Chapter 80 — REFERENCED STANDARDS
Section CC105 — DISTRIBUTION OF FIRE HYDRANTS
2025 California Fire Code (Title 24, Part 9) · 2025 edition · ingested 2026-07-07 · California
Full text via GoCodebook AI
We have the complete 2025 text of this code. Ask a question and get the exact controlling section with a citation.
CC105.1 The average spacing between fire hydrants shall not exceed that listed in Table CC105.1. ¶
CC105.1 The average spacing between fire hydrants shall not exceed that listed in Table CC105.1. Exception: A deficiency of up to 10 percent shall not be allowed when existing fire hydrants provide all, or a portion, of the required fire hydrant service. Regardless of the average spacing, fire hydrants shall be located such that all points on streets and access roads adjacent to a build- ing are within the distances listed in Table CC105.1.
CC105.2 When public or private water mains are not available to supply fire flow [not… ¶
CC105.2 When public or private water mains are not available to supply fire flow [not within 1,000 feet (304 800 mm) of the proposed building], the following alternatives shall be used: 1. Building(s) shall be protected by an automatic sprinkler system Exception: Portable (relocatable) buildings, as defined in California Education Code Section 17742.5(e), which requires that portable buildings be designed and constructed to be relocatable over public streets, shall be designed and constructed for relocation without the separation of the roof or floor from the building and when measured at the…