Chapter 80 — REFERENCED STANDARDS
Section BB105 — FIRE-FLOW REQUIREMENTS FOR BUILDINGS
2025 California Fire Code (Title 24, Part 9) · 2025 edition · ingested 2026-07-07 · California
Full text via GoCodebook AI
We have the complete 2025 text of this code. Ask a question and get the exact controlling section with a citation.
BB105.1 The minimum fire flow and flow duration for school buildings shall be as specified in Table BB105.1. ¶
BB105.1 The minimum fire flow and flow duration for school buildings shall be as specified in Table BB105.1. Exception: A reduction in required fire flow of up to 75 percent is allowed when the building is provided with an approved automatic sprinkler system. When a reduction in fire flow is used, fire flow shall not be less than 1500 GPM. on Jul 18, 2025 11:14 AM (CDT) THEREUNDER. APPENDIX BB—FIRE-FLOW REQUIREMENTS FOR BUILDINGS TABLE BB105.1—MINIMUM REQUIRED FIRE-FLOW AND FLOW DURATION FOR BUILDINGSCol2Col3Col4Col5Col6Col7 --------------------- FIRE AREA (square feet)FIRE AREA (square…