802.12 Appliances Requiring Draft Hoods. Vented
California Mechanical Code (Title 24, Part 4) · 2025 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
appliances shall be installed with draft hoods.
Exception: Dual oven-type combination ranges; direct vent appliances; fan-assisted combustion system appliances; appli
»
»
»
»
802.10.3.1 Height of Connector. Where two or more vent connectors enter a common vent, chimney flue, or single-wall metal pipe, the smaller connector shall enter at the highest level consistent with the available headroom or clearance to combustible material. [NFPA 54:12.11.4.2]
802.10.3.2 Pressure. Vent connectors serving Category I appliances shall not be connected to any portion of a mechanical draft system operating under positive static pressure, such as those serving Category III or Category IV appliances. [NFPA 54:12.11.4.3]
802.10.4 Clearance. Minimum clearances from vent
connectors to combustible material shall be in accor dance with Table 802.7.3.3.
Exception: The clearance between a vent connector and combustible material shall be permitted to be reduced where the combustible material is protected as specified for vent connectors in Table 303.10.1. [NFPA 54:12.11.5]
802.10.5 Joints. Joints between sections of connector piping and connections to flue collars or draft hood outlets shall be fastened in accordance with one of the following methods:
(1) Mechanically fastened by means of not less than three sheet-metal screws equally spaced around the joint.
(2) Vent connectors of listed vent material assembled and connected to flue collars or draft hood outlets in
accordance with the manufacturer’s instructions.
(3) Other approved means. {NFPA 54:12.11.6}
802.10.6 Connector Junctions. Where vent connectors are joined together, the connection shall be made with a manufactured tee or wye fitting. [NFPA 54:12.11.7]
802.10.7 Slope. A vent connector shall be installed without any dips or sags and shall slope upward toward the vent or chimney at least [1] ⁄ 4 inch per foot (20.8 mm/m).
Exception: Vent connectors attached to a mechanical draft system installed in accordance with appliance and the draft system manufacturers’ instructions. [NFPA 54:12.11.8]
802.10.8 Length of Vent Connector. The length of vent connectors shall comply with Section 802.10.8.1 or Section 802.10.8.2.
802.10.8.1 Single Wall Connector. The maximum horizontal length of a single-wall connector shall be 75 percent of the height of the chimney or vent, except for engineered systems. [NFPA 54:12.11.9.1]
802.10.8.2 Type B Double Wall Connector. The maximum horizontal length of a Type B double-wall connector shall be 100 percent of the height of the chimney or vent, except for engineered systems. The maximum length of an individual connector for a chimney or vent system serving multiple
«
«
«
«
«
«
164 2025 CALIFORNIA MECHANICAL CODE
CHIMNEYS AND VENTS
ances requiring chimney draft for operation; single-firebox boilers equipped with conversion burners with inputs greater than 400 000 Btu/h (117 kW); appliances equipped with blast, power, or pressure burners that are not listed for use with draft hoods; and appliances designed for forced venting. [NFPA 54:12.13.1]
802.12.1 Installation. A draft hood supplied with or forming a part of a listed vented appliance shall be installed without alteration, exactly as furnished and specified by the appliance manufacturer. [NFPA 54:12.13.2]
If a draft hood is not supplied by the appliance manufacturer where one is required, a draft hood shall be installed, be of a listed or approved type, and, in the absence of other instructions, be of the same size as the appliance flue collar. Where a draft hood is required with a conversion burner, it shall be of a listed or approved type. [NFPA 54:12.13.2.1]
802.12.2 Draft Control Devices. Where a draft con trol device is part of the appliance or is supplied by the appliance manufacturer, it shall be installed in accordance with the manufacturer’s instructions. In the
absence of manufacturer’s instructions, the device shall be attached to the flue collar of the appliance or as near to the appliance as practical. [NFPA 54:12.13.3]
802.12.3 Additional Devices. Appliances requiring controlled chimney draft shall be permitted to be equipped with listed double-acting barometric draft regulators installed and adjusted in accordance with the manufacturer’s instructions. [NFPA 54:12.13.4]
802.12.4 Location. Draft hoods and barometric draft
regulators shall be installed in the same room or enclosure as the appliance in such a manner as to prevent any difference in pressure between the hood or regulator and the combustion air supply. [NFPA 54:12.13.5]
802.12.5 Positioning. Draft hoods and draft regulators shall be installed in the position for which they were designed with reference to the horizontal and vertical planes and shall be located so that the relief opening is not obstructed by any part of the appliance or adjacent construction. The appliance and its draft hood shall be located so that the relief opening is accessible for checking vent operation. [NFPA 54:12.13.6]
802.12.6 Clearance. A draft hood shall be located so
that its relief opening is not less than 6 inches (152 mm) from any surface except that of the appliance it serves and the venting system to which the draft hood is connected. Where a greater or lesser clearance is indicated on the appliance label, the clearance shall not be less than that specified on the label. Such clearances shall not be reduced. [NFPA 54:12.13.7]
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Mechanical Code (Title 24, Part 4)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — VENTILATION AIR
- Chapter 5 — EXHAUST SYSTEMS
- Chapter 6 — DUCT SYSTEMS
- Chapter 7 — COMBUSTION AIR
▸Chapter 8 — CHIMNEYS AND VENTS
Overview- 801.1 Applicability. The requirements of this chapter shall
- 801.2 Venting of Gas Appliances. Low-heat and
- 801.3 Appliances Fueled by Other Fuels. Appliances
- 802.1 Listing. Type B and Type B-W gas vents shall comply with…
- 802.2 Connection to Venting Systems. Except as permitted in Se…
- 802.3 Minimum Safe Performance. Venting systems shall
- 802.4 Type of Venting System to be Used. The type of
- 802.5 Masonry, Metal, and Factory-Built Chimneys.
- 802.6 Gas Vents. The installation of gas vents shall meet
- 802.7 Single-Wall Metal Pipe. Single-wall metal pipe shall
- 802.8 Through-the-Wall Vent Termination. Throughthe-wall vent …
- 802.9 Condensation Drain. Provision shall be made to
- 802.10 Vent Connectors for Category I Appliances.
- 802.11 Vent Connectors for Category II, Category III,
- 802.12 Appliances Requiring Draft Hoods. Vented
- 802.13 Manually Operated Dampers. A manually operated damper s…
- 802.14 Automatically Operated Vent Dampers. An
- 802.15 Obstruction of Flow. Devices that retard the flow
- 803.1 Additional Requirements to Single Appliance
- 803.2 Additional Requirements to Multiple-Appliance
- Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES
- Chapter 10 — BOILERS AND PRESSURE VESSELS
- Chapter 11 — REFRIGERATION
- Chapter 12 — HYDRONICS
- Chapter 13 — FUEL GAS PIPING
- Chapter 14 — PROCESS PIPING
- Chapter 15 — SOLAR ENERGY SYSTEMS
- Chapter 16 — STATIONARY POWER PLANTS
- Chapter 17 — GEOTHERMAL ENERGY SYSTEMS AND AMBIENT TEMPERATURE…
- Chapter 18 — REFERENCED STANDARDS
- Appendix A — RESIDENTIAL PLAN EXAMINER REVIEW FORM FOR HVAC SY…
- Appendix B — PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT …
- Appendix C — INSTALLATION AND TESTING OF OIL (LIQUID) FUEL-FIR…
- Appendix D — FUEL SUPPLY: MANUFACTURED/MOBILE HOME PARKS AND R…
- Appendix E — SUSTAINABLE PRACTICES
- Appendix F — SIZING OF VENTING SYSTEMS AND OUTDOOR COMBUSTION …
- Appendix G — EXAMPLE CALCULATION OF OUTDOOR AIR RATE
- Appendix H — PROFESSIONAL QUALIFICATIONS
- Appendix I — INDOOR HORTICULTURAL FACILITIES
- Appendix J — CLEAN AIR DELIVERY