509.6 Gas Vents. The installation of gas vents shall meet

California Plumbing Code (Title 24, Part 5) · 2025 edition · updated 2026-09-10 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

the following requirements:

(1) Gas vents shall be installed in accordance with the manufacturer’s installation instructions.

(2) A Type B-W gas vent shall have a listed capacity not less than that of the listed vented wall furnace to which it is

connected.

(3) Gas vents installed within masonry chimneys shall be installed in accordance with the manufacturer’s installation instructions. Gas vents installed within masonry

94 2025 CALIFORNIA PLUMBING CODE

WATER HEATERS

chimneys shall be identified with a permanent label installed at the point where the vent enters the chimney. The label shall contain the following language: “This gas vent is for appliances that burn gas. Do not connect to solid or liquid fuel–burning appliances or incinerators.”

(4) Screws, rivets, and other fasteners shall not penetrate the inner wall of double-wall gas vents, except at the transition from the appliance draft hood outlet, flue collar, or single-wall metal connector to a double-wall vent.

[NFPA 54:12.7.2]

509.6.1 Gas Vent Termination. The termination of gas vents shall comply with the following requirements:

(1) A gas vent shall terminate in accordance with one of the following:

(a) Gas vents that are 12 inches (300 mm) or less in size and located not less than 8 feet (2438 mm) from a vertical wall or similar obstruction shall

terminate above the roof in accordance with Figure 509.6.1 and Table 509.6.1.

(b) Gas vents that are over 12 inches (300 mm) in size or are located less than 8 feet (2438 mm) from a vertical wall or similar obstruction shall terminate not less than 2 feet (610 mm) above the highest point where they pass through the roof and not less than 2 feet (610 mm) above any portion of a building within 10 feet (3048 mm) horizontally.

(c) Industrial appliances as provided in Section 509.2.5.

(d) Direct-vent systems as provided in Section 509.2.6.

(e) Appliances with integral vents as provided in Section 509.2.7.

(f) Mechanical draft systems as provided in Section 509.3.3 through Section 509.3.3.4.

(g) Ventilating hoods and exhaust systems as provided in Section 509.3.4.

(2) A Type B or a Type L gas vent shall terminate at least 5 feet (1524 mm) in vertical height above the highest connected appliance draft hood or flue collar.

(3) A Type B-W gas vent shall terminate at least 12 feet (3658 mm) in vertical height above the bottom of the wall furnace.

(4) A gas vent extending through an exterior wall shall not terminate adjacent to the wall or below eaves or parapets, except as provided in Section 509.2.6 and Section 509.3.3 through Section 509.3.3.4.

(5) Decorative shrouds shall not be installed at the termination of gas vents except where such shrouds are listed for use with the specific gas venting system and are installed in accordance with the manufac turer’s installation instructions.

(6) All gas vents shall extend through the roof flashing, roof jack, or roof thimble and terminate with a listed cap or listed roof assembly.

(7) A gas vent shall terminate at least 3 feet (914 mm) above a forced air inlet located within 10 feet (3048 mm). [NFPA 54:12.7.3]

FIGURE 509.6.1

TERMINATION LOCATIONS FOR GAS

VENTS WITH LISTED CAPS 12 INCHES OR LESS IN SIZE

AT LEAST 8 FEET FROM A VERTICAL WALL

[NFPA 54: FIGURE 12.7.3]

TABLE 509.6.1

ROOF SLOPE HEIGHTS

[NFPA 54: TABLE 12.7.3]

ROOF SLOPE H (minimum) (feet)


Flat to6⁄12
1.0

Over6⁄12 to7⁄12
1.25

Over7⁄12 to8⁄12
1.5

Over8⁄12 to9⁄12
2.0

Over9⁄12 to10⁄12
2.5

Over10⁄12 to11⁄12
3.25

Over11⁄12 to12⁄12
4.0

Over12⁄12 to14⁄12
5.0

Over14⁄12 to16⁄12
6.0

Over16⁄12 to18⁄12
7.0

Over18⁄12 to20⁄12
7.5

Over20⁄12 to21⁄12
8.0

For SI Units: 1 inch = 25.4 mm, 1 foot = 304.8 mm

509.6.1.1 Insulation Protection Shield. Where a vent passes through an insulated assembly, an approved metal shield constructed of steel having a thickness of not less than 26 gauge (0.0179 inch) (0.45 mm) (No. 26 gauge) shall be installed between the vent and insulation. The shield shall extend not less than 2 inches (51 mm) above the insulation and be secured to the structure in accordance with the

manufacturer’s installation instructions.

509.6.2 Size of Gas Vents. Venting systems shall be sized and constructed in accordance with Section

WATER HEATERS

509.6.2.1 through Section 509.6.2.3 and the appliance manufacturer’s instructions. [NFPA 54:12.7.4] 509.6.2.1 Category I Appliances. The sizing of natural draft venting systems serving one or more listed appliances equipped with a draft hood or appliances listed for use with a Type B gas vent, installed in a single story of a building, shall be in accordance with one of the following:

(1) The provisions of Section 510.0.

(2) Vents serving fan-assisted combustion system appliances, or combinations of fan-assisted combustion system and draft hood-equipped appliances, shall be sized in accordance with Section 510.0 or other engineering methods.

(3) For sizing an individual gas vent for a single, draft hood-equipped appliance, the effective area of the vent connector and the gas vent shall be not less than the area of the appliance draft hood outlet or greater than seven times the draft hood outlet area.

(4) For sizing a gas vent connected to two appliances with draft hoods, the effective area of the vent shall be not less than the area of the larger draft hood outlet plus 50 percent of the area of the smaller draft hood outlet or greater than seven times the smaller draft hood outlet area.

(5) Engineering methods. [NFPA 54:12.7.4.1] 509.6.2.2 Vent Offsets. Type B and Type L vents sized in accordance with Section 509.6.2.1(3) or Section 509.6.2.1(4) shall extend in a generally vertical direction with offsets not exceeding 45 degrees (0.79 rad), except that a vent system having not more than one 60 degree (1.05 rad) offset shall be permitted. Any angle greater than 45 degrees (0.79 rad) from the vertical is considered horizontal. The total horizontal distance of a vent plus the horizontal vent connector serving draft hood-equipped appliances shall not be greater than 75 percent of the vertical height of the vent. [NFPA 54:12.7.4.2] 509.6.2.3 Category II, Category III, and Cate- gory IV Appliances. The sizing of gas vents for Category II, Category III, and Category IV appliances shall be in accordance with the appliance manufacturers’ instructions. The sizing of plastic pipe specified by the appliance manufacturer as a venting material for Category II, III, and IV appliances shall be in accordance with the appliance manufacturers’ instructions. [NFPA 54:12.7.4.3] 509.6.2.4 Sizing. Chimney venting systems using mechanical draft shall be sized in accordance with engineering methods. [NFPA 54:12.7.4.4] 509.6.3 Gas Vents Serving Appliances on More than One Floor. Where a common vent is installed in a multistory installation to vent Category I appliances located on more than one floor level, the venting system shall be designed and installed in accordance with engineering methods. Crawl spaces, basements, and attics shall be considered as floor levels. [NFPA 54:12.7.5.1]

509.6.3.1 Occupiable Space. All appliances connected to the common vent shall be located in rooms separated from occupiable space. Each of these rooms shall have provisions for an adequate supply of combustion, ventilation, and dilution air that is not supplied from occupiable space. [NFPA 54:12.7.5.2] (See Figure 509.6.3.1)

FIGURE 509.6.3.1

PLAN VIEW OF PRACTICAL SEPARATION

METHOD FOR MULTISTORY GAS VENTING

[NFPA 54: FIGURE A.12.7.5.2]

509.6.3.2 Multistory Venting System. The size of the connectors and common segments of multistory venting systems for appliances listed for use with a Type B double-wall gas vent shall be in accordance with Table 510.2(1), provided all of the following apply:

(1) The available total height ( H ) for each segment of a multistory venting system is the vertical distance between the level of the highest draft hood outlet or flue collar on that floor and the centerline of the next highest interconnection

tee.

(2) The size of the connector for a segment is determined from the appliance’s gas input rate and available connector rise and shall not be smaller

than the draft hood outlet or flue collar size.

(3) The size of the common vertical vent segment, and of the interconnection tee at the base of that segment, is based on the total appliance’s gas input rate entering that segment and its available total height. [NFPA 54:12.7.5.3]

509.6.4 Support of Gas Vents. Gas vents shall be supported and spaced in accordance with the manufacturer’s installation instructions. [NFPA 54:12.7.6]

509.6.5 Marking. In those localities where solid and liquid fuels are used extensively, gas vents shall be per

96 2025 CALIFORNIA PLUMBING CODE

WATER HEATERS

manently identified by a label attached to the wall or ceiling at a point where the vent connector enters the gas vent. The label shall read: “This gas vent is for appliances that burn gas. Do not connect to solid or liquid fuel-burning appliances or incinerators.” The Authority Having Jurisdiction shall determine whether its area constitutes such a locality. [NFPA 54:12.7.7]

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — California Plumbing Code (Title 24, Part 5)
California Plumbing Code (Title 24, Part 5)
  1. Chapter 1 — GENERAL CODE PROVISIONS
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — GENERAL REGULATIONS
  4. Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
  5. Chapter 5 — WATER HEATERS
    Overview
    1. 501.1 Applicability. The regulations of this chapter shall gov…
    2. 501.2 California Energy Code Water Heating System
    3. 502.1 General. It shall be unlawful for a person to install,
    4. 503.1 Inspection of Chimneys or Vents. This inspection shall b…
    5. 503.2 Final Water Heater Inspection. This inspection
    6. 504.1 Location. Water heater installations in bedrooms and
    7. 504.2 Vent. Water heaters of other than the direct-vent type
    8. 504.3 Clearance. The clearance requirements for water
    9. 504.4 Pressure-Limiting Devices. A water heater installation s…
    10. 504.5 Temperature Limiting Devices. A water heater
    11. 504.6 Temperature, Pressure, and Vacuum Relief
    12. 504.7 Lead Content. Water heaters shall comply with the
    13. 505.1 Water Heaters. Water heaters deriving heat from
    14. 505.2 Safety Devices. Storage-type water heaters and hot
    15. 505.3 Oil-Fired Water Heaters. Oil-fired water heaters
    16. 505.4 Indirect-Fired Water Heaters. Indirect-fired water
    17. 506.1 General. Air for combustion, ventilation, and dilution o…
    18. 506.2 Indoor Combustion Air. The required volume of
    19. 506.3 Indoor Opening Size and Location. Openings
    20. 506.4 Outdoor Combustion Air. Outdoor combustion air
    21. 506.5 Combination Indoor and Outdoor Combustion
    22. 506.6 Engineered Installations. Engineered combustion
    23. 506.7 Mechanical Combustion Air Supply. Where all
    24. 506.8 Louvers, Grilles, and Screens. The required size
    25. 506.9 Combustion Air Ducts. Combustion air ducts shall
    26. 507.1 Dielectric Insulator. The Authority Having Jurisdiction …
    27. 507.2 Seismic Provisions. Water heaters shall be
    28. 507.3 Appliance Support. Appliances and equipment shall
    29. 507.4 Ground Support. A water heater supported from the
    30. 507.5 Drainage Pan. Where a water heater is located in an
    31. 507.6 Added or Converted Equipment or Appliances.
    32. 507.7 Type of Gas(es). The appliance shall be connected to
    33. 507.8 Safety Shutoff Devices for Unlisted LP-Gas
    34. 507.9 Use of Air or Oxygen Under Pressure. Where air
    35. 507.10 Protection of Gas Appliances from Fumes or
    36. 507.11 Process Air. In addition to air needed for combustion i…
    37. 507.12 Flammable Vapors. Appliances shall not be
    38. 507.13 Installation in Residential Garages. Appliances
    39. 507.14 Installation in Commercial Garages. Appliances
    40. 507.15 Installation in Aircraft Hangars. Heaters in aircraft h…
    41. 507.16 Venting of Flue Gases. Appliances shall be vented
    42. 507.17 Extra Device or Attachment. No device or attachment sha…
    43. 507.18 Addition to Existing System. When additional
    44. 507.19 Avoiding Strain on Gas Piping. Appliances shall
    45. 507.20 Gas Appliance Pressure Regulators. Where the
    46. 507.21 Bleed Lines for Diaphragm-Type Valves. Bleed
    47. 508.2 Installation of Appliances on Roofs. Appliances
    48. 508.3 Appliances on Roofs. Appliances located on roofs or
    49. 507.22 Combination of Appliances and Equipment.
    50. 507.23 Installation Instructions. The installer shall conform …
    51. 507.24 Protection of Outdoor Appliances. Appliances
    52. 507.25 Accessibility for Service. All appliances shall be
    53. 507.26 Clearance to Combustible Materials. Appliances and thei…
    54. 508.1 General. Appliances on roofs shall be designed or
    55. 508.4 Appliances in Attics and Under-Floor Spaces.
    56. 509.1 Listing. Type B and Type B-W gas vents shall comply
    57. 509.2 Connection to Venting Systems. Except as permitted in Se…
    58. 509.3 Minimum Safe Performance. Venting systems
    59. 509.4 Type of Venting System to be Used. The type of
    60. 509.5 Masonry, Metal, and Factory-Built Chimneys.
    61. 509.6 Gas Vents. The installation of gas vents shall meet
    62. 509.7 Single-Wall Metal Pipe. Single-wall metal pipe
    63. 509.9 Condensation Drain. Provision shall be made to
    64. 509.10 Vent Connectors for Category I Appliances.
    65. 509.8 Through-the-Wall Vent Termination. Throughthe-wall vent …
    66. 509.13 Manually Operated Dampers. A manually operated damper s…
    67. 509.14 Automatically Operated Vent Dampers. An
    68. 509.15 Obstructions. Devices that retard the flow of vent
    69. 510.1 Additional Requirements to Single Appliance
    70. 509.11 Vent Connectors for Category II, Category III,
    71. 509.12 Appliances Requiring Draft Hoods. Vented
    72. 510.2 Additional Requirements to Multiple-Appliance
  6. Chapter 6 — WATER SUPPLY AND DISTRIBUTION
  7. Chapter 7 — SANITARY DRAINAGE
  8. Chapter 8 — INDIRECT WASTES
  9. Chapter 9 — VENTS
  10. Chapter 10 — TRAPS AND INTERCEPTORS
  11. Chapter 11 — STORM DRAINAGE
  12. Chapter 12 — FUEL GAS PIPING
  13. Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
  14. Chapter 14 — FIRESTOP PROTECTION
  15. Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
  16. Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
  17. Chapter 17 — REFERENCED STANDARDS
  18. Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
  19. Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
  20. Appendix C — ALTERNATE PLUMBING SYSTEMS
  21. Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
  22. Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
  23. Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
  24. Appendix G — SIZING OF VENTING SYSTEMS
  25. Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
  26. Appendix I — INSTALLATION STANDARDS
  27. Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
  28. Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
  29. Appendix L — SUSTAINABLE PRACTICES
  30. Appendix M — PEAK WATER DEMAND CALCULATOR
  31. Appendix N — IMPACT OF WATER TEMPERATURE ON THE POTENTIAL FOR …
  32. Appendix O — NON-SEWERED SANITATION SYSTEMS
  33. Appendix P — PROFESSIONAL QUALIFICATIONS
  34. Appendix Q — INDOOR HORTICULTURAL FACILITIES
  35. Appendix R — TINY HOUSES
  36. Appendix S — ONSITE STORMWATER TREATMENT SYSTEMS

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.