Chapter 10 — BOILERS AND PRESSURE VESSELS
1010.2 Power Boilers — 2025 California Mechanical Code
California Mechanical Code (Title 24, Part 4) · 2025 edition · updated 2026-09-25 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
Cite as: 2025 California Mechanical Code (Title 24, Part 4) § 1010.2 · Effective January 1, 2026 · Official source: Building Standards Commission
Power boilers having a steam-generating capacity in excess of 5000 pounds per hour (lb/h) (0.6299 kg/s) or having a heating surface in excess of 1000 square feet (92.9 m [2] ) or input in excess of 5 000 000 Btu/h (1464 kW) shall have a clearance of not less than 7 feet (2134 mm) from the top of the boiler to the ceiling.
Explained in plain English
Guides that cite this section.
Get a plain-English answer with a citation back to this text.
Ask AI about this code