the exhaust air shall be provided to the refrigeration machinery room directly from outside the building. Intakes shall be located as required by other sections of the code and fitted with backdraft dampers or other approved flow-control means to prevent reverse flow. Distribution of makeup air shall be arranged to provide thorough mixing within the refrigeration machinery room to prevent short circuiting of the makeup air directly to the exhaust.
234 2025 CALIFORNIA MECHANICAL CODE
REFRIGERATION
1106.11.6.1 Mechanical Ventilation. The machinery room shall have a mechanical ventilation system in accordance with Section 1106.11.11. The mechanical ventilation system shall:
(1) Run continuously, and failure of the mechanical ventilation system actuates an alarm, or
(2) Be activated by one or more refrigerant detectors, conforming to requirements of Section 1106.11.8. [ASHRAE 15:8.13.6.1] 1106.11.6.2 Detection System. Detection of refrigerant concentration that exceeds 25 percent of the LFL or the upper detection limit of the refrigerant detector, whichever is lower, shall automatically de-energize the following equipment in the machin ery room:
(1) Refrigerant compressors
(2) Refrigerant pumps
(3) Normally closed automatic refrigerant valves
(4) Other unclassified electrical sources of ignition with apparent power rating greater than 1 kVA, where the apparent power is the product of the circuit voltage and current rating. [ASHRAE 15:8.13.6.2] 1106.11.7 Mechanical Equipment Control. Remote control of the mechanical equipment in the refrigerating machinery room shall be provided immediately outside the machinery room door solely for the purpose of shutting down the equipment in an emergency. Ventilation fans shall be on a separate electrical circuit and have a control switch located immediately outside the machinery room door. [ASHRAE 15:8.13.7] 1106.11.8 Refrigerant Detectors. Each refrigerating machinery room in accordance with Section 1106.11 shall contain one or more refrigerant detectors in accordance with Section 1106.11.9. The detector(s) sensing element shall be located in areas where refrigerant from a leak will concentrate, with one or more set points that activate responses in accordance with Section 1106.11.10 for alarms and Section 1106.11.11 for mechanical ventilation. Multiport-type devices shall be prohibited. {ASHRAE 15:8.13.8} 1106.11.9 Refrigerant Detectors Requirements. Refrigerant detectors required by Section 1106.11 shall meet all of the following conditions:
(1) A refrigerant detector shall be capable of detecting each of the specific refrigerant designations in the machinery room.
(2) The refrigerant detector shall activate responses within a time not to exceed a limit specified in Section 1106.11.10 and Section 1106.11.11 after exposure to refrigerant concentration exceeding a limit value specified in Section 1106.11.10 and Section 1106.11.11.
(3) The refrigerant detector shall have a set point not greater than the applicable Occupational Exposure Limit (OEL) value in accordance with Table 1102.3. The applicable OEL value shall be the lowest OEL value for any refrigerant designation in the machinery room. For refrigerants that do not have an OEL value in Table 1102.3, use a value determined in accordance with the OEL as defined by ASHRAE 34 where approved by the Authority Having Jurisdiction.
(4) The refrigerant detector shall have a set point not more than the applicable Refrigerant Concentration Limit (RCL) value in accordance with Table 1102.3. The applicable RCL value shall be the lowest RCL value for any refrigerant designation in the machinery room. For refrigerants that do not have a RCL value in Table 1102.3, use a value determined in accordance with the RCL as defined by ASHRAE 34 where approved by the Authority Having Jurisdiction.
(5) The refrigerant detector shall provide a means for automatic self-testing and shall be in accordance with Section 1106.11.10.4. The refrigerant detector shall be tested during installation and annually thereafter in accordance with the fire code, or at an interval not exceeding the manufacturer’s installation instructions, whichever is less. Testing shall verify compliance with the alarm set points and response times per Section 1106.11.10 and Section 1106.11.11. [ASHRAE 15:8.13.9]
1106.11.10 Alarms. Alarms required by Section 1106.11.8 shall comply with Section 1106.11.10.1 through Section 1106.11.10.4.
1106.11.10.1 Visual and Audio. The alarm shall
have visual and audible annunciation inside the refrigerating machinery room and outside each entrance to the refrigerating machinery room.
[ASHRAE 15:8.13.10.1] 1106.11.10.2 Detector Activation. The refrigerant detector set points shall activate an alarm in accordance with the type of reset in Table 1106.11.10.2. Manual reset type alarms shall have the reset located inside the refrigerating machinery room. [ASHRAE 15:8.13.10.2]
TABLE 1106.11.10.2 REFRIGERANT DETECTOR SET POINTS, RESPONSE TIMES, ALARMS, AND VENTILATION LEVELS
[ASHRAE 15: TABLE 8-1]
| LIMIT VALUE | RESPONSE TIME (seconds) |
ALARM TYPE | ALARM RESET TYPE | VENTILATION RATE | VENTILATION RESET TYPE |
|---|---|---|---|---|---|
| Set point≤ OEL | ≤300 | Trouble Alarm | Automatic | Level 1 | Automatic |
| Set point≤ RCL | ≤15 | Emergency Alarm | Manual | Level 2 | Manual |
REFRIGERATION
1106.11.10.3 Alarm Levels. Alarms set at levels
other than Table 1106.11.10.2 (such as IDLH) and automatic reset alarms are permitted in addition to those required by Section 1106.11.10. The meaning of each alarm shall be clearly marked by signage near the annunciators. [ASHRAE 15:8.13.10.3]
1106.11.10.4 Emergency. In the event of a failure during a refrigerant detector self-test in accordance with Section 1106.11.9(5), a trouble alarm signal shall be transmitted to an approved monitored location. [ASHRAE 15:8.13.10.4]
1106.11.11 Mechanical Ventilation. Machinery rooms, in accordance with Section 1106.11, shall be vented to the outdoors, using mechanical ventilation in accordance with Section 1106.11.11.1, Section 1106.11.11.2, and Section 1106.11.11.3. [ASHRAE 15:8.13.11]
1106.11.11.1 Mechanical Ventilation Require- ments. Mechanical ventilation referred to in Sec tion 1106.11.11 shall be in accordance with all of
the following:
(1) Include one or more power-driven fans capable of exhausting air from the machinery room; multispeed fans shall be permitted.
(2) Electric motors driving fans shall not be placed inside ducts; fan rotating elements shall be nonferrous or non-sparking, or the casing shall consist of or be lined with such material.
(3) Include provision to supply make-up air to replace that being exhausted; ducts for supply to and exhaust from the machinery room shall serve no other area; the makeup air supply locations shall be positioned relative to the exhaust air locations to avoid short circuiting.
(4) Inlets to the exhaust ducts shall be located in an area where refrigerant from a leak will concentrate, in consideration of the location of the replacement supply air paths, refrigerating machines, and the density of the refrigerant relative to air.
(5) Inlets to exhaust ducts shall be within 1 foot (305 mm) of the lowest point of the machinery room for refrigerants that are heavier than air and shall be within 1 foot (305 mm) of the highest point for refrigerants that are lighter than air.
(6) The discharge of the exhaust air shall be to the outdoors in such a manner as not to cause a nui sance or danger. [ASHRAE 15:8.13.11.1]
1106.11.11.2 Level 1 Ventilation Rate. The
refrigerating machinery room mechanical ventilation in Section 1106.11.11.1 shall exhaust at an air flow rate not less than shown in Table 1106.11.11.2.
[ASHRAE 15:8.13.11.2]
TABLE 1106.11.11.2
LEVEL 1 VENTILATION RATE FOR CLASS 2L REFRIGERANTS
[ASHRAE 15: TABLE 8-2]
| STATUS | AIRFLOW |
|---|---|
Operated when occupied and operated when activated in accordance with Section 1106.11.9(3) and Table 1106.11.10.2 |
The greater of the following: (1) 0.5 ft3/min per ft3 of machinery room area, or (2) 20 ft3/min per person |
Operable when occupied |
With or without mechanical cooling of the machinery room, the greater of: (1) The airflow rate required to not exceed a temperature rise of 18°F above inlet air temperature or (2) The airflow rate required to not exceed a maximum air temperature of 122°F in the machinery room. |
For SI units: °C = °F (5/9), 1 cubic foot = 0.0283 m [3], 1 cubic foot per minute = 0.0283 m [3] /min, 1 cubic foot per minute = 0.4719 L/s
1106.11.11.3 Level 2 Ventilation. A part of the refrigerating machinery room mechanical ventilation referred to in Section 1106.11.11.1 shall exhaust an accumulation of refrigerant due to leaks or a rupture of a refrigerating system, or portion thereof, in the machinery room. The refrigerant detectors required in accordance with Section 1106.11.8 shall activate ventilation at a set point and response time in accordance with Table 1106.11.10.2, at an airflow rate not less than the value determined in accordance
with Section 1106.11.11.4.
When multiple refrigerant designations are in the machinery room, evaluate the required airflow according to each refrigerating system, and the highest airflow quantity shall apply.
Ventilation reset shall be in accordance with the type of reset in Table 1106.11.10.2. Manual-type ventilation reset shall have the reset located inside the refrigerating machinery room. [ASHRAE 15:8.13.11.3]
1106.11.11.4 Level 2 Ventilation Rate. When required by Section 1106.11.11.3, the total airflow for Level 2 ventilation shall be not less than the airflow rate determined by Figure 1106.11.11.4.
[ASHRAE 15:8.13.11.4]
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Mechanical Code (Title 24, Part 4)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — VENTILATION AIR
- Chapter 5 — EXHAUST SYSTEMS
- Chapter 6 — DUCT SYSTEMS
- Chapter 7 — COMBUSTION AIR
- Chapter 8 — CHIMNEYS AND VENTS
- Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES
- Chapter 10 — BOILERS AND PRESSURE VESSELS
▸Chapter 11 — REFRIGERATION
Overview- 1101.1 Applicability. Part I governs the design, installation,
- 1101.2 Equipment. Equipment for refrigerant recovery,
- 1102.1 General. Refrigeration systems using a refrigerant
- 1102.2 Ammonia Refrigeration Systems. Refrigeration
- 1102.3 Refrigerants. The refrigerant used shall be of a type
- 1103.1 Classification of Refrigerants. Refrigerants shall
- 1103.2 Classification of Refrigeration Systems.
- 1103.3 Higher Flammability Refrigerants. Group A3
- 1104.1 System Selection. Refrigeration systems shall be
- 1104.2 Refrigerant Concentration Limit (RCL). The
- 1104.3 Institutional Occupancies. The RCL value
- 1104.4 Industrial Occupancies and Refrigerated
- 1104.5 Flammable Refrigerants. The total of Group A2,
- 1104.6 Group A2L Refrigerants for Human Comfort.
- 1104.7 Applications for Human Comfort and for Non-
- 1104.8 Refrigerant Type and Purity. Refrigerants shall
- 1105.3 Access. An unobstructed readily accessible opening and …
- 1105.4 Illumination and Service Receptacles. In addition to th…
- 1105.5 Ventilation of Rooms Containing Condensing
- 1104.9 Changing Refrigerants. Changes of refrigerant in
- 1105.1 Human Comfort. Cooling systems used for human
- 1105.2 Supports and Anchorage. Supports and anchorage for refr…
- 1105.6 Prohibited Locations. Refrigeration systems or
- 1105.7 Condensate. Condensate from air-cooling coils
- 1105.8 Defrost. Where defrost cycles are required for portions…
- 1105.9 Overflows. Where condensate or defrost liquids are
- 1105.10 Condensate, Defrost, and Overflow Dis-
- 1105.11 Refrigerant Port Protection. Air conditioning
- 1105.12 Storage. Refrigerants and refrigerant oils not
- 1106.1 Where Required. Refrigeration systems shall be
- 1106.2 Refrigeration Machinery Room, General
- 1106.3 Normal Operation. A part of the refrigeration
- 1106.7 Maximum Temperature. Ventilation or mechanical cooling …
- 1106.8 Refrigerant Parts in Air Duct. Joints and refrigerant-c…
- 1106.9 Dimensions. Refrigeration machinery rooms shall
- 1106.10 Exits. Exits shall comply with the building code for
- 1106.11 Machinery Room, A2L and B2L. When required
- 1106.4 Natural Ventilation. When a refrigerating system
- 1106.5 Combustion Air. No open flames that use combustion air …
- 1106.6 Ventilation Intake. Makeup air intakes to replace
- 1107.1 General. In cases specified in the rules of Section
- 1108.1 General. Equipment, piping, ducts, vents, or similar
- 1108.2 Electrical. Electrical equipment and installations shall
- 1108.3 Emergency Shutoff. A clearly identified emergency shuto…
- 1108.4 Installation, Maintenance, and Testing. Detection and a…
- 1108.5 Emergency Pressure Control System. Where
- 1109.1 Materials. Materials used in the construction and
- 1109.2 Joints. Iron or steel pipe joints shall be of approved
- 1109.3 Penetration of Piping. Refrigerant piping shall not
- 1109.4 Location of Refrigeration Piping. Refrigerant
- 1109.5 Underground Piping. Refrigerant piping placed
- 1109.6 Support. In addition to the requirements of Section
- 1109.7 Pipe Enclosure. Refrigerant piping and tubing
- 1109.8 Visual Inspection. Refrigerant piping and joints
- 1109.9 Condensation. Piping and fittings that convey
- 1109.10 Identification. Piping shall be in accordance with
- 1110.1 More than 6.6 Pounds of Refrigerant. Systems
- 1110.2 More than 110 Pounds of Refrigerant. Systems
- 1110.3 Support. Stop valves installed in copper refrigerant
- 1110.4 Access. Stop valves required by Section 1110.0 shall
- 1110.5 Identification. Stop valves shall be identified by tagg…
- 1111.1 Where Required. Pressure-limiting devices complying wit…
- 1111.2 Setting. Pressure limiting devices shall be set in
- 1111.3 Location. Stop valves shall not be installed between
- 1111.4 Emergency Stop. Activation of a pressure-limiting
- 1112.1 General. Refrigeration systems shall be protected by
- 1112.2 Positive Displacement Compressor. A positive
- 1112.3 Liquid-Containing Portions of Systems. Liquid-containin…
- 1112.4 Evaporators. Heat exchanger coils located downstream, o…
- 1112.5 Hydrostatic Expansion. Pressure rise resulting
- 1112.6 Actuation. Pressure-relief devices shall be direct
- 1112.7 Stop Valves Prohibited. Stop valves shall not be
- 1112.8 Location. Pressure-relief devices shall be connected
- 1112.9 Materials. The seats and discs of pressure-relief
- 1112.10 Pressure-Relief Valve Setting. Pressure-relief
- 1112.11 Discharge from Pressure-Relief Devices.
- 1112.12 Discharge Piping. The piping used for pressure-relief …
- 1112.13 Rating of Pressure-Relief Device. The rated
- 1112.14 Rating of Rupture Members and Fusible
- 1113.1 General. Pressure vessels shall be provided with
- 1113.2 Type of Protection. Pressure vessels with an internal g…
- 1113.3 Discharging into Lowside of System. For pressure-relief…
- 1113.4 Parallel Pressure-Relief Devices. Two or more
- 1113.5 Discharge Capacity. The minimum required discharge capa…
- 1113.6 Three-Way Valve. Pressure vessels of 10 cubic feet
- 1114.1 General. Systems containing other than Group A1 or
- 1114.2 Design Requirements. Flaring devices shall be
- 1114.3 Testing. Flaring systems shall be tested to demonstrate…
- 1115.1 General. In addition to labels required elsewhere in
- 1115.2 Volume and Type. A condenser, receiver, absorber,
- 1115.3 Permanent Sign. In a refrigeration machinery
- 1115.4 Marking of Pressure-Relief Devices. Pressurerelief valv…
- 1115.5 Nameplate. Each self-contained system and each
- 1116.1 Factory Tests. Refrigerant-containing parts of unit
- 1116.2 Field Tests. Refrigerant-containing parts of a system t…
- 1116.3 Test Gases. Tests shall be performed with dry nitrogen …
- 1116.4 Declaration. A dated declaration of test shall be
- 1116.5 Brine Systems. Brine-containing portions of a system sh…
- 1117.1 Inside Dimensions 6 Inches or Less. Pressure
- 1117.2 Inside Dimensions More than 6 Inches. Pressure vessels …
- 1117.3 Pressure Vessels for 15 psig or Less. Pressure
- 1118.1 General. Refrigeration systems shall be operated and
- 1119.1 Applicability. Cooling towers, evaporative condensers, …
- 1120.1 General. Cooling towers, evaporative condensers,
- 1121.1 General. Drains, overflows, and blow-down provisions sh…
- 1122.1 General. Chemical treatment systems shall comply
- 1122.2 Automated Control of Cycles of Concentra-
- 1123.1 General. Cooling towers, evaporative condensers,
- 1124.1 General. Electrical systems shall be in accordance
- 1125.1 General. Equipment containing refrigerants as a part
- 1126.1 General. Cooling towers, evaporative condensers,
- 1127.1 General. Cooling towers, evaporative coolers and
- Chapter 12 — HYDRONICS
- Chapter 13 — FUEL GAS PIPING
- Chapter 14 — PROCESS PIPING
- Chapter 15 — SOLAR ENERGY SYSTEMS
- Chapter 16 — STATIONARY POWER PLANTS
- Chapter 17 — GEOTHERMAL ENERGY SYSTEMS AND AMBIENT TEMPERATURE…
- Chapter 18 — REFERENCED STANDARDS
- Appendix A — RESIDENTIAL PLAN EXAMINER REVIEW FORM FOR HVAC SY…
- Appendix B — PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT …
- Appendix C — INSTALLATION AND TESTING OF OIL (LIQUID) FUEL-FIR…
- Appendix D — FUEL SUPPLY: MANUFACTURED/MOBILE HOME PARKS AND R…
- Appendix E — SUSTAINABLE PRACTICES
- Appendix F — SIZING OF VENTING SYSTEMS AND OUTDOOR COMBUSTION …
- Appendix G — EXAMPLE CALCULATION OF OUTDOOR AIR RATE
- Appendix H — PROFESSIONAL QUALIFICATIONS
- Appendix I — INDOOR HORTICULTURAL FACILITIES
- Appendix J — CLEAN AIR DELIVERY