Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
1504.5 Irrigation, Disposal Field and Mulch Basin Con-struction.
California Plumbing Code (Title 24, Part 5) · 2019 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
Irrigation fields, disposal fields and mulch basins used in gray water systems shall comply with this section. Gray water systems may contain either an irrigation field or a dis- posal field or a combination of both. This section is not intended to prevent the use of other methods of gray water irri- gation or disposal approved by the Enforcing Agency.
1504.5.1 Mulch Basin. A mulch basin may be used as an irrigation or disposal field. Mulch basins shall be sized in accordance with Table 1504.2 and of sufficient depth, length and width to prevent ponding or runoff dur- ing the gray water surge of a clothes washer, bathtub or shower. Mulch must be replenished as required due to decomposition of organic matter. Mulch basins will require periodic maintenance, reshaping or removal of dirt to maintain surge capacity and to accommodate plant growth and prevent ponding or runoff. 1504.5.2 Irrigation Field. The provisions of this section are not intended to prevent the use of any appropriate material, appliance, installation, device, design or method of construction. If an alternate design is not available, the following provisions may be used as guidance in the design of a gray water irrigation field: (1) Filters used in gray water irrigation systems shall
be as specified by the manufacturer’s installation
(1) Filters used in gray water irrigation systems shall
be as specified by the manufacturer’s installation instructions for the design flow rate and intended use. The filter backwash and flush discharge shall be contained and disposed of into the building sewer system, septic tank or, with approval of the Enforc- ing Agency, a separate mini-leachfield sized to accept all the backwash and flush discharge water. Filter backwash water and flush water shall not be used for any purpose. Sanitary procedures shall be followed when handling filter backwash and flush discharge or gray water. (2) Emitters shall be designed to resist root intrusion
and shall be of a design recommended by the man-
Emitters shall be designed to resist root intrusion
and shall be of a design recommended by the man- ufacturer for the intended gray water flow and use.
2019 CALIFORNIA PLUMBING CODE 317
ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS any other purpose or distributed to any other persons or parties.
For emitter ratings, refer to Irrigation Equipment Performance Report, Drip Emitters and Micro- Sprinklers, Center for Irrigation Technology, Cali- fornia State University, 5730 N. Chestnut Avenue, Fresno, California 93740-0018. (3) Each irrigation zone shall be designed to include no
less than the number of emitters specified in Table
(3) Each irrigation zone shall be designed to include no
less than the number of emitters specified in Table 1504.5, or through a procedure designated by the Enforcing Agency. Minimum spacing between emit- ters in any direction shall be sufficient to prevent surfacing or runoff. (4) The system design shall provide user controls, such
as valves, switches, timers and other controllers, as
(C) Disposal fields shall be constructed in accordance
with Table 1504.5.3. (D) When necessary on sloping ground to prevent exces-
sive line slopes, disposal lines shall be stepped or
(4) The system design shall provide user controls, such
as valves, switches, timers and other controllers, as appropriate, to rotate the distribution of gray water between irrigation zones. (5) All drip irrigation supply lines shall be polyethylene
tubing or PVC Class 200 pipe or better and Sched-
be laid on the filter material in an approved manner. The perforated section shall then be covered with fil- ter material to the minimum depth required by this section. The filter material shall then be covered with untreated building paper, straw, or similar porous material to prevent closure of voids with earth back- fill. No earth backfill shall be placed over the filter material cover until after inspection and acceptance. Exception: Manufactured leaching chambers shall be installed in compliance with the manufacturer’s installation instructions. (C) Disposal fields shall be constructed in accordance
with Table 1504.5.3.
« « «
(5) All drip irrigation supply lines shall be polyethylene
tubing or PVC Class 200 pipe or better and Sched- ule 40 fittings. All joints shall be pressure tested at 40 psi (276 kPa), and shown to be drip tight for five min- utes, before burial. All supply piping shall be cov- ered to a minimum depth of two (2) inches (51 mm) of mulch or soil. Drip feeder lines can be poly or flex- ible PVC tubing and shall be covered to a minimum depth of two (2) inches (51 mm) of mulch or soil. (6) Where pressure at the discharge side of the pump
exceeds 20 psi (138 kPa), a pressure-reducing valve
When necessary on sloping ground to prevent exces-
sive line slopes, disposal lines shall be stepped or installed on the contour lines of the slope. The lines between each horizontal leaching section shall be made with approved water-tight joints and installed on natural or unfilled ground.
TABLE 1504.5.3 SUBSOIL IRRIGATION FIELD CONSTRUCTION
(6) Where pressure at the discharge side of the pump
exceeds 20 psi (138 kPa), a pressure-reducing valve able to maintain downstream pressure no greater than the maximum operating pressure of the installed tubing, emitters, or other components shall be installed downstream from the pump and before any emission device. (7) When an irrigation system utilizes a pump, and dis-
charges water at a point higher than the pump, a
(7) When an irrigation system utilizes a pump, and dis-
charges water at a point higher than the pump, a backwater valve shall be installed downstream of the pump to prevent back siphonage of water and soil. 1504.5.3 Disposal Field. The provisions of this sec- tion are not intended to prevent the use of any appropri- ate material, appliance, installation, device, design or method of construction. If an alternate design is not available, the following provisions may be used as guid- ance in the design of a gray water disposal field: (A) Disposal systems shall be not less than three (3)
inches (80 mm) in cross sectional dimension and
| DESCRIPTION | MINIMUM | MAXIMUM |
|---|---|---|
zone_1_ |
||
lines |
||
lines_1_ |
||
100 feet |
83.3 mm/m 1 Manufactured leaching chambers shall be installed in compliance with the manufacturer’s installation instructions.
(A) Disposal systems shall be not less than three (3)
inches (80 mm) in cross sectional dimension and shall be constructed of perforated high-density poly- ethylene pipe, perforated ABS pipe, perforated PVC pipe, leaching chambers or other approved materi- als, provided that sufficient openings are available for distribution of the gray water into the trench area. Material, construction, and perforation shall be in compliance with the appropriate absorption field’s drainage standards and shall be approved by the Enforcing Agency. (B) Filter material, clean stone, gravel, slag, or similar
filter material acceptable to the Enforcing Agency,
Filter material, clean stone, gravel, slag, or similar
filter material acceptable to the Enforcing Agency, varying in size from three-quarter ( 3 ⁄4) inch (19.1 mm) to two and one-half (2 1 ⁄2) inches (64 mm) shall be placed in the trench to the depth and grade required by this section. The perforated section shall
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Plumbing Code (Title 24, Part 5)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
- Chapter 5 — WATER HEATERS
- Chapter 6 — WATER SUPPLY AND DISTRIBUTION
- Chapter 7 — SANITARY DRAINAGE
- Chapter 8 — INDIRECT WASTES
- Chapter 9 — VENTS
- Chapter 10 — TRAPS AND INTERCEPTORS
- Chapter 11 — STORM DRAINAGE
- Chapter 12 — FUEL GAS PIPING
- Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
- Chapter 14 — FIRESTOP PROTECTION
▸Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
Overview- 1501.0 General.1501.1 Applicability [BSC-CG, DWR & HCD 1]. The
- 1501.2 System Design. Alternate water source systems
- 1501.3 Permit [BSC-CG, HCD 1, DWR]. It shall be unlawful for a…
- 1501.4 Component Identification. System components
- 1501.5 Maintenance and Inspection 1, DWR]. Alternate water sou…
- 1501.6 Operation and Maintenance Manual [BSC-
- 1501.7 Minimum Water Quality Requirements [BSC-
- 1501.8 Material Compatibility. Alternate water source systems …
- 1501.9 Signage [BSC-CG, HCD 1, HCD 2, HCD 1-AC, &DWR]. Signage…
- 1501.10 System Controls. Controls for pumps, valves, and
- 1501.11 Hose Bibbs for Single-Family Dwellings [HCD1]. Hose bi…
- 1502.2 Supply System Inspection and Test. Alternate
- 1502.3 Cross-Connection Inspection and Testing. An
- 1502.6 Sizing. Unless otherwise provided for in this chapter, …
- 1503.1 General. The provisions of this section shall apply
- 1502.4 Separation Requirements. Underground alternate
- 1502.5 Abandonment. Alternate water source systems that
- 1503.2 System Requirements. Gray water shall be permitted to b…
- 1503.3 Connections to Potable and Reclaimed(Recycled) Water Sy…
- 1503.4 Location. No gray water system or part thereof shall
- 1503.5 Plot Plan Submission. No permit for a gray water
- 1503.6 Prohibited Location. Where there is insufficient
- 1503.7 Drawings and Specifications. The Authority
- 1503.9 Gray Water System Components. Gray water
- 1504.2 Required Area of Subsurface Irrigation
- 1504.3 Determination of Maximum Absorption Capac-
- 1504.4 Groundwater Level. No excavation for an irrigation fiel…
- 1504.5 Irrigation, Disposal Field and Mulch Basin Con-structio…
- 1504.6 Reserved.
- 1504.7 Reserved.
- 1504.8 Gray Water System Color and Marking Infor-mation. Press…
- 1504.9 Other Collection and Distribution Systems. Other collec…
- 1504.10 Testing. Building drains and vents for gray water
- 1504.11 Maintenance. Gray water systems and components shall b…
- 1505.0 Recycled Water 1505.1 General. The provisions of Supply…
- 1505.3 System Changes. No changes or connections shall
- 1505.4 Connections to Potable or Reclaimed (Recy-cled) Water S…
- 1505.2 Permit. It shall be unlawful for a person to construct,
- 1505.5 Initial Cross-Connection Test. A cross-connection test …
- 1505.6 Recycled Water Recycled water supply system materials s…
- 1505.8 Valves. Valves, except fixture supply control valves,
- 1505.9 Hose Bibbs. Hose bibbs shall not be allowed on
- 1505.10 Required Appurtenances. The recycled water
- 1505.11 Pipe Separation in Trenches. Reclaimed (recycled) wate…
- 1505.12 Signage. Signs in rooms and water closet tanks in
- 1505.13 Inspection and Testing. Recycled water supply
- 1505.15 Maintenance and Inspection. Recycled water
- 1506.0 On-Site Treated Nonpotable Gray Water Sys-
- 1506.2 Plumbing Plan Submission. No permit for an
- 1506.3 System Changes. No changes or connections shall
- 1506.4 Connections to Potable or Reclaimed (Recy-
- 1506.5 Initial Cross-Connection Test. A cross-connection test …
- 1506.6 On-Site Treated Nonpotable tem Materials. On-site treat…
- 1506.7 On-Site Treated Nonpotable Devices and Systems. Devices…
- 1506.9 Design and Installation. The design and installation of…
- 1506.10 Valves. Valves, except fixture supply control
- 1506.11 Signs. Signs in buildings using on-site treated nonpot…
- 1506.12 Inspection and Testing. On-site treated nonpotable gra…
- Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
- Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
- Appendix C — ALTERNATE PLUMBING SYSTEMS
- Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
- Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
- Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
- Appendix G — SIZING OF VENTING SYSTEMS
- Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
- Appendix I — INSTALLATION STANDARD FOR PEX TUBING SYSTEMS FOR …
- Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
- Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
- Appendix L — SUSTAINABLE PRACTICES
- Appendix M — PEAK WATER DEMAND CALCULATOR