1004.4 Minimum Capacity of Closed-Type Tank — 2025 California Mechanical Code

California Mechanical Code (Title 24, Part 4) · 2025 edition · updated 2026-09-25 · California

CBSC: official editions, supplements and errata

Italicized text is a California amendment to the model code, as printed in the official publication.

Cite as: 2025 California Mechanical Code (Title 24, Part 4) § 1004.4 · Effective January 1, 2026 · Official source: Building Standards Commission

The minimum capacity for a gravity-type hot water system expansion tank shall be in accordance with Table 1004.4(1). The minimum capacity for a forced-type hot water system expansion tank shall be in accordance with Table 1004.4(2) or Equation 1004.4(1). The minimum capacity for a diaphragmtype hot water system expansion tank shall be in accordance with Table 1004.4(2) or Equation 1004.4(2).

[Equation 1004.4(1)]

Vt (forced-type) = [(0.00041] [t] [ - 0.0466) ] [V][s]

(

P P a a

Pf Po )

[Equation 1004.4(2)]

Vt (diaphragm-type) = [(0.00041] [t] [ - 0.0466) ] [V][s]

– [P][f]

[1]

( Po )

Where:

Vt = Minimum volume of expansion tank, gallons. Vs = Volume of system, not including expansion tank, gallons.

t = Average operating temperature, °F.

Pa = Atmospheric pressure, pounds per square inch. Pf = Fill pressure, pounds per square inch. Po = Maximum operating pressure, pounds per square inch.

For SI units: 1 gallon = 3.785 L

218 2025 CALIFORNIA MECHANICAL CODE

BOILERS AND PRESSURE VESSELS

TABLE 1004.4(1) EXPANSION TANK CAPACITIES FOR GRAVITY HOT WATER SYSTEMS [1]

INSTALLED EQUIVALENT
DIRECT RADIATION2
(square feet)
TANK CAPACITY
(gallons)

Up to 350
18

Up to 450
21

Up to 650
24


Up to 900
30


Up to 1100
35


Up to 1400
40


Up to 1600
2 to 30


Up to 1800
2 to 30

Up to 2000
2 to 35

Up to 2400
2 to 40

For SI units: 1 gallon = 3.785 L, 1 square foot = 0.0929 m [2]

Notes: 1 Based on a two-pipe system with an average operating water temperature of 170°F (77°C), using cast-iron column radiation with a heat emission rate of 150 British thermal units per square foot hour [Btu/(ft [2] - h)] (473 W/m [2] ) equivalent direct radiation. 2 For systems that exceed 2400 square feet (222.9 m 2 ) of installed equivalent direct water radiation, the required capacity of the cushion tank shall be increased on the basis of 1 gallon (4 L) tank capacity per 33 square feet (3.1 m [2] ) of additional equivalent direct radiation.

TABLE 1004.4(2) EXPANSION TANK CAPACITIES FOR FORCED HOT WATER SYSTEMS [1]

SYSTEM VOLUME2
(gallons)
TANK CAPACITY
DIAPHRAGM TYPE
(gallons)
TANK CAPACITY NON-
DIAPHRAGM TYPE
(gallons)


100
9 15


200
17 30


300
25 45

400
33 60

500
42 75

1000
83 150

2000
165 300

For SI units: 1 gallon = 3.785 L

Notes: 1 Based on an average operating water temperature of 195°F (91°C), a fill pressure of 12 psig (83 kPa), and an operating pressure of not more than 30 psig (207 kPa). 2 Includes volume of water in boiler, radiation, and piping, not including expansion tank.