802.2 Connection to Venting Systems.
California Mechanical Code (Title 24, Part 4) · 2025 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
Except as permitted in Section 802.2.1 through Section 802.2.7, all appliances shall be connected to venting systems. [NFPA 54:12.3.1]
802.2.1 Appliances Not Required to be Vented. The following appliances shall not be required to be vented:
(1) Listed ranges.
(2) Built-in domestic cooking units listed and marked for optional venting.
(3) Listed hot plates.
(4) Listed Type 1 clothes dryers exhausted in accordance with Section 504.4.
(5) A single listed booster-type (automatic instantaneous) water heater, when designed and used solely for the sanitizing rinse requirements of a dishwashing machine, provided that the appliance is installed with the draft hood in place and unaltered, if a draft hood is required, in a commercial kitchen having a mechanical exhaust system. [Where installed in this manner, the draft hood outlet shall not be less than 36 inches (914 mm) vertically and 6 inches (152 mm) horizontally from any surface other than the appliance.]
(6) Listed refrigerators.
(7) Counter appliances.
(8) Room heaters listed for unvented use.
(9) Direct gas-fired makeup-air heaters.
(10)Other appliances listed for unvented use and not provided with flue collars.
(11)Specialized appliances of limited input such as laboratory burners or gas lights. [NFPA 54:12.3.2]
802.2.2 Maximum Input Rating. Where any or all of the appliances in Section 802.2.1(5) through Section 802.2.1(11) are installed so the aggregate input rating exceeds 20 Btu/h/ft [3] (207 W/m [3] ) of room or space in which it is installed, one or more shall be provided with venting systems or other approved means for conveying the vent gases to the outdoors so that the aggregate input rating of the remaining unvented appliances does not exceed 20 Btu/h/ft [3] (207 W/m [3] ). [NFPA 54:12.3.2.1]
802.2.3 Adjacent Room or Space. Where the calculation includes the volume of an adjacent room or space, the room or space in which the appliances are installed shall be directly connected to the adjacent room or space by a doorway, archway, or other opening of comparable size that cannot be closed. [NFPA 54:12.3.2.2]
802.2.4 Ventilating Hoods. The use of ventilating hoods and exhaust systems to vent appliances shall be limited to industrial appliances and appliances installed in commercial applications. [NFPA 54:12.3.3]
802.2.5 Well-Ventilated Spaces. The flue gases from industrial-type appliances shall not be required to be vented to the outdoors where such gases are discharged into a large and well-ventilated industrial space. [NFPA 54:12.3.4]
802.2.6 Direct Vent Appliances. Listed direct vent appliances shall be installed in accordance with the manufacturer’s installation instructions. [NFPA 54:12.3.5.1]
802.2.6.1 Through-the-Wall Vent Terminations. Through-the-wall vent terminations for listed direct vent appliances shall be in accordance with Section 802.8.1. [NFPA 54:12.3.5.2]
802.2.7 Appliances with Integral Vents. Appliances incorporating integral venting means shall be installed in accordance with Section 802.8.1. [NFPA 54:12.3.6]
802.2.8 Incinerators, Commercial–Industrial. Incinerators shall be vented in accordance with NFPA 82.
[NFPA 54:12.3.7]
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Mechanical Code (Title 24, Part 4)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — VENTILATION AIR
- Chapter 5 — EXHAUST SYSTEMS
- Chapter 6 — DUCT SYSTEMS
- Chapter 7 — COMBUSTION AIR
▸Chapter 8 — CHIMNEYS AND VENTS
Overview- 801.1 Applicability. The requirements of this chapter shall
- 801.2 Venting of Gas Appliances. Low-heat and
- 801.3 Appliances Fueled by Other Fuels. Appliances
- 802.1 Listing. Type B and Type B-W gas vents shall comply with…
- 802.2 Connection to Venting Systems. Except as permitted in Se…
- 802.3 Minimum Safe Performance. Venting systems shall
- 802.4 Type of Venting System to be Used. The type of
- 802.5 Masonry, Metal, and Factory-Built Chimneys.
- 802.6 Gas Vents. The installation of gas vents shall meet
- 802.7 Single-Wall Metal Pipe. Single-wall metal pipe shall
- 802.8 Through-the-Wall Vent Termination. Throughthe-wall vent …
- 802.9 Condensation Drain. Provision shall be made to
- 802.10 Vent Connectors for Category I Appliances.
- 802.11 Vent Connectors for Category II, Category III,
- 802.12 Appliances Requiring Draft Hoods. Vented
- 802.13 Manually Operated Dampers. A manually operated damper s…
- 802.14 Automatically Operated Vent Dampers. An
- 802.15 Obstruction of Flow. Devices that retard the flow
- 803.1 Additional Requirements to Single Appliance
- 803.2 Additional Requirements to Multiple-Appliance
- Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES
- Chapter 10 — BOILERS AND PRESSURE VESSELS
- Chapter 11 — REFRIGERATION
- Chapter 12 — HYDRONICS
- Chapter 13 — FUEL GAS PIPING
- Chapter 14 — PROCESS PIPING
- Chapter 15 — SOLAR ENERGY SYSTEMS
- Chapter 16 — STATIONARY POWER PLANTS
- Chapter 17 — GEOTHERMAL ENERGY SYSTEMS AND AMBIENT TEMPERATURE…
- Chapter 18 — REFERENCED STANDARDS
- Appendix A — RESIDENTIAL PLAN EXAMINER REVIEW FORM FOR HVAC SY…
- Appendix B — PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT …
- Appendix C — INSTALLATION AND TESTING OF OIL (LIQUID) FUEL-FIR…
- Appendix D — FUEL SUPPLY: MANUFACTURED/MOBILE HOME PARKS AND R…
- Appendix E — SUSTAINABLE PRACTICES
- Appendix F — SIZING OF VENTING SYSTEMS AND OUTDOOR COMBUSTION …
- Appendix G — EXAMPLE CALCULATION OF OUTDOOR AIR RATE
- Appendix H — PROFESSIONAL QUALIFICATIONS
- Appendix I — INDOOR HORTICULTURAL FACILITIES
- Appendix J — CLEAN AIR DELIVERY