Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
1603.12 Storage Tank Venting — 2025 California Plumbing Code
California Plumbing Code (Title 24, Part 5) · 2025 edition · updated 2026-09-25 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
Cite as: 2025 California Plumbing Code (Title 24, Part 5) § 1603.12 · Effective January 1, 2026 · Official source: Building Standards Commission
Where venting using drainage or overflow piping is not provided or is considered insufficient, a vent shall be installed on each tank. The vent shall extend from the top of the tank and terminate not less than 6 inches (152 mm) above grade and shall be provided with a vent sized in accordance with this code, and based on the size of the influent pipe . The vent terminal shall be directed downward and covered with a [1] ∕ 16 of an inch ( 1.6 mm) mesh screen to prevent the entry of vermin and insects. Tank vent pipes shall not be connected to the sanitary drainage system vent.
Explained in plain English
Guides that cite this section.
Get a plain-English answer with a citation back to this text.
Ask AI about this code