Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS

1603.12 Storage Tank Venting — 2025 California Plumbing Code

California Plumbing Code (Title 24, Part 5) · 2025 edition · updated 2026-09-25 · California

CBSC: official editions, supplements and errata

Italicized text is a California amendment to the model code, as printed in the official publication.

Cite as: 2025 California Plumbing Code (Title 24, Part 5) § 1603.12 · Effective January 1, 2026 · Official source: Building Standards Commission

Where venting using drainage or overflow piping is not provided or is considered insufficient, a vent shall be installed on each tank. The vent shall extend from the top of the tank and terminate not less than 6 inches (152 mm) above grade and shall be provided with a vent sized in accordance with this code, and based on the size of the influent pipe . The vent terminal shall be directed downward and covered with a [1] ∕ 16 of an inch ( 1.6 mm) mesh screen to prevent the entry of vermin and insects. Tank vent pipes shall not be connected to the sanitary drainage system vent.