Methods. Materials used for piping systems shall comply with the requirements of Section 1208.5.1 through Section 1208.5.6.3. {NFPA 54:5.5.1.1}

1208.5.1 Used Materials. Pipe, fittings, valves, or other materials shall not be used again unless they are free of foreign materials and have been ascertained to be adequate for the service intended. [NFPA 54:5.5.1.2]

1208.5.2 Metallic Pipe. Metallic pipe shall be in accordance with the Section 1208.5.2.1 through Section 1208.5.2.4.

1208.5.2.1 Cast Iron. Cast-iron pipe shall not be used. [NFPA 54:5.5.2.1]

1208.5.2.2 Steel, Stainless Steel, and Wrought- Iron Pipe. Steel, stainless steel, and wrought-iron pipe shall be at least Schedule 40 and shall comply

»

»

»

Exception: Sizing shall be permitted to be based upon established load diversity factors. [NFPA 54:5.3.2.3]

TABLE 1208.3.1

APPROXIMATE GAS INPUT FOR

TYPICAL APPLIANCES

[NFPA 54: TABLE A.5.3.2.1]

APPLIANCE INPUT
(Btu/h approx.)







Space Heating Units
Warm air furnace
Single family
Multifamily, per unit
Hydronic boiler
Single family
Multifamily, per unit


100 000
60 000

100 000
60 000




Space and Water Heating Units
Hydronic boiler
Single-family
Multifamily, per unit


120 000
75 000











Water Heating Appliances
Water heater, automatic storage
30 to 40 gallon tank
Water heater, automatic storage
50 gallon tank
Water heater, automatic instantaneous
Capacity at 2 gallons per minute
Capacity at 4 gallons per minute
Capacity at 6 gallons per minute
Water heater, domestic, circulating or
side-arm


35 000

50 000

142 800
285 000
428 400

35 000




Cooking Appliances
Range, freestanding, domestic
Built-in oven or broiler unit, domestic
Built-in top unit, domestic

65 000
25 000
40 000






Other Appliances
Refrigerator
Clothes dryer, Type 1 (domestic)
Gas fireplace direct-vent
Gas log
Barbecue
Gaslight

3000
35 000
40 000
80 000
40 000
2500

For SI units: 1000 British thermal units per hour = 0.293 kW

1208.3.2 Sizing Methods. Gas piping shall be sized in accordance with one of the following:

(1) Pipe sizing tables or sizing equations in this chap ter.

(2) Sizing tables included in a listed piping system manufacturer’s installation instructions.

(3) Engineering methods. [NFPA 54:5.3.3]

1208.3.3 Allowable Pressure Drop. The design pressure loss in a piping system from the point of delivery to

TABLE 1208.3.1

APPROXIMATE GAS INPUT FOR

TYPICAL APPLIANCES

[NFPA 54: TABLE A.5.3.2.1]

«

«

«

«

«

For SI units: 1000 British thermal units per hour = 0.293 kW

FUEL GAS PIPING

«

«

«

«

«

«

«

«

«

«

1208.5.4 Plastic Pipe, Tubing, and Fittings. Polyethylene plastic pipe, tubing, and fittings used to supply fuel gas shall conform to ASTM D2513. Pipe to be used shall be marked “gas” and “ASTM D2513.” Polyamide pipe, tubing, and fittings shall be identified in and conform to ASTM F2945. Pipe to be used shall be marked “gas” and “ASTM F2945.” Polyvinyl chloride (PVC) and chlorinated polyvinyl chloride (CPVC) plastic pipe, tubing, and fittings shall not be used to supply fuel gas. [NFPA 54:5.5.4.1.1 – 5.5.4.1.3]

1208.5.5 Regulator Vent Piping. Plastic pipe and fittings used to connect regulator vents to remote vent terminations shall be PVC (Schedule 40 and 80). PVC vent piping shall not be installed indoors. {NFPA 54:5.5.4.2}

1208.5.6 Anodeless Risers. Anodeless risers shall

comply with Section 1208.5.6.1 through Section 1208.5.6.3.

1208.5.6.1 Factory-Assembled Anodeless Risers. Factory-assembled anodeless risers shall be recommended by the manufacturer for the gas used and shall be leak tested by the manufacturer in accordance with written procedures. [NFPA 54:5.5.4.3(1)]

1208.5.6.2 Service Head Adapters and Field- Assembled Anodeless Risers. Service head

adapters and field-assembled anodeless risers incorporating service head adapters shall be recommended by the manufacturer for the gas used and shall be design-certified to meet the requirements of Category I of ASTM D2513 and 49 CFR 192.281(e). The manufacturer shall provide the user qualified installation instructions as prescribed by 49 CFR 192.283(b).

[NFPA 54:5.5.4.3(2)]

1208.5.6.3 Undiluted Liquefied Petroleum Gas Piping. The use of plastic pipe, tubing, and fittings in undiluted LP-Gas piping systems shall be in accordance with NFPA 58. [NFPA 54:5.5.4.3(3)]

1208.5.7 Workmanship and Defects. Gas pipe, tubing, and fittings shall be clear and free from cutting burrs and defects in structure or threading and shall be thoroughly brushed and chip and scale blown. Defects in pipe, tubing, and fittings shall not be repaired. Defective pipe, tubing, and fittings shall be replaced. [NFPA 54:5.5.5]

1208.5.8 Metallic Pipe Threads. Metallic pipe and fitting threads shall be taper pipe threads and shall comply with ASME B1.20.1. [NFPA 54:5.5.6.1]

1208.5.8.1 Damaged Threads. Pipe with threads that are stripped, chipped, corroded, or otherwise damaged shall not be used. Where a weld opens during the operation of cutting or threading, that portion of the pipe shall not be used. [NFPA 54:5.5.6.2]

1208.5.8.2 Number of Threads. Field threading of metallic pipe shall be in accordance with Table 1208.5.8.2. [NFPA 54:5.5.6.3]

»

»

»

»

»

»

»

»

with the dimensional standards of ASME B36.10M

and one of the following:

(1) ASTM A53

(2) ASTM A106

(3) ASTM A312 {NFPA 54:5.5.2.2}

1208.5.2.3 Copper and Copper Alloy Pipe. Copper and copper alloy pipe shall not be used if the gas contains more than an average of 0.3 grains of hydrogen sulfide per 100 standard cubic feet (scf) of gas (0.7 mg/100 L).

Threaded copper, copper alloy, or aluminum alloy pipe shall not be used with gases corrosive to such material. [NFPA 54:5.5.2.3 – 5.5.2.4]

1208.5.2.4 Aluminum Alloy Pipe. Aluminum alloy pipe shall comply with ASTM B241 (except that the use of alloy 5456 is prohibited), and shall be marked at each end of each length indicating compliance. Aluminum alloy pipe shall be coated to protect against external corrosion where it is in contact with masonry, plaster, or insulation or is subject to repeated wettings by such liquids as water, detergents, or sewage. [NFPA 54:5.5.2.5]

Aluminum alloy pipe shall not be used in exterior locations or underground. [NFPA 54:5.5.2.6]

1208.5.3 Metallic Tubing. Tubing shall not be used with gases corrosive to the tubing material. [NFPA 54:5.5.3.1]

1208.5.3.1 Steel Tubing. Steel tubing shall comply with ASTM A254. [NFPA 54:5.5.3.2]

1208.5.3.2 Stainless Steel. Stainless steel tub ing shall comply with one of the following:

(1) ASTM A268

(2) ASTM A269 [NFPA 54:5.5.3.3]

1208.5.3.3 Copper and Copper Alloy Tubing. Copper and copper alloy tubing shall not be used if the gas contains more than an average of 0.3 grains of hydrogen sulfide per 100 scf of gas (0.7 mg/100 L). Copper tubing shall comply with standard Type K or Type L of ASTM B88 or ASTM B280. [NFPA 54:5.5.3.4]

1208.5.3.4 Aluminum Alloy Tubing. Aluminum alloy tubing shall comply with ASTM B210 or ASTM B241. Aluminum alloy tubing shall be coated to protect against external corrosion where it is in contact with masonry, plaster, or insulation or is subject to repeated wettings by such liquids as water, detergent, or sewage. Aluminum alloy tubing shall not be used in exterior locations or under ground. [NFPA 54:5.5.3.5]

1208.5.3.5 Corrugated Stainless Steel Tub- ing. Corrugated stainless steel tubing shall be listed in accordance with CSA/ANSI LC 1/CSA 6.26.

[NFPA 54:5.5.3.6]

218 2025 CALIFORNIA PLUMBING CODE

FUEL GAS PIPING

»

»

»

»

»

»

IRON
PIPE SIZE
(inches)
APPROXIMATE
LENGTH OF
THREADED PORTION
(inches)
APPROXIMATE
NUMBER OF
THREADS TO BE CUT

1⁄2
3⁄4 10

3⁄4
3⁄4 10

1
7⁄8 10

11⁄4
1 11

11⁄2
1 11

2
1 11
21⁄2 11⁄2 12


3
11⁄2 12

4
15⁄8 13

For SI units: 1 inch = 25.4 mm

1208.5.8.3 Thread Joint Sealing. Threaded joints shall be made using a thread joint sealing material.

[NFPA 54:5.5.6.4.1]

Thread joint sealing materials shall be compatible with the pipe and fitting material on which the compounds are used. [NFPA 54:5.5.6.4.2]

Thread joint sealing materials shall be resistant to the chemical constituents of the gases to be conducted through the piping. {NFPA 54:5.5.6.4.3}

1208.5.9 Metallic Piping Joints and Fittings. The type of piping joint used shall be suitable for the pressure and temperature conditions and shall be selected giving consideration to joint tightness and mechanical strength under the service conditions. The joint shall be able to sustain the maximum end force due to the internal pressure and any additional forces due to temperature expansion or contraction, vibration, fatigue, or the weight of the pipe and its contents. [NFPA 54:5.5.7]

1208.5.9.1 Pipe Joints. Schedule 40 and heavier pipe joints shall be threaded, flanged, brazed, welded, or assembled with press-connect fittings listed to ANSI LC 4/CSA 6.32.

(1) Where nonferrous pipe is brazed, the brazing materials shall have a melting point in excess of 1000°F (538°C).

(2) Brazing alloys shall not contain more than 0.05 percent phosphorus. {NFPA 54:5.5.7.1} 1208.5.9.2 Copper Tubing Joints. Copper tubing joints shall be assembled with approved gas tubing fittings, shall be brazed with a material having a melting point in excess of 1000°F (538°C), or shall be assembled with press-connect fittings listed to ANSI LC 4/CSA 6.32. Brazing alloys shall not contain more than 0.05 percent phosphorus. [NFPA 54:5.5.7]

1208.5.9.3 Stainless Steel Tubing Joints. Stainless steel joints shall be welded, assembled with approved tubing fittings, brazed with a material hav

TABLE 1208.5.8.2

SPECIFICATIONS FOR THREADING METALLIC PIPE

[NFPA 54: TABLE 5.5.6.3]

ing a melting point in excess of 1000°F (538°C), or assembled with press-connect fittings listed to ANSI LC 4/CSA 6.32. Brazing alloys and fluxes shall be recommended by the manufacturer for use on stainless steel alloys. [NFPA 54:5.5.7.3]

1208.5.9.4 Flared Joints. Flared joints shall be used only in systems constructed from nonferrous pipe and tubing where experience or tests have demonstrated that the joint is suitable for the conditions and where provisions are made in the design to prevent separation of the joints. [NFPA 54:5.5.7.4]

1208.5.9.5 Metallic Pipe Fittings. Metallic fittings shall comply with the following:

(1) Threaded fittings in sizes larger than 4 inches (100 mm) shall not be used.

(2) Fittings used with steel, stainless steel, or wrought-iron pipe shall be steel, stainless steel, copper alloy, malleable iron, or cast iron.

(3) Fittings used with copper or copper alloy pipe shall be copper or copper alloy.

(4) Fittings used with aluminum alloy pipe shall be aluminum alloy.

(5) Cast-iron fittings shall comply with the following:

(a) Flanges shall be permitted.

(b) Bushings shall not be used.

(c) Fittings shall not be used in systems containing flammable gas-air mixtures.

(d) Fittings in sizes 4 inches (100 mm) and larger shall not be used indoors unless approved by the Authority Having Jurisdiction.

(e) Fittings in sizes 6 inches (150 mm) and larger shall not be used unless approved by the Authority Having Jurisdiction.

(6) Aluminum alloy fitting threads shall not form the joint seal.

(7) Zinc-aluminum alloy fittings shall not be used in systems containing flammable gas-air mix tures.

(8) Special fittings such as couplings, proprietarytype joints, saddle tees, gland-type compression fittings, and flared, flareless, or compressiontype tubing fittings shall be as follows:

(a) Used within the fitting manufacturer’s pressure-temperature recommendations.

(b) Used within the service conditions anticipated with respect to vibration, fatigue, thermal expansion, or contraction.

(c) Acceptable to the Authority Having Jurisdiction.

(9) When pipe fittings are drilled and tapped in the field, the operation shall be in accordance with the following:

«

«

FUEL GAS PIPING

(1) ASME B16.5 or

(2) ASME B16.47. [NFPA 54:5.5.9.1.2]

1208.5.11.3 Non-Ferrous Flanges. Non-ferrous flanges shall be in accordance with ASME B16.24.

[NFPA 54:5.5.9.1.3]

1208.5.11.4 Ductile Iron Flanges. Ductile iron flanges shall be in accordance with ASME B16.42.

[NFPA 54:5.5.9.1.4]

1208.5.11.5 Dissimilar Flange Connections. Raised-face flanges shall not be joined to flat-faced cast iron, ductile iron or nonferrous material flanges.

[NFPA 54:5.5.9.2]

1208.5.11.6 Flange Facings. Standard facings shall be permitted for use under this code. Where 150 psi (1034 kPa) steel flanges are bolted to Class 125 cast-iron flanges, the raised face on the steel flange shall be removed. [NFPA 54:5.5.9.3]

1208.5.11.7 Lapped Flanges. Lapped flanges shall be used only aboveground or in exposed locations accessible for inspection. [NFPA 54:5.5.9.4]

1208.5.12 Flange Gaskets. The material for gaskets shall be capable of withstanding the design temperature and pressure of the piping system and the chemical constituents of the gas being conducted without change to its chemical and physical properties. The effects of fire exposure to the joint shall be considered in choosing the material. [NFPA 54:5.5.10]

1208.5.12.1 Flange Gasket Materials. Acceptable materials shall include the following:

(1) Metal (plain or corrugated)

(2) Composition

(3) Aluminum “O” rings

(4) Spiral-wound metal gaskets

(5) Rubber-faced phenolic

(6) Elastomeric [NFPA 54:5.5.10.1]

1208.5.12.2 Metallic Flange Gaskets. Metallic flange gaskets shall be in accordance with ASME B16.20. [NFPA 54:5.5.10.2.1]

1208.5.12.3 Non-Metallic Flange Gaskets. Non-metallic flange gaskets shall be in accordance with ASME B16.21. [NFPA 54:5.5.10.2.2]

1208.5.12.4 Full-Face Flange Gasket. Full-face flange gaskets shall be used with all non-steel flanges. [NFPA 54:5.5.10.3]

1208.5.12.5 Separated Flanges. When a flanged joint is separated, the gasket shall be replaced. [NFPA 54:5.5.10.4]

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — California Plumbing Code (Title 24, Part 5)
California Plumbing Code (Title 24, Part 5)
  1. Chapter 1 — GENERAL CODE PROVISIONS
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — GENERAL REGULATIONS
  4. Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
  5. Chapter 5 — WATER HEATERS
  6. Chapter 6 — WATER SUPPLY AND DISTRIBUTION
  7. Chapter 7 — SANITARY DRAINAGE
  8. Chapter 8 — INDIRECT WASTES
  9. Chapter 9 — VENTS
  10. Chapter 10 — TRAPS AND INTERCEPTORS
  11. Chapter 11 — STORM DRAINAGE
  12. Chapter 12 — FUEL GAS PIPING
    Overview
    1. 1201.1 Applicability. The regulations of this chapter shall
    2. 1202.1 General. Coverage of piping systems shall extend
    3. 1202.2 Piping System Requirements. Requirements for
    4. 1202.3 Applications. This chapter shall not apply to the
    5. 1203.1 Inspection Notification. Upon completion of the
    6. 1203.2 Excavation. Excavations required for the installation o…
    7. 1203.3 Type of Inspections. The Authority Having Jurisdiction …
    8. 1203.4 Inspection Waived. In cases where the work
    9. 1204.1 Issuance. Whereupon final piping inspection, the
    10. 1204.2 Gas Supplier. A copy of the certificate of such final
    11. 1204.3 Unlawful. It shall be unlawful for a serving gas suppli…
    12. 1205.1 Authorized Personnel. It shall be unlawful for a
    13. 1205.2 Outlets. It shall be unlawful to turn on or connect gas
    14. 1206.1 Disconnection. The Authority Having Jurisdiction
    15. 1206.2 Notice. Where such disconnection has been made, a
    16. 1206.3 Capped Outlets. It shall be unlawful to remove or
    17. 1207.1 General. Where temporary use of gas is desired, and
    18. 1208.1 Installation of Piping System. Where required
    19. 1208.2 Interconnections Supplying Separate Users.
    20. 1208.3 Sizing of Gas Piping Systems. Gas piping systems shall …
    21. 1208.4 Maximum Operating Pressure in Buildings.
    22. 1208.5 Acceptable Piping Materials and Joining
    23. 1208.6 Gas Meters. Gas meters shall be selected for the
    24. 1208.7 Gas Pressure Regulators. A line pressure regulator shal…
    25. 1208.8 Overpressure Protection Required. Where the
    26. 1208.9 Overpressure Protection Devices. Overpressure protectio…
    27. 1208.10 Pressure Limitation Requirements. Where piping systems…
    28. 1208.11 Backpressure Protection. Protective devices
    29. 1208.12 Low-Pressure Protection. A protective device
    30. 1208.13 Shutoff Valves. Shutoff valves shall be selected in
    31. 1208.14 Expansion and Flexibility. Piping systems shall
    32. 1208.15 Pressure Regulator and Pressure Control
    33. 1209.1 General. Where automatic excess flow valves are
    34. 1210.1 Piping Underground. Underground gas piping
    35. 1210.2 CSST Piping Systems. CSST piping systems shall
    36. 1210.3 Installation of Aboveground Piping. Piping
    37. 1210.4 Concealed Piping in Buildings. Gas piping in
    38. 1210.5 Piping in Vertical Chases. Where gas piping
    39. 1210.6 Gas Pipe Turns. Changes in direction of gas pipe
    40. 1210.7 Drips and Sediment Traps. For other than dry gas
    41. 1210.8 Outlets. Outlets shall be located and installed in
    42. 1210.9 Manual Gas Shutoff Valves. An accessible gas
    43. 1210.10 Prohibited Devices. Devices shall not be placed
    44. 1210.11 Systems Containing Gas-Air Mixtures Out-
    45. 1210.12 Systems Containing Flammable Gas-Air
    46. 1211.1 Pipe and Tubing Other than CSST. Each aboveground porti…
    47. 1211.2 Bonding of CSST Gas Piping. CSST gas piping
    48. 1211.3 Arc-Resistant Jacketed CSST. CSST listed with
    49. 1211.4 Prohibited Use. Gas piping shall not be used as a
    50. 1211.5 Lightning Protection System. Where a lightning
    51. 1211.6 Electrical Circuits. Electrical circuits shall not util…
    52. 1211.7 Electrical Connections. All electrical connections
    53. 1211.8 Earthquake-Actuated Gas Shutoff Valves.
    54. 1212.1 Connecting Appliances and Equipment.
    55. 1212.4 Injection (Bunsen) Burners. Injection (Bunsen)
    56. 1212.5 Connection of Portable and Mobile Industrial
    57. 1212.6 Appliance Shutoff Valves and Connections.
    58. 1212.7 Quick-Disconnect Devices. Quick-disconnect
    59. 1212.2 Suspended Low-Intensity Infrared Tube
    60. 1212.3 Use of Nonmetallic Gas Hose Connectors.
    61. 1212.8 Gas Convenience Outlets. Appliances shall be
    62. 1212.9 Sediment Trap. Where a sediment trap is not incorporate…
    63. 1212.10 Installation of Piping. Piping shall be installed in
    64. 1212.11 Liquefied Petroleum Gas Facilities and Pip-
    65. 1213.1 Piping Installations. Prior to acceptance and initial o…
    66. 1213.2 Test Preparation. Test preparation shall comply
    67. 1213.3 Test Pressure. This inspection shall include an air,
    68. 1213.4 Detection of Leaks and Defects. The piping system shall…
    69. 1213.5 Piping System Leak Test. Leak checks using fuel
    70. 1213.6 Purging Requirements. The purging of piping
    71. 1214.1 General. The following regulations shall comply
    72. 1214.2 Volume. The hourly volume of gas required at each
    73. 1214.3 Gas Appliances. Where the gas appliances to be
    74. 1214.4 Size of Piping Outlets. The size of the supply piping o…
    75. 1215.1 Pipe Sizing Methods. Where the pipe size is to be
    76. 1215.2 Sizing of Gas Piping Systems. Sizing of piping
    77. 1215.3 Sizing Equations. The inside diameter of smooth
    78. 1215.4 Sizing of Piping Sections. To determine the size
    79. 1215.5 Engineering Methods. For conditions other than
    80. 1215.6 Variable Gas Pressure. Where the supply gas
  13. Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
  14. Chapter 14 — FIRESTOP PROTECTION
  15. Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
  16. Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
  17. Chapter 17 — REFERENCED STANDARDS
  18. Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
  19. Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
  20. Appendix C — ALTERNATE PLUMBING SYSTEMS
  21. Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
  22. Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
  23. Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
  24. Appendix G — SIZING OF VENTING SYSTEMS
  25. Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
  26. Appendix I — INSTALLATION STANDARDS
  27. Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
  28. Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
  29. Appendix L — SUSTAINABLE PRACTICES
  30. Appendix M — PEAK WATER DEMAND CALCULATOR
  31. Appendix N — IMPACT OF WATER TEMPERATURE ON THE POTENTIAL FOR …
  32. Appendix O — NON-SEWERED SANITATION SYSTEMS
  33. Appendix P — PROFESSIONAL QUALIFICATIONS
  34. Appendix Q — INDOOR HORTICULTURAL FACILITIES
  35. Appendix R — TINY HOUSES
  36. Appendix S — ONSITE STORMWATER TREATMENT SYSTEMS

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.