Chapter 80 — REFERENCED STANDARDS
Section B104 — FIRE-FLOW CALCULATION AREA
2025 California Fire Code (Title 24, Part 9) · 2025 edition · ingested 2026-07-07 · California
Full text via GoCodebook AI
We have the complete 2025 text of this code. Ask a question and get the exact controlling section with a citation.
B104.1 General. ¶
B104.1 General. The fire-flow calculation area shall be the total floor area of all floor levels within the exterior walls, and under the horizontal projections of the roof of a building. Exceptions: 1. The fire-flow calculation area of buildings constructed of Types IA and IB construction shall be the area of the three largest successive floors. 2. The fire-flow calculation area for open parking garages of Types IA and IB construction shall be determined by the area of the largest floor.
B104.2 Area separation. ¶
B104.2 Area separation. Portions of buildings that are separated by fire walls without openings, constructed in accordance with the California Building Code, are allowed to be considered as separate fire-flow calculation areas.