315.1 General. Existing buildings housing existing protective

social-care homes or facilities established prior to March 4,

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

PROVISIONS FOR ALL COMPLIANCE METHODS

1972 may have their use continued if they conform, or are made to conform, to the following provisions:

315.2 Use of floors. The use of floor levels in buildings of

Type III, IV or V nonfire-rated construction may be as fol- lows: Nonambulatory—first floor only; Ambulatory—not higher than the third-floor level, provided walls and parti- tions are constructed of materials equal in fireresistive qual- ity to that of wood lath and plaster in good repair and all walls are firestopped at each floor level.

315.3 Enclosure of exits and vertical openings. Except for

two-story structures housing ambulatory guests, all interior stairs shall be enclosed in accordance with Chapter 10 of the California Building Code. In lieu of stairway enclosures, floor separations or smoke barriers may be provided in such a man- ner that fire and smoke will not spread rapidly to floors above or otherwise impair exit facilities. In these instances, floor sep- arations or smoke barriers shall have a fire resistance equal to not less than 1 /2-inch (13 mm) gypsum wall board on each side of wood studs with openings protected by not less than a 1 3 /4- inch (44.5 mm) solid bonded wood-core door of the self-clos- ing type. All other vertical openings shall be enclosed in accor- dance with the provisions of Section 314.6 and 314.13.

315.4 Exit access. Each floor or portion thereof of buildings

used for the housing of existing protective social-care homes or facilities shall have access to not less than two exits in such a manner as to furnish egress from the building or struc- ture in the event of an emergency substantially equivalent to the provisions of Chapter 10 of the California Building Code.

315.5 Corridor openings. Openings from rooms to interior

corridors shall be protected by not less than 1 3 /4-inch (44.5 mm) solid-bonded wood-core doors. Transoms and other similar openings shall be sealed with materials equivalent to existing corridor wall construction.

315.6 Interior finishes. Interior wall and ceiling finishes shall

conform to the requirements for a Group R-1 Occupancy as specified in Chapter 8 of the California Building Code.

315.7 Automatic fire sprinklers. Automatic sprinkler systems

shall be installed in existing protective social-care occupan- cies in accordance with the provisions of Section 903.2.6 of the California Building Code.

315.8 Fire alarm systems. Automatic fire alarm systems shall

be installed in existing protective social-care homes or facili- ties in accordance with the provisions of Section 907.2.6 of the California Building Code.

Exception: When an approved automatic sprinkler system conforming to Section 903.2.6 of the California Building Code is installed, a separate fire alarm system as specified in this section need not be provided.