1208.5 Acceptable Piping Materials and Joining
California Plumbing Code (Title 24, Part 5) · 2025 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
Methods. Materials used for piping systems shall comply with the requirements of Section 1208.5.1 through Section 1208.5.6.3. {NFPA 54:5.5.1.1}
1208.5.1 Used Materials. Pipe, fittings, valves, or other materials shall not be used again unless they are free of foreign materials and have been ascertained to be adequate for the service intended. [NFPA 54:5.5.1.2]
1208.5.2 Metallic Pipe. Metallic pipe shall be in accordance with the Section 1208.5.2.1 through Section 1208.5.2.4.
1208.5.2.1 Cast Iron. Cast-iron pipe shall not be used. [NFPA 54:5.5.2.1]
1208.5.2.2 Steel, Stainless Steel, and Wrought- Iron Pipe. Steel, stainless steel, and wrought-iron pipe shall be at least Schedule 40 and shall comply
»
»
»
Exception: Sizing shall be permitted to be based upon established load diversity factors. [NFPA 54:5.3.2.3]
TABLE 1208.3.1
APPROXIMATE GAS INPUT FOR
TYPICAL APPLIANCES
[NFPA 54: TABLE A.5.3.2.1]
| APPLIANCE | INPUT (Btu/h approx.) |
|---|---|
Space Heating Units Warm air furnace Single family Multifamily, per unit Hydronic boiler Single family Multifamily, per unit |
100 000 60 000 100 000 60 000 |
Space and Water Heating Units Hydronic boiler Single-family Multifamily, per unit |
120 000 75 000 |
Water Heating Appliances Water heater, automatic storage 30 to 40 gallon tank Water heater, automatic storage 50 gallon tank Water heater, automatic instantaneous Capacity at 2 gallons per minute Capacity at 4 gallons per minute Capacity at 6 gallons per minute Water heater, domestic, circulating or side-arm |
35 000 50 000 142 800 285 000 428 400 35 000 |
Cooking Appliances Range, freestanding, domestic Built-in oven or broiler unit, domestic Built-in top unit, domestic |
65 000 25 000 40 000 |
Other Appliances Refrigerator Clothes dryer, Type 1 (domestic) Gas fireplace direct-vent Gas log Barbecue Gaslight |
3000 35 000 40 000 80 000 40 000 2500 |
For SI units: 1000 British thermal units per hour = 0.293 kW
1208.3.2 Sizing Methods. Gas piping shall be sized in accordance with one of the following:
(1) Pipe sizing tables or sizing equations in this chap ter.
(2) Sizing tables included in a listed piping system manufacturer’s installation instructions.
(3) Engineering methods. [NFPA 54:5.3.3]
1208.3.3 Allowable Pressure Drop. The design pressure loss in a piping system from the point of delivery to
TABLE 1208.3.1
APPROXIMATE GAS INPUT FOR
TYPICAL APPLIANCES
[NFPA 54: TABLE A.5.3.2.1]
«
«
«
«
«
For SI units: 1000 British thermal units per hour = 0.293 kW
FUEL GAS PIPING
«
«
«
«
«
«
«
«
«
«
1208.5.4 Plastic Pipe, Tubing, and Fittings. Polyethylene plastic pipe, tubing, and fittings used to supply fuel gas shall conform to ASTM D2513. Pipe to be used shall be marked “gas” and “ASTM D2513.” Polyamide pipe, tubing, and fittings shall be identified in and conform to ASTM F2945. Pipe to be used shall be marked “gas” and “ASTM F2945.” Polyvinyl chloride (PVC) and chlorinated polyvinyl chloride (CPVC) plastic pipe, tubing, and fittings shall not be used to supply fuel gas. [NFPA 54:5.5.4.1.1 – 5.5.4.1.3]
1208.5.5 Regulator Vent Piping. Plastic pipe and fittings used to connect regulator vents to remote vent terminations shall be PVC (Schedule 40 and 80). PVC vent piping shall not be installed indoors. {NFPA 54:5.5.4.2}
1208.5.6 Anodeless Risers. Anodeless risers shall
comply with Section 1208.5.6.1 through Section 1208.5.6.3.
1208.5.6.1 Factory-Assembled Anodeless Risers. Factory-assembled anodeless risers shall be recommended by the manufacturer for the gas used and shall be leak tested by the manufacturer in accordance with written procedures. [NFPA 54:5.5.4.3(1)]
1208.5.6.2 Service Head Adapters and Field- Assembled Anodeless Risers. Service head
adapters and field-assembled anodeless risers incorporating service head adapters shall be recommended by the manufacturer for the gas used and shall be design-certified to meet the requirements of Category I of ASTM D2513 and 49 CFR 192.281(e). The manufacturer shall provide the user qualified installation instructions as prescribed by 49 CFR 192.283(b).
[NFPA 54:5.5.4.3(2)]
1208.5.6.3 Undiluted Liquefied Petroleum Gas Piping. The use of plastic pipe, tubing, and fittings in undiluted LP-Gas piping systems shall be in accordance with NFPA 58. [NFPA 54:5.5.4.3(3)]
1208.5.7 Workmanship and Defects. Gas pipe, tubing, and fittings shall be clear and free from cutting burrs and defects in structure or threading and shall be thoroughly brushed and chip and scale blown. Defects in pipe, tubing, and fittings shall not be repaired. Defective pipe, tubing, and fittings shall be replaced. [NFPA 54:5.5.5]
1208.5.8 Metallic Pipe Threads. Metallic pipe and fitting threads shall be taper pipe threads and shall comply with ASME B1.20.1. [NFPA 54:5.5.6.1]
1208.5.8.1 Damaged Threads. Pipe with threads that are stripped, chipped, corroded, or otherwise damaged shall not be used. Where a weld opens during the operation of cutting or threading, that portion of the pipe shall not be used. [NFPA 54:5.5.6.2]
1208.5.8.2 Number of Threads. Field threading of metallic pipe shall be in accordance with Table 1208.5.8.2. [NFPA 54:5.5.6.3]
»
»
»
»
»
»
»
»
with the dimensional standards of ASME B36.10M
and one of the following:
(1) ASTM A53
(2) ASTM A106
(3) ASTM A312 {NFPA 54:5.5.2.2}
1208.5.2.3 Copper and Copper Alloy Pipe. Copper and copper alloy pipe shall not be used if the gas contains more than an average of 0.3 grains of hydrogen sulfide per 100 standard cubic feet (scf) of gas (0.7 mg/100 L).
Threaded copper, copper alloy, or aluminum alloy pipe shall not be used with gases corrosive to such material. [NFPA 54:5.5.2.3 – 5.5.2.4]
1208.5.2.4 Aluminum Alloy Pipe. Aluminum alloy pipe shall comply with ASTM B241 (except that the use of alloy 5456 is prohibited), and shall be marked at each end of each length indicating compliance. Aluminum alloy pipe shall be coated to protect against external corrosion where it is in contact with masonry, plaster, or insulation or is subject to repeated wettings by such liquids as water, detergents, or sewage. [NFPA 54:5.5.2.5]
Aluminum alloy pipe shall not be used in exterior locations or underground. [NFPA 54:5.5.2.6]
1208.5.3 Metallic Tubing. Tubing shall not be used with gases corrosive to the tubing material. [NFPA 54:5.5.3.1]
1208.5.3.1 Steel Tubing. Steel tubing shall comply with ASTM A254. [NFPA 54:5.5.3.2]
1208.5.3.2 Stainless Steel. Stainless steel tub ing shall comply with one of the following:
(1) ASTM A268
(2) ASTM A269 [NFPA 54:5.5.3.3]
1208.5.3.3 Copper and Copper Alloy Tubing. Copper and copper alloy tubing shall not be used if the gas contains more than an average of 0.3 grains of hydrogen sulfide per 100 scf of gas (0.7 mg/100 L). Copper tubing shall comply with standard Type K or Type L of ASTM B88 or ASTM B280. [NFPA 54:5.5.3.4]
1208.5.3.4 Aluminum Alloy Tubing. Aluminum alloy tubing shall comply with ASTM B210 or ASTM B241. Aluminum alloy tubing shall be coated to protect against external corrosion where it is in contact with masonry, plaster, or insulation or is subject to repeated wettings by such liquids as water, detergent, or sewage. Aluminum alloy tubing shall not be used in exterior locations or under ground. [NFPA 54:5.5.3.5]
1208.5.3.5 Corrugated Stainless Steel Tub- ing. Corrugated stainless steel tubing shall be listed in accordance with CSA/ANSI LC 1/CSA 6.26.
[NFPA 54:5.5.3.6]
218 2025 CALIFORNIA PLUMBING CODE
FUEL GAS PIPING
»
»
»
»
»
»
| IRON PIPE SIZE (inches) |
APPROXIMATE LENGTH OF THREADED PORTION (inches) |
APPROXIMATE NUMBER OF THREADS TO BE CUT |
|---|---|---|
1⁄2 |
3⁄4 | 10 |
3⁄4 |
3⁄4 | 10 |
1 |
7⁄8 | 10 |
11⁄4 |
1 | 11 |
11⁄2 |
1 | 11 |
2 |
1 | 11 |
| 21⁄2 | 11⁄2 | 12 |
3 |
11⁄2 | 12 |
4 |
15⁄8 | 13 |
For SI units: 1 inch = 25.4 mm
1208.5.8.3 Thread Joint Sealing. Threaded joints shall be made using a thread joint sealing material.
[NFPA 54:5.5.6.4.1]
Thread joint sealing materials shall be compatible with the pipe and fitting material on which the compounds are used. [NFPA 54:5.5.6.4.2]
Thread joint sealing materials shall be resistant to the chemical constituents of the gases to be conducted through the piping. {NFPA 54:5.5.6.4.3}
1208.5.9 Metallic Piping Joints and Fittings. The type of piping joint used shall be suitable for the pressure and temperature conditions and shall be selected giving consideration to joint tightness and mechanical strength under the service conditions. The joint shall be able to sustain the maximum end force due to the internal pressure and any additional forces due to temperature expansion or contraction, vibration, fatigue, or the weight of the pipe and its contents. [NFPA 54:5.5.7]
1208.5.9.1 Pipe Joints. Schedule 40 and heavier pipe joints shall be threaded, flanged, brazed, welded, or assembled with press-connect fittings listed to ANSI LC 4/CSA 6.32.
(1) Where nonferrous pipe is brazed, the brazing materials shall have a melting point in excess of 1000°F (538°C).
(2) Brazing alloys shall not contain more than 0.05 percent phosphorus. {NFPA 54:5.5.7.1} 1208.5.9.2 Copper Tubing Joints. Copper tubing joints shall be assembled with approved gas tubing fittings, shall be brazed with a material having a melting point in excess of 1000°F (538°C), or shall be assembled with press-connect fittings listed to ANSI LC 4/CSA 6.32. Brazing alloys shall not contain more than 0.05 percent phosphorus. [NFPA 54:5.5.7]
1208.5.9.3 Stainless Steel Tubing Joints. Stainless steel joints shall be welded, assembled with approved tubing fittings, brazed with a material hav
TABLE 1208.5.8.2
SPECIFICATIONS FOR THREADING METALLIC PIPE
[NFPA 54: TABLE 5.5.6.3]
ing a melting point in excess of 1000°F (538°C), or assembled with press-connect fittings listed to ANSI LC 4/CSA 6.32. Brazing alloys and fluxes shall be recommended by the manufacturer for use on stainless steel alloys. [NFPA 54:5.5.7.3]
1208.5.9.4 Flared Joints. Flared joints shall be used only in systems constructed from nonferrous pipe and tubing where experience or tests have demonstrated that the joint is suitable for the conditions and where provisions are made in the design to prevent separation of the joints. [NFPA 54:5.5.7.4]
1208.5.9.5 Metallic Pipe Fittings. Metallic fittings shall comply with the following:
(1) Threaded fittings in sizes larger than 4 inches (100 mm) shall not be used.
(2) Fittings used with steel, stainless steel, or wrought-iron pipe shall be steel, stainless steel, copper alloy, malleable iron, or cast iron.
(3) Fittings used with copper or copper alloy pipe shall be copper or copper alloy.
(4) Fittings used with aluminum alloy pipe shall be aluminum alloy.
(5) Cast-iron fittings shall comply with the following:
(a) Flanges shall be permitted.
(b) Bushings shall not be used.
(c) Fittings shall not be used in systems containing flammable gas-air mixtures.
(d) Fittings in sizes 4 inches (100 mm) and larger shall not be used indoors unless approved by the Authority Having Jurisdiction.
(e) Fittings in sizes 6 inches (150 mm) and larger shall not be used unless approved by the Authority Having Jurisdiction.
(6) Aluminum alloy fitting threads shall not form the joint seal.
(7) Zinc-aluminum alloy fittings shall not be used in systems containing flammable gas-air mix tures.
(8) Special fittings such as couplings, proprietarytype joints, saddle tees, gland-type compression fittings, and flared, flareless, or compressiontype tubing fittings shall be as follows:
(a) Used within the fitting manufacturer’s pressure-temperature recommendations.
(b) Used within the service conditions anticipated with respect to vibration, fatigue, thermal expansion, or contraction.
(c) Acceptable to the Authority Having Jurisdiction.
(9) When pipe fittings are drilled and tapped in the field, the operation shall be in accordance with the following:
«
«
FUEL GAS PIPING
(1) ASME B16.5 or
(2) ASME B16.47. [NFPA 54:5.5.9.1.2]
1208.5.11.3 Non-Ferrous Flanges. Non-ferrous flanges shall be in accordance with ASME B16.24.
[NFPA 54:5.5.9.1.3]
1208.5.11.4 Ductile Iron Flanges. Ductile iron flanges shall be in accordance with ASME B16.42.
[NFPA 54:5.5.9.1.4]
1208.5.11.5 Dissimilar Flange Connections. Raised-face flanges shall not be joined to flat-faced cast iron, ductile iron or nonferrous material flanges.
[NFPA 54:5.5.9.2]
1208.5.11.6 Flange Facings. Standard facings shall be permitted for use under this code. Where 150 psi (1034 kPa) steel flanges are bolted to Class 125 cast-iron flanges, the raised face on the steel flange shall be removed. [NFPA 54:5.5.9.3]
1208.5.11.7 Lapped Flanges. Lapped flanges shall be used only aboveground or in exposed locations accessible for inspection. [NFPA 54:5.5.9.4]
1208.5.12 Flange Gaskets. The material for gaskets shall be capable of withstanding the design temperature and pressure of the piping system and the chemical constituents of the gas being conducted without change to its chemical and physical properties. The effects of fire exposure to the joint shall be considered in choosing the material. [NFPA 54:5.5.10]
1208.5.12.1 Flange Gasket Materials. Acceptable materials shall include the following:
(1) Metal (plain or corrugated)
(2) Composition
(3) Aluminum “O” rings
(4) Spiral-wound metal gaskets
(5) Rubber-faced phenolic
(6) Elastomeric [NFPA 54:5.5.10.1]
1208.5.12.2 Metallic Flange Gaskets. Metallic flange gaskets shall be in accordance with ASME B16.20. [NFPA 54:5.5.10.2.1]
1208.5.12.3 Non-Metallic Flange Gaskets. Non-metallic flange gaskets shall be in accordance with ASME B16.21. [NFPA 54:5.5.10.2.2]
1208.5.12.4 Full-Face Flange Gasket. Full-face flange gaskets shall be used with all non-steel flanges. [NFPA 54:5.5.10.3]
1208.5.12.5 Separated Flanges. When a flanged joint is separated, the gasket shall be replaced. [NFPA 54:5.5.10.4]
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Plumbing Code (Title 24, Part 5)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
- Chapter 5 — WATER HEATERS
- Chapter 6 — WATER SUPPLY AND DISTRIBUTION
- Chapter 7 — SANITARY DRAINAGE
- Chapter 8 — INDIRECT WASTES
- Chapter 9 — VENTS
- Chapter 10 — TRAPS AND INTERCEPTORS
- Chapter 11 — STORM DRAINAGE
▸Chapter 12 — FUEL GAS PIPING
Overview- 1201.1 Applicability. The regulations of this chapter shall
- 1202.1 General. Coverage of piping systems shall extend
- 1202.2 Piping System Requirements. Requirements for
- 1202.3 Applications. This chapter shall not apply to the
- 1203.1 Inspection Notification. Upon completion of the
- 1203.2 Excavation. Excavations required for the installation o…
- 1203.3 Type of Inspections. The Authority Having Jurisdiction …
- 1203.4 Inspection Waived. In cases where the work
- 1204.1 Issuance. Whereupon final piping inspection, the
- 1204.2 Gas Supplier. A copy of the certificate of such final
- 1204.3 Unlawful. It shall be unlawful for a serving gas suppli…
- 1205.1 Authorized Personnel. It shall be unlawful for a
- 1205.2 Outlets. It shall be unlawful to turn on or connect gas
- 1206.1 Disconnection. The Authority Having Jurisdiction
- 1206.2 Notice. Where such disconnection has been made, a
- 1206.3 Capped Outlets. It shall be unlawful to remove or
- 1207.1 General. Where temporary use of gas is desired, and
- 1208.1 Installation of Piping System. Where required
- 1208.2 Interconnections Supplying Separate Users.
- 1208.3 Sizing of Gas Piping Systems. Gas piping systems shall …
- 1208.4 Maximum Operating Pressure in Buildings.
- 1208.5 Acceptable Piping Materials and Joining
- 1208.6 Gas Meters. Gas meters shall be selected for the
- 1208.7 Gas Pressure Regulators. A line pressure regulator shal…
- 1208.8 Overpressure Protection Required. Where the
- 1208.9 Overpressure Protection Devices. Overpressure protectio…
- 1208.10 Pressure Limitation Requirements. Where piping systems…
- 1208.11 Backpressure Protection. Protective devices
- 1208.12 Low-Pressure Protection. A protective device
- 1208.13 Shutoff Valves. Shutoff valves shall be selected in
- 1208.14 Expansion and Flexibility. Piping systems shall
- 1208.15 Pressure Regulator and Pressure Control
- 1209.1 General. Where automatic excess flow valves are
- 1210.1 Piping Underground. Underground gas piping
- 1210.2 CSST Piping Systems. CSST piping systems shall
- 1210.3 Installation of Aboveground Piping. Piping
- 1210.4 Concealed Piping in Buildings. Gas piping in
- 1210.5 Piping in Vertical Chases. Where gas piping
- 1210.6 Gas Pipe Turns. Changes in direction of gas pipe
- 1210.7 Drips and Sediment Traps. For other than dry gas
- 1210.8 Outlets. Outlets shall be located and installed in
- 1210.9 Manual Gas Shutoff Valves. An accessible gas
- 1210.10 Prohibited Devices. Devices shall not be placed
- 1210.11 Systems Containing Gas-Air Mixtures Out-
- 1210.12 Systems Containing Flammable Gas-Air
- 1211.1 Pipe and Tubing Other than CSST. Each aboveground porti…
- 1211.2 Bonding of CSST Gas Piping. CSST gas piping
- 1211.3 Arc-Resistant Jacketed CSST. CSST listed with
- 1211.4 Prohibited Use. Gas piping shall not be used as a
- 1211.5 Lightning Protection System. Where a lightning
- 1211.6 Electrical Circuits. Electrical circuits shall not util…
- 1211.7 Electrical Connections. All electrical connections
- 1211.8 Earthquake-Actuated Gas Shutoff Valves.
- 1212.1 Connecting Appliances and Equipment.
- 1212.4 Injection (Bunsen) Burners. Injection (Bunsen)
- 1212.5 Connection of Portable and Mobile Industrial
- 1212.6 Appliance Shutoff Valves and Connections.
- 1212.7 Quick-Disconnect Devices. Quick-disconnect
- 1212.2 Suspended Low-Intensity Infrared Tube
- 1212.3 Use of Nonmetallic Gas Hose Connectors.
- 1212.8 Gas Convenience Outlets. Appliances shall be
- 1212.9 Sediment Trap. Where a sediment trap is not incorporate…
- 1212.10 Installation of Piping. Piping shall be installed in
- 1212.11 Liquefied Petroleum Gas Facilities and Pip-
- 1213.1 Piping Installations. Prior to acceptance and initial o…
- 1213.2 Test Preparation. Test preparation shall comply
- 1213.3 Test Pressure. This inspection shall include an air,
- 1213.4 Detection of Leaks and Defects. The piping system shall…
- 1213.5 Piping System Leak Test. Leak checks using fuel
- 1213.6 Purging Requirements. The purging of piping
- 1214.1 General. The following regulations shall comply
- 1214.2 Volume. The hourly volume of gas required at each
- 1214.3 Gas Appliances. Where the gas appliances to be
- 1214.4 Size of Piping Outlets. The size of the supply piping o…
- 1215.1 Pipe Sizing Methods. Where the pipe size is to be
- 1215.2 Sizing of Gas Piping Systems. Sizing of piping
- 1215.3 Sizing Equations. The inside diameter of smooth
- 1215.4 Sizing of Piping Sections. To determine the size
- 1215.5 Engineering Methods. For conditions other than
- 1215.6 Variable Gas Pressure. Where the supply gas
- Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
- Chapter 14 — FIRESTOP PROTECTION
- Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
- Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
- Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
- Appendix C — ALTERNATE PLUMBING SYSTEMS
- Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
- Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
- Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
- Appendix G — SIZING OF VENTING SYSTEMS
- Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
- Appendix I — INSTALLATION STANDARDS
- Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
- Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
- Appendix L — SUSTAINABLE PRACTICES
- Appendix M — PEAK WATER DEMAND CALCULATOR
- Appendix N — IMPACT OF WATER TEMPERATURE ON THE POTENTIAL FOR …
- Appendix O — NON-SEWERED SANITATION SYSTEMS
- Appendix P — PROFESSIONAL QUALIFICATIONS
- Appendix Q — INDOOR HORTICULTURAL FACILITIES
- Appendix R — TINY HOUSES
- Appendix S — ONSITE STORMWATER TREATMENT SYSTEMS