OF HAZARD DEGREE OF HAZARD DEGREE OF HAZARD DEGREE OF HAZARD
DEVICE, ASSEMBLY,
OR METHOD1
APPLICABLE
STANDARDS
POLLUTION
(LOW HAZARD)
POLLUTION
(LOW HAZARD)
CONTAMINATION
(HIGH HAZARD)
CONTAMINATION
(HIGH HAZARD)
INSTALLATION2,3
DEVICE, ASSEMBLY,
OR METHOD1
APPLICABLE
STANDARDS
BACK-
SIPHONAGE
BACK-
PRESSURE
BACK-
SIPHONAGE
BACK-
PRESSURE
BACK-
PRESSURE
Air gap ASME
A112.1.2
X –– X –– See Table 603.3.1 in this chapter.
Air gap fittings for use
with plumbing fixtures,
appliances, and appurte-
nances
ASME
A112.1.3
X –– X –– Air gap fitting is a device with an internal air
gap, and typical installation includes
plumbing fixtures, appliances, and
appurtenances. The critical level shall not be
installed below the flood level rim.
Atmospheric vacuum
breaker (consists of a
body, checking member
and atmospheric port)
ASSE 1001 or
CSA B64.1.1
X –– X –– Upright position. No valve downstream.
Minimum of 6 inches or listed distance
above all downstream piping and flood level
rim of receptor.4,5
Antisiphon fill valve
(ballcocks) for gravity
water closet flush tanks
and urinal tanks
ASSE 1002/
ASME
A112.1002/
CSA B125.12
X –– X –– Installation of gravity water closet flush tank
and urinal tanks with the fill valve installed
with the critical level not less than 1 inch
above the opening of the overflow pipe.4,5
Vacuum breaker wall
hydrants, hose bibbs,
freeze resistant, auto-
matic draining type
ASSE 1019 or
CSA B64.2.1.1
X –– X –– Installation includes wall hydrants and hose
bibbs. Such devices are not for use under con-
tinuous pressure conditions (means of shutoff
downstream of device is prohibited).4,5
Hose connection vacuum
breakers
ASSE 1011 X –– X –– Such devices are not for use under
continuous pressure conditions. No valve
downstream.4,6
Hose connection back-
flow preventers
ASSE 1052 X –– X –– Such devices are not for use under
continuous pressure conditions.4,6
Dual check backflow
preventer
ASSE 1024 X X Installation does not include carbonated
drink dispensers.
Dual check backflow
preventer wall hydrants,
freeze resistant
ASSE 1053 X –– X –– Such devices are not for use under
continuous pressure conditions.4
Freeze resistant sanitary
yard hydrants
ASSE 1057 X –– X –– Such devices are not for use under
continuous pressure conditions.4
Backflow preventer with
intermediate atmospheric
vent

ASSE 1012
X X Installation of potable water connections to
water boilers. No high-hazard chemicals
shall be introduced into the system using
such devices. Designed to operate under con-
tinuous pressure conditions. May discharge
water.
Backflow preventer with
intermediate atmospheric
vent and pressure reduc-
ing valve
ASSE 1081 X X Installation of potable water connections to
water boilers. No high-hazard chemicals
shall be introduced into the system using
such devices. Designed to operate under con-
tinuous pressure conditions. May discharge
water.
Backflow preventer for
Carbonated Beverage
Dispensers (two inde-
pendent check valves
with a vent to the atmos-
phere)
ASSE 1022 X –– –– –– Installation includes carbonated beverage
machines or dispensers. These devices
operate under intermittent or continuous
pressure conditions.
Spill-Resistant Pressure
Vacuum Breaker (single
check valve with air inlet
vent and means of field
testing)
ASSE 1056 X –– X –– Upright position. Minimum of 12 inches or
listed distance above all downstream piping
and flood-level rim of receptor.5

140 2022 CALIFORNIA PLUMBING CODE

WATER SUPPLY AND DISTRIBUTION

TABLE 603.2 BACKFLOW PREVENTION DEVICES, ASSEMBLIES, AND METHODS (continued)
DEGREE OF HAZARD DEGREE OF HAZARD DEGREE OF HAZARD DEGREE OF HAZARD DEGREE OF HAZARD DEGREE OF HAZARD DEGREE OF HAZARD
DEVICE, ASSEMBLY,
OR METHOD1
APPLICABLE
STANDARDS
POLLUTION
(LOW HAZARD)
POLLUTION
(LOW HAZARD)
CONTAMINATION
(HIGH HAZARD)
CONTAMINATION
(HIGH HAZARD)
INSTALLATION2,3
DEVICE, ASSEMBLY,
OR METHOD1
APPLICABLE
STANDARDS
BACK-
SIPHONAGE
BACK-
PRESSURE
BACK-
SIPHONAGE
BACK-
PRESSURE
BACK-
PRESSURE
Double Check Valve
Backflow Prevention
Assembly (two inde-
pendent check valves
and means of field test-
ing)
ASSE 1015;
AWWA C510;
CSA B64.5 or
CSA B64.5.1
X X –– –– Horizontal unless otherwise listed. Access
and clearance shall be in accordance with the
manufacturer’s instructions, and not less
than a 12 inch clearance at the bottom for
maintenance. May need platform/ladder for
test and repair.
Does not discharge water.
Double Check Detector
Fire Protection Backflow
Prevention Assembly
(two independent check
valves with a parallel
detector assembly con-
sisting of a water meter
and a double check valve
backflow prevention
assembly and means for
field testing)
ASSE 1048 X X –– –– Horizontal unless otherwise listed. Access
and clearance shall be in accordance with the
manufacturer’s instructions, and not less
than a 12 inch clearance at the bottom for
maintenance. May need platform/ladder for
test and repair. Does not discharge water.
Installation includes a fire protection system
and is designed to operate under continuous
pressure conditions.
Pressure Vacuum
Breaker Backflow Pre-
vention Assembly
(loaded air inlet valve,
internally loaded check
valve and means for field
testing)
ASSE 1020 or
CSA B64.1.2
X –– X –– Upright position. May have valves down-
stream. Minimum of 12 inches above all
downstream piping and flood-level rim of
the receptor. May discharge water.
Reduced Pressure Princi-
ple Backflow Prevention
Assembly (two independ-
ently acting loaded check
valves, a differential
pressure relief valve and
means for field testing)
ASSE 1013;
AWWA C511;
CSA B64.4 or
CSA B64.4.1
X X X X Horizontal unless otherwise listed. Access
and clearance shall be in accordance with the
manufacturer’s instructions, and not less
than a 12 inch clearance at the bottom for
maintenance. May need platform/ladder for
test and repair. May discharge water.
Reduced Pressure Detec-
tor Fire Protection Back-
flow Prevention
Assembly (two inde-
pendently acting loaded
check valves, a differen-
tial pressure relief valve,
with a parallel detector
assembly consisting of a
water meter and a
reduced-pressure princi-
ple backflow prevention
assembly, and means for
field testing)
ASSE 1047 X X X X Horizontal unless otherwise listed. Access
and clearance shall be in accordance with the
manufacturer’s instructions, and not less
than a 12 inch clearance at the bottom for
maintenance. May need platform/ladder for
test and repair. May discharge water.
Installation includes a fire protection system
and is designed to operate under continuous
pressure conditions.
Laboratory faucet back-
flow preventer
ASSE 1035 –– –– X X Installation includes laboratory faucets. Such
devices are not for use under continuous
pressure conditions. No valve downstream.4

For SI units: 1 inch = 25.4 mm Notes: 1 See the description of devices and assemblies in this chapter. 2 Installation in pit or vault requires previous approval by the Authority Having Jurisdiction. 3 Refer to the general and specific requirement for installation. 4 Not to be subjected to operating pressure for more than 12 hours in a 24 hour period. 5 For deck-mounted and equipment-mounted vacuum breaker, see Section 603.5.13. 6 Shall be installed in accordance with Section 603.5.7.

2022 CALIFORNIA PLUMBING CODE 141

WATER SUPPLY AND DISTRIBUTION

Devices or assemblies installed in a potable water supply system for protection against backflow shall be maintained in good working condition by the person or persons having control of such devices or assemblies. Such devices or assemblies shall be tested at the time of installation, repair, or relocation and not less than on an annual schedule thereafter, or more often where required by the Authority Having Jurisdiction. Where found to be defective or inoperative, the device or assembly shall be repaired or replaced. No device or assembly shall be removed from use or relocated or other device or assembly substituted, without the approval of the Authority Having Jurisdiction.

Testing or maintenance shall be performed by a certified backflow assembly tester or repairer in accordance with ASSE Series 5000 or otherwise approved by the Authority Having Jurisdiction.

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — California Plumbing Code (Title 24, Part 5)
California Plumbing Code (Title 24, Part 5)
  1. Chapter 1 — GENERAL CODE PROVISIONS
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — GENERAL REGULATIONS
  4. Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
  5. Chapter 5 — WATER HEATERS
  6. Chapter 6 — WATER SUPPLY AND DISTRIBUTION
    Overview
    1. 601.1 Applicability. This chapter shall govern the materials,
    2. 601.2 Water Supply and Flushing. Each plumbing fixture shall b…
    3. 601.3 Identification of a Potable and Nonpotable
    4. 601.4 [CA] Schools of Cosmetology and Cosmeto-
    5. 601.5 [AGR] Meat and Poultry Processing Plants.
    6. 601.6 [AGR] Collection Centers and Facilities.
    7. 601.7 [AGR] Renderers. This area shall be provided with
    8. 601.8 [AGR] Horse Meat and Pet Food Establishments.
    9. 602.1 Prohibited Installation. No installation of potable
    10. 602.2 Cross-Contamination. No person shall make a connection o…
    11. 602.3 Backflow Prevention. No plumbing fixture, device,
    12. 602.4 Approval by Authority. No water piping supplied
    13. 603.1 General. Cross-connection control shall be provided
    14. 603.2 Approval of Devices or Assemblies. Before a
    15. 603.3 Backflow Prevention Devices, Assemblies, and
    16. 603.4 General Requirements. Assemblies shall comply
    17. 603.5 Specific Requirements. Specific requirements for
    18. 604.1 Pipe, Tube, and Fittings. Pipe, tube, fittings, solvent …
    19. 604.2 Lead Content. The maximum allowable lead content in pipe…
    20. 604.3 Copper or Copper Alloy Tube. Copper or copper
    21. 604.4 Hard-Drawn Copper or Copper Alloy Tubing.
    22. 604.5 Flexible Connectors. Flexible water connectors
    23. 604.6 Cast-Iron Fittings. Cast-iron fittings up to and
    24. 604.7 Malleable Iron Fittings. Malleable iron water fittings s…
    25. 604.8 Previously Used Piping and Tubing. Piping and
    26. 604.9 Epoxy Coating. The epoxy coating used on existing, under…
    27. 604.10 Plastic Materials. Approved plastic materials shall
    28. 604.11 Solder. Solder shall comply with the requirements of
    29. 604.12 Flexible Corrugated Connectors. Flexible corrugated con…
    30. 604.13 Water Heater Connectors. Flexible metallic (copper and …
    31. 605.1 Copper or Copper Alloy Pipe, Tubing, and
    32. 605.2 CPVC Plastic Pipe and Joints. CPVC plastic pipe
    33. 605.3 CPVC/AL/CPVC Plastic Pipe and Joints. Chlorinated polyvi…
    34. 605.4 Ductile Iron Pipe and Joints. Ductile iron pipe
    35. 605.5 Galvanized Steel Pipe and Joints. Galvanized
    36. 605.6 PE Plastic Pipe/Tubing and Joints. PE plastic
    37. 605.7 PE-AL-PE Plastic Pipe/Tubing and Joints. PEAL-PE plastic…
    38. 605.8 PE-RT. Polyethylene of raised temperature (PE-RT)
    39. 605.9 PEX Plastic Tubing and Joints. PEX plastic tubing and fi…
    40. 605.10 PEX-AL-PEX Plastic Tubing and Joints. PEXAL-PEX plastic…
    41. 605.11 Polypropylene (PP) Piping and Joints. PP pipe
    42. 605.12 PVC Plastic Pipe and Joints. PVC plastic pipe
    43. 605.13 Stainless Steel Pipe and Joints. Joining methods for st…
    44. 605.14 Slip Joints. In water piping, slip joints shall be perm…
    45. 605.15 Dielectric Unions. Dielectric unions where
    46. 605.16 Joints Between Various Materials. Joints
    47. 606.1 General. Valves up to and including 2 inches (50
    48. 606.2 Fullway Valve. A fullway valve controlling outlets
    49. 606.3 Multidwelling Units. In multidwelling units, one or
    50. 606.4 Multiple Openings. Valves used to control two or
    51. 606.5 Control Valve. A control valve shall be installed
    52. 606.6 Accessible. Required shutoff or control valves shall
    53. 606.7 Multiple Fixtures. A single control valve shall be
    54. 606.8 [OSHPD 1, 1R, 2, 3, 4 & 5] Each riser or branch
    55. 606.9 Check Valve Required. All systems that circulate
    56. 606.10 Leak Detection Devices. Where leak detection
    57. 607.1 General. Potable water supply tanks shall be installed
    58. 607.2 Potable Water Tanks. Potable water supply tanks,
    59. 607.3 Venting. Tanks used for potable water shall be tightly
    60. 607.4 Overflow. Tanks shall have not less than a 16 square
    61. 607.5 Valves. Pressurized tanks shall be provided with a
    62. 608.1 Inadequate Water Pressure. Where the water pressure in t…
    63. 608.2 Excessive Water Pressure. Where static water
    64. 608.3 Expansion Tanks, and Combination Tempera-
    65. 608.4 Pressure Relief Valves. Each pressure relief valve
    66. 608.5 Discharge Piping. The discharge piping serving a
    67. 608.6 Water-Heating Devices. A water-heating device
    68. 608.7 Vacuum Relief Valves. Where a hot-water storage
    69. 609.1 Installation. Water piping shall be adequately supported…
    70. 609.2 Trenches. Water pipes shall not be run or laid in the
    71. 609.3 Under Concrete Slab. Water piping installed within
    72. 609.4 Testing. Upon completion of a section or of the entire
    73. 609.5 Unions. Unions shall be installed in the water supply
    74. 609.6 Location. Except as provided in Section 609.7, no
    75. 609.7 Abutting Lot. Nothing contained in this code shall
    76. 609.8 Pumps. Pumps shall be installed in accordance with
    77. 609.9 Low-Pressure Cutoff Required on Booster
    78. 609.10 Disinfection of Potable Water System. New or
    79. 609.11 Water Hammer. [Not adopted by HCD] Building
    80. 609.12 Pipe Insulation. Insulation of domestic hot water
    81. 610.1 Size. The size of each water meter and each potable
    82. 610.2 Pressure Loss. Where a water filter, water softener,
    83. 610.3 Quantity of Water. The quantity of water required to
    84. 610.4 Sizing Water Supply and Distribution Systems.
    85. 610.5 Sizing per Appendices A and C. Except as provided in Sec…
    86. 610.6 Friction and Pressure Loss. Except where the type
    87. 610.7 Conditions for Using Table 610.4. On a proposed
    88. 610.8 Size of Meter and Building Supply Pipe Using
    89. 610.9 Size of Branches. Where Table 610.4 is used, the
    90. 610.10 Sizing for Flushometer Valves. Where using
    91. 610.11 Sizing Systems for Flushometer Tanks. The size
    92. 610.12 Sizing for Velocity. Water piping systems shall not
    93. 610.13 Exceptions. The provisions of this section relative
    94. 611.1 Application. Drinking water treatment units shall
    95. 611.2 Air Gap Discharge. Discharge from drinking water
    96. 611.3 Connection Tubing. The tubing to and from drinking water…
    97. 611.4 Sizing of Residential Softeners. Residential-use
    98. 612.1 Installation. Residential Sprinkler Systems shall be
    99. 613.1 The domestic water-heating equipment and distribu-
    100. 613.2 At least two pieces of hot-water-heating equipment shall
    101. 613.3 Instantaneous heaters are permitted for supplying hot
    102. 613.4 Water storage tanks shall be fabricated of corrosion-
    103. 613.5 Temperature control valves shall be provided to auto-
    104. 613.6 Hot-water distribution system serving patient care
    105. 613.7 At fixtures where water exceeding 125°F (52°C) is acces-
    106. 613.8 Sectionalizing valves shall be provided as required by
    107. 614.1 [OSHPD 1, 1R, 2, 3, 4 & 5] Dialysis water feedlines
    108. 614.2 All piping for multistation or central dialysis units sh…
    109. 614.3 All valves shall be located in accessible locations.
    110. 614.4 Piping and valves shall be identified according to their
    111. 614.5 A means of preventing backwashing or flushing of the
    112. 614.6 A continuous audible alarm shall sound at the nurses’
    113. 614.7 Water used for dialysis treatment shall meet the latest
    114. 614.8 A diagram of all piping as installed shall be posted at …
    115. 615.1 Uses Not Permitted.
    116. 615.2 [OSHPD 1, 1R, 2, 3, 4 & 5] Non-potable water sys-
    117. 615.3 [OSHPD 1, 1R, 2, 3, 4 & 5] Outlets for non-potable
    118. 615.4 [OSHPD 1] Emergency Water Supply.
  7. Chapter 7 — SANITARY DRAINAGE
  8. Chapter 8 — INDIRECT WASTES
  9. Chapter 9 — VENTS
  10. Chapter 10 — TRAPS AND INTERCEPTORS
  11. Chapter 11 — STORM DRAINAGE
  12. Chapter 12 — FUEL GAS PIPING
  13. Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
  14. Chapter 14 — FIRESTOP PROTECTION
  15. Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
  16. Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
  17. Chapter 17 — REFERENCED STANDARDS
  18. Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
  19. Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
  20. Appendix C — ALTERNATE PLUMBING SYSTEMS
  21. Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
  22. Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
  23. Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
  24. Appendix G — SIZING OF VENTING SYSTEMS
  25. Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
  26. Appendix I — INSTALLATION STANDARDS
  27. Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
  28. Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
  29. Appendix L — SUSTAINABLE PRACTICES
  30. Appendix M — PEAK WATER DEMAND CALCULATOR
  31. Appendix N — IMPACT OF WATER TEMPERATURE ON THE POTENTIAL FOR …

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.