C102.1 Minimum number of fire hydrants for a building. ¶
C102.1 Minimum number of fire hydrants for a building. The number of fire hydrants available to a building shall be not less than the minimum specified in Table C102.1. TABLE C102.1—REQUIRED NUMBER AND SPACING OF FIRE HYDRANTShCol2Col3Col4 ------------ FIRE-FLOW REQUIREMENT<br(gpm)MINIMUM NUMBER OF<brHYDRANTSAVERAGE SPACING<brBETWEEN HYDRANTSa, b, c, f, g<br(feet)MAXIMUM DISTANCE FROM ANY<brPOINT ON STREET OR ROAD<brFRONTAGE TO A HYDRANTd, f, g 1,750 or less1500250 1,751–2,2502450225 2,251–2,7503450225 2,751–3,2503400225 3,251–4,0004350210 4,001–5,0005300180 5,001–5,5006300180…