Chapter 12 — FUEL GAS PIPING

1210.12 Systems Containing Flammable Gas-Air

California Plumbing Code (Title 24, Part 5) · 2022 edition · updated 2026-09-10 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

Mixtures. Systems containing flammable gas-air mixtures shall be in accordance with Section 1210.12.1 through Section 1210.12.6.

1210.12.1 Required Components. A central premix system with a flammable mixture in the blower or compressor shall consist of the following components: (1) Gas-mixing machine in the form of an automatic

gas-air proportioning device combined with a downstream blower or compressor.

FUEL GAS PIPING

(2) Flammable mixture piping, minimum Schedule 40. (3) Automatic firecheck(s). (4) Safety blowout(s) or backfire preventers for systems

utilizing flammable mixture lines above 2 1 ⁄ 2 inches (65 mm) nominal pipe size (NPS) or the equivalent.

[NFPA 54:7.11.1] 1210.12.2 Optional Components. The following components shall also be permitted to be utilized in any type of central premix system: (1) Flowmeter(s) (2) Flame arrester(s) [NFPA 54:7.11.2] 1210.12.3 Additional Requirements. Gas-mixing machines shall have nonsparking blowers and shall be constructed so that a flashback does not rupture machine casings. [NFPA 54:7.11.3]

1210.12.4 Special Requirements for Mixing Blowers. A mixing blower system shall be limited to applications with minimum practical lengths of mixture piping, limited to a maximum mixture pressure of 10 inches water column (2.5 kPa) and limited to gases containing no more than 10 percent hydrogen. The blower shall be equipped with a gas control valve at its air entrance arranged so that gas is admitted to the airstream, entering the blower in proper proportions for correct combustion by the type of burners employed, the said gas control valve being of either the zero governor or mechanical ratio valve type that controls the gas and air adjustment simultaneously. No valves or other obstructions shall be installed between the blower discharge and the burner or burners. [NFPA 54:7.11.4] 1210.12.5 Installation of Gas-Mixing Machines. Installation of gas-mixing machines shall comply with the following: (1) The gas-mixing machine shall be located in a well ventilated area or in a detached building or cutoff room provided with room construction and explosion vents in accordance with sound engineering principles. Such rooms or below-grade installations shall have adequate positive ventilation. (2) Where gas-mixing machines are installed in well ventilated areas, the type of electrical equipment shall be in accordance with NFPA 70 for general service conditions unless other hazards in the area prevail. Where gas-mixing machines are installed in small detached buildings or cutoff rooms, the electrical equipment and wiring shall be installed in accordance with NFPA 70 for hazardous locations (Articles 500 and 501, Class I, Division 2). (3) Air intakes for gas-mixing machines using com pressors or blowers shall be taken from outdoors whenever practical. (4) Controls for gas-mixing machines shall include inter locks and a safety shutoff valve of the manual reset type in the gas supply connection to each machine arranged to automatically shut off the gas supply in

for hazardous locations (Articles 500 and 501, Class I, Division 2). (3) Air intakes for gas-mixing machines using com pressors or blowers shall be taken from outdoors whenever practical. (4) Controls for gas-mixing machines shall include inter locks and a safety shutoff valve of the manual reset type in the gas supply connection to each machine arranged to automatically shut off the gas supply in

2022 CALIFORNIA PLUMBING CODE 223

FUEL GAS PIPING

the event of high or low gas pressure. Except for open burner installations only, the controls shall be interlocked so that the blower or compressor stops operating following a gas supply failure. Where a system employs pressurized air, means shall be provided to shut off the gas supply in the event of air failure. (5) Centrifugal gas-mixing machines in parallel shall be

reviewed by the user and equipment manufacturer before installation, and means or plans for minimizing the effects of downstream pulsation and equipment overload shall be prepared and utilized as needed. [NFPA 54:7.11.5.1 – 7.11.5.5]

1210.12.6 Use of Automatic Firechecks, Safety Blowouts, or Backfire Preventers. Automatic firechecks and safety blowouts or backfire preventers shall be provided in piping systems distributing flammable air-gas mixtures from gas-mixing machines to protect the piping and the machines in the event of flashback, in accordance with the following: (1) Approved automatic firechecks shall be installed

upstream as close as practical to the burner inlets following the firecheck manufacturer’s instructions. (2) A separate manually operated gas valve shall be pro vided at each automatic firecheck for shutting off the flow of the gas-air mixture through the firecheck after a flashback has occurred. The valve shall be located upstream as close as practical to the inlet of the automatic firecheck. Caution: These valves shall not be reopened after a flashback has occurred until the firecheck has cooled sufficiently to prevent re-ignition of the flammable mixture and has been reset properly. (3) A safety blowout or backfiring preventer shall be

h the firecheck after a flashback has occurred. The valve shall be located upstream as close as practical to the inlet of the automatic firecheck. Caution: These valves shall not be reopened after a flashback has occurred until the firecheck has cooled sufficiently to prevent re-ignition of the flammable mixture and has been reset properly. (3) A safety blowout or backfiring preventer shall be

provided in the mixture line near the outlet of each gas-mixing machine where the size of the piping is larger than 2 1 ⁄ 2 inches (65 mm) NPS, or equivalent, to protect the mixing equipment in the event of an explosion passing through an automatic firecheck. The manufacturer’s instructions shall be followed when installing these devices, particularly after a disc has burst. The discharge from the safety blowout or backfire preventer shall be located or shielded so that particles from the ruptured disc cannot be directed toward personnel. Wherever there are interconnected installations of gas-mixing machines with safety blowouts or backfire preventers, provision shall be made to keep the mixture from other machines from reaching any ruptured disc opening. Check valves shall not be used for this purpose. (4) Large-capacity premix systems provided with explo sion heads (rupture discs) to relieve excessive pressure in pipelines shall be located at and vented to a safe outdoor location. Provisions shall be provided for automatically shutting off the supply of the gas-air mixture in the event of rupture. [NFPA 54:7.11.6]

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — California Plumbing Code (Title 24, Part 5)
California Plumbing Code (Title 24, Part 5)
  1. Chapter 1 — GENERAL CODE PROVISIONS
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — GENERAL REGULATIONS
  4. Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
  5. Chapter 5 — WATER HEATERS
  6. Chapter 6 — WATER SUPPLY AND DISTRIBUTION
  7. Chapter 7 — SANITARY DRAINAGE
  8. Chapter 8 — INDIRECT WASTES
  9. Chapter 9 — VENTS
  10. Chapter 10 — TRAPS AND INTERCEPTORS
  11. Chapter 11 — STORM DRAINAGE
  12. Chapter 12 — FUEL GAS PIPING
    Overview
    1. 1201.1 Applicability. The regulations of this chapter shall
    2. 1202.1 General. Coverage of piping systems shall extend
    3. 1202.2 Piping System Requirements. Requirements for
    4. 1202.3 Applications. This code shall not apply to the followin…
    5. 1203.1 Inspection Notification. Upon completion of the
    6. 1203.2 Excavation. Excavations required for the installation o…
    7. 1203.3 Type of Inspections. The Authority Having Jurisdiction …
    8. 1203.4 Inspection Waived. In cases where the work
    9. 1204.1 Issuance. Whereupon final piping inspection, the
    10. 1204.2 Gas Supplier. A copy of the certificate of such final
    11. 1204.3 Unlawful. It shall be unlawful for a serving gas suppli…
    12. 1205.1 Authorized Personnel. It shall be unlawful for a
    13. 1205.2 Outlets. It shall be unlawful to turn on or connect gas
    14. 1206.1 Disconnection. The Authority Having Jurisdiction
    15. 1206.2 Notice. Where such disconnection has been made, a
    16. 1206.3 Capped Outlets. It shall be unlawful to remove or
    17. 1207.1 General. Where temporary use of gas is desired, and
    18. 1208.1 Installation of Piping System. Where required
    19. 1208.2 Provision for Location of Point of Delivery.
    20. 1208.3 Interconnections Between Gas Piping Sys-
    21. 1208.4 Sizing of Gas Piping Systems. Gas piping systems shall …
    22. 1208.5 Maximum Operating Pressure in Buildings.
    23. 1208.6 Acceptable Piping Materials and Joining
    24. 1208.7 Gas Meters. Gas meters shall be selected for the
    25. 1208.8 Gas Pressure Regulators. A line pressure regulator shal…
    26. 1208.9 Overpressure Protection Required. Where the
    27. 1208.10 Overpressure Protection Devices. Overpressure protecti…
    28. 1208.12 Backpressure Protection. Protective devices
    29. 1208.13 Low-Pressure Protection. A protective device
    30. 1208.11 Pressure Limitation Requirements. Where piping systems…
    31. 1208.14 Shutoff Valves. Shutoff valves shall be approved
    32. 1208.15 Expansion and Flexibility. Piping systems shall
    33. 1209.1 General. Where automatic excess flow valves are
    34. 1210.1 Piping Underground. Underground gas piping
    35. 1210.2 CSST Piping Systems. CSST piping systems shall
    36. 1210.3 Installation of Aboveground Piping. Piping
    37. 1210.5 Piping in Vertical Chases. Where gas piping
    38. 1210.4 Concealed Piping in Buildings. Gas piping in
    39. 1210.6 Gas Pipe Turns. Changes in direction of gas pipe
    40. 1210.7 Drips and Sediment Traps. For other than dry gas
    41. 1210.8 Outlets. Outlets shall be located and installed in
    42. 1210.9 Manual Gas Shutoff Valves. An accessible gas
    43. 1210.10 Prohibited Devices. Devices shall not be placed
    44. 1210.11 Systems Containing Gas-Air Mixtures Out-
    45. 1210.12 Systems Containing Flammable Gas-Air
    46. 1211.1 Pipe and Tubing Other than CSST. Each aboveground porti…
    47. 1211.2 Bonding of CSST Gas Piping. CSST gas piping
    48. 1211.3 Arc-Resistant Jacketed CSST. CSST listed with
    49. 1211.4 Prohibited Use. Gas piping shall not be used as a
    50. 1211.5 Lightning Protection System. Where a lightning
    51. 1211.6 Electrical Circuits. Electrical circuits shall not util…
    52. 1211.7 Electrical Connections. All electrical connections
    53. 1211.8 Earthquake-Actuated Gas Shutoff Valves. Earth-
    54. 1212.1 Connecting Appliances and Equipment.
    55. 1212.2 Suspended Low-Intensity Infrared Tube
    56. 1212.3 Use of Nonmetallic Gas Hose Connectors.
    57. 1212.4 Injection (Bunsen) Burners. Injection (Bunsen)
    58. 1212.5 Connection of Portable and Mobile Industrial
    59. 1212.6 Appliance Shutoff Valves and Connections.
    60. 1212.7 Quick-Disconnect Devices. Quick-disconnect
    61. 1212.8 Gas Convenience Outlets. Appliances shall be
    62. 1212.9 Sediment Trap. Where a sediment trap is not incorporate…
    63. 1212.10 Installation of Piping. Piping shall be installed in
    64. 1212.11 Liquefied Petroleum Gas Facilities and Pip-
    65. 1213.1 Piping Installations. Prior to acceptance and initial o…
    66. 1213.2 Test Preparation. Test preparation shall comply
    67. 1213.3 Test Pressure. This inspection shall include an air,
    68. 1213.4 Detection of Leaks and Defects. The piping system shall…
    69. 1213.5 Piping System Leak Test. Leak checks using fuel
    70. 1213.6 Purging Requirements. The purging of piping
    71. 1214.1 General. The following regulations shall comply
    72. 1214.2 Volume. The hourly volume of gas required at each
    73. 1214.3 Gas Appliances. Where the gas appliances to be
    74. 1214.4 Size of Piping Outlets. The size of the supply piping o…
    75. 1215.1 Pipe Sizing Methods. Where the pipe size is to be
    76. 1215.2 Sizing of Gas Piping Systems. Sizing of piping
    77. 1215.3 Sizing Equations. The inside diameter of smooth
    78. 1215.5 Engineering Methods. For conditions other than
    79. 1215.6 Variable Gas Pressure. Where the supply gas
    80. 1215.4 Sizing of Piping Sections. To determine the size
  13. Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
  14. Chapter 14 — FIRESTOP PROTECTION
  15. Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
  16. Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
  17. Chapter 17 — REFERENCED STANDARDS
  18. Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
  19. Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
  20. Appendix C — ALTERNATE PLUMBING SYSTEMS
  21. Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
  22. Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
  23. Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
  24. Appendix G — SIZING OF VENTING SYSTEMS
  25. Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
  26. Appendix I — INSTALLATION STANDARDS
  27. Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
  28. Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
  29. Appendix L — SUSTAINABLE PRACTICES
  30. Appendix M — PEAK WATER DEMAND CALCULATOR
  31. Appendix N — IMPACT OF WATER TEMPERATURE ON THE POTENTIAL FOR …

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.