436.1 Group I-4 special provisions.

436.1 Group I-4 special provisions. Rooms classified as Group I-4 shall not be located above or below the first story. Exceptions: 1. Basements or stories having floor levels located within 4 feet (1219 mm), measured vertically, from adjacent ground level at the level of exit discharge, provided the basement or story has exterior exit doors at that level. 2. Group I-4 child-care center or adult cay care may be located above the first story in buildings of Types I-A, I-B, II-A, III-A, IV-A, IV-B and IV-C construction, subject to the limitation of Section 503 when: 2.1. Group I-4 child-care…