509.3 Minimum Safe Performance. Venting systems
California Plumbing Code (Title 24, Part 5) · 2025 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
shall be designed and constructed to convey all flue and vent gases to the outdoors. [NFPA 54:12.1] 509.3.1 Appliance Draft Requirements. A venting system shall satisfy the draft requirements of the appliance in accordance with the manufacturer’s instructions.
[NFPA 54:12.4.1]
509.3.2 Appliance Venting Requirements. Appliances required to be vented shall be connected to a venting system designed and installed in accordance with the provisions of Section 509.4 through Section 509.15.
[NFPA 54:12.4.2] 509.3.3 Mechanical Draft Systems. Mechanical draft systems shall be listed in accordance with UL 378 and installed in accordance with both the appliance and the mechanical draft system manufacturer’s installation instructions. [NFPA 54:12.4.3.1]
WATER HEATERS
509.3.3.1 Venting. Appliances requiring venting shall be permitted to be vented by means of mechanical draft systems of either forced or induced draft design. [NFPA 54:12.4.3.2]
509.3.3.2 Leakage. Forced draft systems and all portions of induced draft systems under positive pressure during operation shall be designed and installed so as to prevent leakage of flue or vent gases into a building. [NFPA 54:12.4.3.3]
509.3.3.3 Vent Connectors. Vent connectors serving appliances vented by natural draft shall not be connected into any portion of mechanical draft systems operating under positive pressure. [NFPA 54:12.4.3.4]
509.3.3.4 Operation. Where a mechanical draft system is employed, provision shall be made to prevent the flow of gas to the main burners when the draft system is not performing so as to satisfy the operating requirements of the appliance for safe performance. [NFPA 54:12.4.3.5]
509.3.4 Ventilating Hoods and Exhaust Systems. Where automatically operated appliances, other than food service appliances, are vented through a ventilating hood or exhaust system equipped with a damper or with a power means of exhaust, provisions shall be made to allow the flow of gas to the main burners only when the damper is open to a position to properly vent the appliance and when the power means of exhaust is in operation. [NFPA 54:12.4.4.1]
509.3.5 Circulating Air Ducts, Above-Ceiling Air- Handling Spaces, and Furnace Plenums. Venting systems shall not extend into or pass through any fabricated air duct or furnace plenum. [NFPA 54:12.4.5.1] 509.3.6 Above-Ceiling or Nonducted Air Han- dling System. Where a venting system passes through an above-ceiling air space or other nonducted portion of an air-handling system, it shall conform to one of the following requirements:
(1) The venting system shall be a listed special gas vent, other system serving a Category III or Category IV appliance, or other positive pressure vent, with joints sealed in accordance with the appliance or vent manufacturer’s instructions.
(2) The vent system shall be installed such that no fittings or joints between sections are installed in the above-ceiling space.
(3) The venting system shall be installed in a conduit or enclosure with joints between the interior of the enclosure and the ceiling space sealed. [NFPA 54:12.4.5.2]
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Plumbing Code (Title 24, Part 5)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
▸Chapter 5 — WATER HEATERS
Overview- 501.1 Applicability. The regulations of this chapter shall gov…
- 501.2 California Energy Code Water Heating System
- 502.1 General. It shall be unlawful for a person to install,
- 503.1 Inspection of Chimneys or Vents. This inspection shall b…
- 503.2 Final Water Heater Inspection. This inspection
- 504.1 Location. Water heater installations in bedrooms and
- 504.2 Vent. Water heaters of other than the direct-vent type
- 504.3 Clearance. The clearance requirements for water
- 504.4 Pressure-Limiting Devices. A water heater installation s…
- 504.5 Temperature Limiting Devices. A water heater
- 504.6 Temperature, Pressure, and Vacuum Relief
- 504.7 Lead Content. Water heaters shall comply with the
- 505.1 Water Heaters. Water heaters deriving heat from
- 505.2 Safety Devices. Storage-type water heaters and hot
- 505.3 Oil-Fired Water Heaters. Oil-fired water heaters
- 505.4 Indirect-Fired Water Heaters. Indirect-fired water
- 506.1 General. Air for combustion, ventilation, and dilution o…
- 506.2 Indoor Combustion Air. The required volume of
- 506.3 Indoor Opening Size and Location. Openings
- 506.4 Outdoor Combustion Air. Outdoor combustion air
- 506.5 Combination Indoor and Outdoor Combustion
- 506.6 Engineered Installations. Engineered combustion
- 506.7 Mechanical Combustion Air Supply. Where all
- 506.8 Louvers, Grilles, and Screens. The required size
- 506.9 Combustion Air Ducts. Combustion air ducts shall
- 507.1 Dielectric Insulator. The Authority Having Jurisdiction …
- 507.2 Seismic Provisions. Water heaters shall be
- 507.3 Appliance Support. Appliances and equipment shall
- 507.4 Ground Support. A water heater supported from the
- 507.5 Drainage Pan. Where a water heater is located in an
- 507.6 Added or Converted Equipment or Appliances.
- 507.7 Type of Gas(es). The appliance shall be connected to
- 507.8 Safety Shutoff Devices for Unlisted LP-Gas
- 507.9 Use of Air or Oxygen Under Pressure. Where air
- 507.10 Protection of Gas Appliances from Fumes or
- 507.11 Process Air. In addition to air needed for combustion i…
- 507.12 Flammable Vapors. Appliances shall not be
- 507.13 Installation in Residential Garages. Appliances
- 507.14 Installation in Commercial Garages. Appliances
- 507.15 Installation in Aircraft Hangars. Heaters in aircraft h…
- 507.16 Venting of Flue Gases. Appliances shall be vented
- 507.17 Extra Device or Attachment. No device or attachment sha…
- 507.18 Addition to Existing System. When additional
- 507.19 Avoiding Strain on Gas Piping. Appliances shall
- 507.20 Gas Appliance Pressure Regulators. Where the
- 507.21 Bleed Lines for Diaphragm-Type Valves. Bleed
- 508.2 Installation of Appliances on Roofs. Appliances
- 508.3 Appliances on Roofs. Appliances located on roofs or
- 507.22 Combination of Appliances and Equipment.
- 507.23 Installation Instructions. The installer shall conform …
- 507.24 Protection of Outdoor Appliances. Appliances
- 507.25 Accessibility for Service. All appliances shall be
- 507.26 Clearance to Combustible Materials. Appliances and thei…
- 508.1 General. Appliances on roofs shall be designed or
- 508.4 Appliances in Attics and Under-Floor Spaces.
- 509.1 Listing. Type B and Type B-W gas vents shall comply
- 509.2 Connection to Venting Systems. Except as permitted in Se…
- 509.3 Minimum Safe Performance. Venting systems
- 509.4 Type of Venting System to be Used. The type of
- 509.5 Masonry, Metal, and Factory-Built Chimneys.
- 509.6 Gas Vents. The installation of gas vents shall meet
- 509.7 Single-Wall Metal Pipe. Single-wall metal pipe
- 509.9 Condensation Drain. Provision shall be made to
- 509.10 Vent Connectors for Category I Appliances.
- 509.8 Through-the-Wall Vent Termination. Throughthe-wall vent …
- 509.13 Manually Operated Dampers. A manually operated damper s…
- 509.14 Automatically Operated Vent Dampers. An
- 509.15 Obstructions. Devices that retard the flow of vent
- 510.1 Additional Requirements to Single Appliance
- 509.11 Vent Connectors for Category II, Category III,
- 509.12 Appliances Requiring Draft Hoods. Vented
- 510.2 Additional Requirements to Multiple-Appliance
- Chapter 6 — WATER SUPPLY AND DISTRIBUTION
- Chapter 7 — SANITARY DRAINAGE
- Chapter 8 — INDIRECT WASTES
- Chapter 9 — VENTS
- Chapter 10 — TRAPS AND INTERCEPTORS
- Chapter 11 — STORM DRAINAGE
- Chapter 12 — FUEL GAS PIPING
- Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
- Chapter 14 — FIRESTOP PROTECTION
- Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
- Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
- Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
- Appendix C — ALTERNATE PLUMBING SYSTEMS
- Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
- Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
- Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
- Appendix G — SIZING OF VENTING SYSTEMS
- Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
- Appendix I — INSTALLATION STANDARDS
- Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
- Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
- Appendix L — SUSTAINABLE PRACTICES
- Appendix M — PEAK WATER DEMAND CALCULATOR
- Appendix N — IMPACT OF WATER TEMPERATURE ON THE POTENTIAL FOR …
- Appendix O — NON-SEWERED SANITATION SYSTEMS
- Appendix P — PROFESSIONAL QUALIFICATIONS
- Appendix Q — INDOOR HORTICULTURAL FACILITIES
- Appendix R — TINY HOUSES
- Appendix S — ONSITE STORMWATER TREATMENT SYSTEMS