603.3 Backflow Prevention Devices, Assemblies, and

California Plumbing Code (Title 24, Part 5) · 2022 edition · updated 2026-09-10 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

Methods. Backflow prevention devices, assemblies, and methods shall comply with Section 603.3.1 through Section 603.3.12. 603.3.1 Air Gap. The minimum air gap to afford backflow protection shall be in accordance with Table 603.3.1. 603.3.2 Atmospheric Vacuum Breaker (AVB). An atmospheric vacuum breaker consists of a body, a checking member, and an atmospheric port. 603.3.3 Hose Connection Backflow Preventer. A hose connection backflow preventer consists of two independent check valves with an independent atmospheric vent between and a means of field testing and draining.

603.3.4 Double Check Valve Backflow Prevention Assembly (DC). A double check valve backflow prevention assembly consists of two independently acting internally loaded check valves, four properly located test cocks, and two isolation valves.

603.3.5 Pressure Vacuum Breaker Backflow Pre- vention Assembly (PVB). A pressure vacuum breaker backflow prevention assembly consists of a loaded air inlet valve, an internally loaded check valve, two properly located test cocks, and two isolation valves. This device shall be permitted to be installed indoors where provisions for spillage are provided. 603.3.6 Spill-Resistant Pressure Vacuum Breaker (SVB). A pressure-type vacuum breaker backflow prevention assembly consists of one check valve force loaded closed and an air inlet vent valve force loaded open to atmosphere, positioned downstream of the check valve and located between and including two tightly closing shutoff valves and test cocks. 603.3.7 Reduced-Pressure Principle Backflow Prevention Assembly (RP). A reduced-pressure principle backflow prevention assembly consists of two independently acting internally loaded check valves, a differential pressure relief valve, four properly located test cocks, and two isolation valves. 603.3.8 Double Check Detector Fire Protection Backflow Prevention Assembly. A double check valve backflow prevention assembly with a parallel detector assembly consisting of a water meter and a double check valve backflow prevention assembly (DC). 603.3.9 Reduced Pressure Detector Fire Protec- tion Backflow Prevention Assembly. A reducedpressure principle backflow prevention assembly with a parallel detector assembly consisting of a water meter and a reduced-pressure principle backflow prevention assembly (RP). 603.3.10 Dual Check Backflow Preventer. A dual check backflow preventer consists of two independently acting check valves, force loaded to a normally closed position.

TABLE 603.3.1 MINIMUM AIR GAPS FOR WATER DISTRIBUTION 4

FIXTURES WHERE NOT AFFECTED BY SIDEWALLS1
(inches)
WHERE AFFECTED BY SIDEWALLS2
(inches)
Effective openings3 not greater than1⁄2 of an inch
in diameter
1 11⁄2
Effective openings3 not greater than3⁄4 of an inch
in diameter
11⁄2 21⁄4
Effective openings3 not greater than 1 inch in
diameter
2 3
Effective openings3 greater than 1 inch in
diameter
Two times the diameter of
effective opening
Three times the diameter of
effective opening

For SI units: 1 inch = 25.4 mm Notes: 1 Sidewalls, ribs, or similar obstructions do not affect air gaps where spaced from the inside edge of the spout opening a distance exceeding three times the diameter of the effective opening for a single wall, or a distance exceeding four times the effective opening for two intersecting walls. 2 Vertical walls, ribs, or similar obstructions extending from the water surface to or above the horizontal plane of the spout opening other than specified in Footnote 1 above. The effect of three or more such vertical walls or ribs has not been determined. In such cases, the air gap shall be measured from the top of the wall. 3 The effective opening shall be the minimum cross-sectional area at the seat of the control valve or the supply pipe or tubing that feeds the device or outlet. Where two or more lines supply one outlet, the effective opening shall be the sum of the cross-sectional areas of the individual supply lines or the area of the single outlet, whichever is smaller. 4 Air gaps less than 1 inch (25.4 mm) shall be approved as a permanent part of a listed assembly that has been tested under actual backflow conditions with vacuums of 0 to 25 inches of mercury (85 kPa).

142 2022 CALIFORNIA PLUMBING CODE

603.3.11 Laboratory Faucet Backflow Preven- ters. Laboratory faucet backflow preventers shall comply with ASSE 1035.

603.3.12 Backflow Preventer with Intermediate Atmospheric Vent. A backflow preventer with intermediate atmospheric vent consists of two independently acting check valves, force loaded to a normally closed position, and an intermediate chamber with a means for automatically venting to atmosphere, force loaded to a normally open position.

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — California Plumbing Code (Title 24, Part 5)
California Plumbing Code (Title 24, Part 5)
  1. Chapter 1 — GENERAL CODE PROVISIONS
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — GENERAL REGULATIONS
  4. Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
  5. Chapter 5 — WATER HEATERS
  6. Chapter 6 — WATER SUPPLY AND DISTRIBUTION
    Overview
    1. 601.1 Applicability. This chapter shall govern the materials,
    2. 601.2 Water Supply and Flushing. Each plumbing fixture shall b…
    3. 601.3 Identification of a Potable and Nonpotable
    4. 601.4 [CA] Schools of Cosmetology and Cosmeto-
    5. 601.5 [AGR] Meat and Poultry Processing Plants.
    6. 601.6 [AGR] Collection Centers and Facilities.
    7. 601.7 [AGR] Renderers. This area shall be provided with
    8. 601.8 [AGR] Horse Meat and Pet Food Establishments.
    9. 602.1 Prohibited Installation. No installation of potable
    10. 602.2 Cross-Contamination. No person shall make a connection o…
    11. 602.3 Backflow Prevention. No plumbing fixture, device,
    12. 602.4 Approval by Authority. No water piping supplied
    13. 603.1 General. Cross-connection control shall be provided
    14. 603.2 Approval of Devices or Assemblies. Before a
    15. 603.3 Backflow Prevention Devices, Assemblies, and
    16. 603.4 General Requirements. Assemblies shall comply
    17. 603.5 Specific Requirements. Specific requirements for
    18. 604.1 Pipe, Tube, and Fittings. Pipe, tube, fittings, solvent …
    19. 604.2 Lead Content. The maximum allowable lead content in pipe…
    20. 604.3 Copper or Copper Alloy Tube. Copper or copper
    21. 604.4 Hard-Drawn Copper or Copper Alloy Tubing.
    22. 604.5 Flexible Connectors. Flexible water connectors
    23. 604.6 Cast-Iron Fittings. Cast-iron fittings up to and
    24. 604.7 Malleable Iron Fittings. Malleable iron water fittings s…
    25. 604.8 Previously Used Piping and Tubing. Piping and
    26. 604.9 Epoxy Coating. The epoxy coating used on existing, under…
    27. 604.10 Plastic Materials. Approved plastic materials shall
    28. 604.11 Solder. Solder shall comply with the requirements of
    29. 604.12 Flexible Corrugated Connectors. Flexible corrugated con…
    30. 604.13 Water Heater Connectors. Flexible metallic (copper and …
    31. 605.1 Copper or Copper Alloy Pipe, Tubing, and
    32. 605.2 CPVC Plastic Pipe and Joints. CPVC plastic pipe
    33. 605.3 CPVC/AL/CPVC Plastic Pipe and Joints. Chlorinated polyvi…
    34. 605.4 Ductile Iron Pipe and Joints. Ductile iron pipe
    35. 605.5 Galvanized Steel Pipe and Joints. Galvanized
    36. 605.6 PE Plastic Pipe/Tubing and Joints. PE plastic
    37. 605.7 PE-AL-PE Plastic Pipe/Tubing and Joints. PEAL-PE plastic…
    38. 605.8 PE-RT. Polyethylene of raised temperature (PE-RT)
    39. 605.9 PEX Plastic Tubing and Joints. PEX plastic tubing and fi…
    40. 605.10 PEX-AL-PEX Plastic Tubing and Joints. PEXAL-PEX plastic…
    41. 605.11 Polypropylene (PP) Piping and Joints. PP pipe
    42. 605.12 PVC Plastic Pipe and Joints. PVC plastic pipe
    43. 605.13 Stainless Steel Pipe and Joints. Joining methods for st…
    44. 605.14 Slip Joints. In water piping, slip joints shall be perm…
    45. 605.15 Dielectric Unions. Dielectric unions where
    46. 605.16 Joints Between Various Materials. Joints
    47. 606.1 General. Valves up to and including 2 inches (50
    48. 606.2 Fullway Valve. A fullway valve controlling outlets
    49. 606.3 Multidwelling Units. In multidwelling units, one or
    50. 606.4 Multiple Openings. Valves used to control two or
    51. 606.5 Control Valve. A control valve shall be installed
    52. 606.6 Accessible. Required shutoff or control valves shall
    53. 606.7 Multiple Fixtures. A single control valve shall be
    54. 606.8 [OSHPD 1, 1R, 2, 3, 4 & 5] Each riser or branch
    55. 606.9 Check Valve Required. All systems that circulate
    56. 606.10 Leak Detection Devices. Where leak detection
    57. 607.1 General. Potable water supply tanks shall be installed
    58. 607.2 Potable Water Tanks. Potable water supply tanks,
    59. 607.3 Venting. Tanks used for potable water shall be tightly
    60. 607.4 Overflow. Tanks shall have not less than a 16 square
    61. 607.5 Valves. Pressurized tanks shall be provided with a
    62. 608.1 Inadequate Water Pressure. Where the water pressure in t…
    63. 608.2 Excessive Water Pressure. Where static water
    64. 608.3 Expansion Tanks, and Combination Tempera-
    65. 608.4 Pressure Relief Valves. Each pressure relief valve
    66. 608.5 Discharge Piping. The discharge piping serving a
    67. 608.6 Water-Heating Devices. A water-heating device
    68. 608.7 Vacuum Relief Valves. Where a hot-water storage
    69. 609.1 Installation. Water piping shall be adequately supported…
    70. 609.2 Trenches. Water pipes shall not be run or laid in the
    71. 609.3 Under Concrete Slab. Water piping installed within
    72. 609.4 Testing. Upon completion of a section or of the entire
    73. 609.5 Unions. Unions shall be installed in the water supply
    74. 609.6 Location. Except as provided in Section 609.7, no
    75. 609.7 Abutting Lot. Nothing contained in this code shall
    76. 609.8 Pumps. Pumps shall be installed in accordance with
    77. 609.9 Low-Pressure Cutoff Required on Booster
    78. 609.10 Disinfection of Potable Water System. New or
    79. 609.11 Water Hammer. [Not adopted by HCD] Building
    80. 609.12 Pipe Insulation. Insulation of domestic hot water
    81. 610.1 Size. The size of each water meter and each potable
    82. 610.2 Pressure Loss. Where a water filter, water softener,
    83. 610.3 Quantity of Water. The quantity of water required to
    84. 610.4 Sizing Water Supply and Distribution Systems.
    85. 610.5 Sizing per Appendices A and C. Except as provided in Sec…
    86. 610.6 Friction and Pressure Loss. Except where the type
    87. 610.7 Conditions for Using Table 610.4. On a proposed
    88. 610.8 Size of Meter and Building Supply Pipe Using
    89. 610.9 Size of Branches. Where Table 610.4 is used, the
    90. 610.10 Sizing for Flushometer Valves. Where using
    91. 610.11 Sizing Systems for Flushometer Tanks. The size
    92. 610.12 Sizing for Velocity. Water piping systems shall not
    93. 610.13 Exceptions. The provisions of this section relative
    94. 611.1 Application. Drinking water treatment units shall
    95. 611.2 Air Gap Discharge. Discharge from drinking water
    96. 611.3 Connection Tubing. The tubing to and from drinking water…
    97. 611.4 Sizing of Residential Softeners. Residential-use
    98. 612.1 Installation. Residential Sprinkler Systems shall be
    99. 613.1 The domestic water-heating equipment and distribu-
    100. 613.2 At least two pieces of hot-water-heating equipment shall
    101. 613.3 Instantaneous heaters are permitted for supplying hot
    102. 613.4 Water storage tanks shall be fabricated of corrosion-
    103. 613.5 Temperature control valves shall be provided to auto-
    104. 613.6 Hot-water distribution system serving patient care
    105. 613.7 At fixtures where water exceeding 125°F (52°C) is acces-
    106. 613.8 Sectionalizing valves shall be provided as required by
    107. 614.1 [OSHPD 1, 1R, 2, 3, 4 & 5] Dialysis water feedlines
    108. 614.2 All piping for multistation or central dialysis units sh…
    109. 614.3 All valves shall be located in accessible locations.
    110. 614.4 Piping and valves shall be identified according to their
    111. 614.5 A means of preventing backwashing or flushing of the
    112. 614.6 A continuous audible alarm shall sound at the nurses’
    113. 614.7 Water used for dialysis treatment shall meet the latest
    114. 614.8 A diagram of all piping as installed shall be posted at …
    115. 615.1 Uses Not Permitted.
    116. 615.2 [OSHPD 1, 1R, 2, 3, 4 & 5] Non-potable water sys-
    117. 615.3 [OSHPD 1, 1R, 2, 3, 4 & 5] Outlets for non-potable
    118. 615.4 [OSHPD 1] Emergency Water Supply.
  7. Chapter 7 — SANITARY DRAINAGE
  8. Chapter 8 — INDIRECT WASTES
  9. Chapter 9 — VENTS
  10. Chapter 10 — TRAPS AND INTERCEPTORS
  11. Chapter 11 — STORM DRAINAGE
  12. Chapter 12 — FUEL GAS PIPING
  13. Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
  14. Chapter 14 — FIRESTOP PROTECTION
  15. Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
  16. Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
  17. Chapter 17 — REFERENCED STANDARDS
  18. Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
  19. Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
  20. Appendix C — ALTERNATE PLUMBING SYSTEMS
  21. Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
  22. Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
  23. Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
  24. Appendix G — SIZING OF VENTING SYSTEMS
  25. Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
  26. Appendix I — INSTALLATION STANDARDS
  27. Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
  28. Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
  29. Appendix L — SUSTAINABLE PRACTICES
  30. Appendix M — PEAK WATER DEMAND CALCULATOR
  31. Appendix N — IMPACT OF WATER TEMPERATURE ON THE POTENTIAL FOR …

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.