1208.8 Gas Pressure Regulators.
California Plumbing Code (Title 24, Part 5) · 2022 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
A line pressure regulator shall be installed where the gas supply pressure exceeds the maximum allowable inlet pressure of the appliance served. [NFPA 54:5.8.1]
1208.8.1 Listing. Line pressure regulators shall be listed in accordance with CSA Z21.80 where the outlet pressure is set to 2 psi (14 kPa) or less. [NFPA 54:5.8.2] 1208.8.2 Location. The gas pressure regulator shall be accessible for servicing. [NFPA 54:5.8.3] 1208.8.3 Regulator Protection. Pressure regulators shall be protected against physical damage. [NFPA 54:5.8.4] 1208.8.4 Venting of Line Pressure Regulators. Line pressure regulators shall comply with all of the following: (1) An independent vent to the exterior of the building,
sized in accordance with the regulator manufacturer’s instructions, shall be provided where the location of a regulator is such that a ruptured diaphragm will cause a hazard. (a) Where more than one regulator is at a location,
each regulator shall have a separate vent to the outdoors or, if approved by the Authority Having Jurisdiction, the vent lines shall be permitted to be manifolded in accordance with accepted engineering practices to minimize back pressure in the event of diaphragm failure. (b) Materials for vent piping shall be in accordance
with Section 1208.6 through Section 1208.6.13.5.
FUEL GAS PIPING
Exception: A regulator and vent limiting means combination listed as complying with CSA Z21.80 shall be permitted to be used without a vent to the outdoors. (2) The vent shall be designed to prevent the entry of
water, insects, or other foreign materials that could cause blockage. (3) The regulator vent shall terminate at least 3 feet (914
mm) from a source of ignition. (4) At locations where regulators might be submerged
during floods, a special antiflood-type breather vent fitting shall be installed, or the vent line shall be extended above the height of the expected flood waters. (5) A regulator shall not be vented to the appliance flue
or exhaust system. [NFPA 54:5.8.5.1] 1208.8.5 Venting of Gas Appliance Pressure Regulators. For venting of gas appliance pressure regulators see Section 507.21. [NFPA 54:5.8.5.2] 1208.8.6 Bypass Piping. Valved and regulated bypasses shall be permitted to be placed around gas line pressure regulators where continuity of service is imperative. [NFPA 54:5.8.6] 1208.8.7 Identification. Line pressure regulators at multiple regulator installations shall be marked by a metal tag or other permanent means designating the building or the part of the building being supplied.
[NFPA 54:5.8.7]
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Plumbing Code (Title 24, Part 5)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
- Chapter 5 — WATER HEATERS
- Chapter 6 — WATER SUPPLY AND DISTRIBUTION
- Chapter 7 — SANITARY DRAINAGE
- Chapter 8 — INDIRECT WASTES
- Chapter 9 — VENTS
- Chapter 10 — TRAPS AND INTERCEPTORS
- Chapter 11 — STORM DRAINAGE
▸Chapter 12 — FUEL GAS PIPING
Overview- 1201.1 Applicability. The regulations of this chapter shall
- 1202.1 General. Coverage of piping systems shall extend
- 1202.2 Piping System Requirements. Requirements for
- 1202.3 Applications. This code shall not apply to the followin…
- 1203.1 Inspection Notification. Upon completion of the
- 1203.2 Excavation. Excavations required for the installation o…
- 1203.3 Type of Inspections. The Authority Having Jurisdiction …
- 1203.4 Inspection Waived. In cases where the work
- 1204.1 Issuance. Whereupon final piping inspection, the
- 1204.2 Gas Supplier. A copy of the certificate of such final
- 1204.3 Unlawful. It shall be unlawful for a serving gas suppli…
- 1205.1 Authorized Personnel. It shall be unlawful for a
- 1205.2 Outlets. It shall be unlawful to turn on or connect gas
- 1206.1 Disconnection. The Authority Having Jurisdiction
- 1206.2 Notice. Where such disconnection has been made, a
- 1206.3 Capped Outlets. It shall be unlawful to remove or
- 1207.1 General. Where temporary use of gas is desired, and
- 1208.1 Installation of Piping System. Where required
- 1208.2 Provision for Location of Point of Delivery.
- 1208.3 Interconnections Between Gas Piping Sys-
- 1208.4 Sizing of Gas Piping Systems. Gas piping systems shall …
- 1208.5 Maximum Operating Pressure in Buildings.
- 1208.6 Acceptable Piping Materials and Joining
- 1208.7 Gas Meters. Gas meters shall be selected for the
- 1208.8 Gas Pressure Regulators. A line pressure regulator shal…
- 1208.9 Overpressure Protection Required. Where the
- 1208.10 Overpressure Protection Devices. Overpressure protecti…
- 1208.12 Backpressure Protection. Protective devices
- 1208.13 Low-Pressure Protection. A protective device
- 1208.11 Pressure Limitation Requirements. Where piping systems…
- 1208.14 Shutoff Valves. Shutoff valves shall be approved
- 1208.15 Expansion and Flexibility. Piping systems shall
- 1209.1 General. Where automatic excess flow valves are
- 1210.1 Piping Underground. Underground gas piping
- 1210.2 CSST Piping Systems. CSST piping systems shall
- 1210.3 Installation of Aboveground Piping. Piping
- 1210.5 Piping in Vertical Chases. Where gas piping
- 1210.4 Concealed Piping in Buildings. Gas piping in
- 1210.6 Gas Pipe Turns. Changes in direction of gas pipe
- 1210.7 Drips and Sediment Traps. For other than dry gas
- 1210.8 Outlets. Outlets shall be located and installed in
- 1210.9 Manual Gas Shutoff Valves. An accessible gas
- 1210.10 Prohibited Devices. Devices shall not be placed
- 1210.11 Systems Containing Gas-Air Mixtures Out-
- 1210.12 Systems Containing Flammable Gas-Air
- 1211.1 Pipe and Tubing Other than CSST. Each aboveground porti…
- 1211.2 Bonding of CSST Gas Piping. CSST gas piping
- 1211.3 Arc-Resistant Jacketed CSST. CSST listed with
- 1211.4 Prohibited Use. Gas piping shall not be used as a
- 1211.5 Lightning Protection System. Where a lightning
- 1211.6 Electrical Circuits. Electrical circuits shall not util…
- 1211.7 Electrical Connections. All electrical connections
- 1211.8 Earthquake-Actuated Gas Shutoff Valves. Earth-
- 1212.1 Connecting Appliances and Equipment.
- 1212.2 Suspended Low-Intensity Infrared Tube
- 1212.3 Use of Nonmetallic Gas Hose Connectors.
- 1212.4 Injection (Bunsen) Burners. Injection (Bunsen)
- 1212.5 Connection of Portable and Mobile Industrial
- 1212.6 Appliance Shutoff Valves and Connections.
- 1212.7 Quick-Disconnect Devices. Quick-disconnect
- 1212.8 Gas Convenience Outlets. Appliances shall be
- 1212.9 Sediment Trap. Where a sediment trap is not incorporate…
- 1212.10 Installation of Piping. Piping shall be installed in
- 1212.11 Liquefied Petroleum Gas Facilities and Pip-
- 1213.1 Piping Installations. Prior to acceptance and initial o…
- 1213.2 Test Preparation. Test preparation shall comply
- 1213.3 Test Pressure. This inspection shall include an air,
- 1213.4 Detection of Leaks and Defects. The piping system shall…
- 1213.5 Piping System Leak Test. Leak checks using fuel
- 1213.6 Purging Requirements. The purging of piping
- 1214.1 General. The following regulations shall comply
- 1214.2 Volume. The hourly volume of gas required at each
- 1214.3 Gas Appliances. Where the gas appliances to be
- 1214.4 Size of Piping Outlets. The size of the supply piping o…
- 1215.1 Pipe Sizing Methods. Where the pipe size is to be
- 1215.2 Sizing of Gas Piping Systems. Sizing of piping
- 1215.3 Sizing Equations. The inside diameter of smooth
- 1215.5 Engineering Methods. For conditions other than
- 1215.6 Variable Gas Pressure. Where the supply gas
- 1215.4 Sizing of Piping Sections. To determine the size
- Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
- Chapter 14 — FIRESTOP PROTECTION
- Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
- Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
- Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
- Appendix C — ALTERNATE PLUMBING SYSTEMS
- Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
- Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
- Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
- Appendix G — SIZING OF VENTING SYSTEMS
- Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
- Appendix I — INSTALLATION STANDARDS
- Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
- Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
- Appendix L — SUSTAINABLE PRACTICES
- Appendix M — PEAK WATER DEMAND CALCULATOR
- Appendix N — IMPACT OF WATER TEMPERATURE ON THE POTENTIAL FOR …