Rainwater tank openings shall be protected to prevent the entrance of insects, birds, or rodents into the tank and piping systems .
Rainwater tank access openings exceeding 12 inches (305 mm) in diameter shall be secured to prevent tampering and unintended entry by either a lockable device or other approved method.
(A) Animals and Insects. Screens installed on vent pipes, inlets, and overflow pipes shall have an aperture of not greater than [1] ∕ 16 of an inch (1.6 mm) and shall be close fit- ting.
(B) Human Access. A minimum of one access opening shall be provided to allow inspection and cleaning. Rainwater tank manholes and access openings shall be secured by either a lockable device or other approved method to pre- vent unauthorized access.