Chapter 16 — REFERENCED STANDARDS

California Existing Building Code (Title 24, Part 10) · 2022 edition · updated 2026-09-10 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

(Matrix Adoption Tables are nonregulatory, intended only as an aid to the code user.

See Chapter 1 for state agency authority and building applications.)

Adopting Agency BSC BSC-
CG
SFM HCD DSA OSHPD BSCC DPH AGR DWR CEC CA SL SLC
Adopting Agency BSC BSC-
CG
SFM 1 2 1/AC AC SS SS/CC 1 1R 2 3 4 5 5 5 5 5 5 5 5 5
Adopt Entire Chapter X X X X
Adopt Entire Chapter as
amended (amended
sections listed below)
X X X X X X X X
Adopt only those sections
that are listed below
Chapter / Section
ASCE/SEI 7—2016 X X X X X X X
ASCE/SEI 41—2013 X
ASCE/SEI 41—2017 X X X X
ASTM A61515ae1 X
ICC CBC—22 X
NFPA 13R—22 X
NFPA 72—22 X

The state agency does not adopt sections identified with the following symbol: The Office of the State Fire Marshal’s adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

16-2 2022 CALIFORNIA EXISTING BUILDING CODE

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

CHAPTER 16

REFERENCED STANDARDS

User note:

About this chapter: This code contains numerous references to standards that are used to regulate materials and methods of construction. Chapter 16 contains a comprehensive list of all standards that are referenced in the code, including the appendices. The standards are part of the code to the extent of the reference to the standard. Compliance with the referenced standard is necessary for compliance with this code. By providing specifically adopted standards, the construction and installation requirements necessary for compliance with the code can be readily determined. The basis for code compliance is, therefore, established and available on an equal basis to the building code official, contractor, designer and owner.

Compliance with the referenced standard is necessary for compliance with this code._ By providing specifically adopted standards, the construction and installation requirements necessary for compliance with the code can be readily determined. The basis for code compliance is, therefore, established and available on an equal basis to the building code official, contractor, designer and owner.

This chapter lists the standards that are referenced in various sections of this document. The standards are listed herein by the promulgating agency of the standard, the standard identification, the effective date and title, and the section or sections of this document that reference the standard. The application of the referenced standards shall be as specified in Section 102.4, or California Administration Division 1, as appli- cable. [OSHPD 1] Reference to other chapters. In addition to the code sections referenced, the standards listed in this chapter are applicable to the respective code sections in Chapters 2, 3A, 4A and 5A.

ASCE/SEI American Society of Civil Engineers

Structural Engineering Institute

1801 Alexander Bell Drive Reston, VA 20191-4400 7—1988: Minimum Design Loads and Associated Criteria for Buildings and Other Structures 503.12, 706.3.2

7—1993: Minimum Design Loads and Associated Criteria for Buildings and Other Structures 503.12, 706.3.2

7—1995: Minimum Design Loads and Associated Criteria for Buildings and Other Structures 503.12, 706.3.2

7—1998: Minimum Design Loads and Associated Criteria for Buildings and Other Structures 503.12, 706.3.2

7—2002: Minimum Design Loads and Associated Criteria for Buildings and Other Structures 503.12, 706.3.2

7—2005: Minimum Design Loads and Associated Criteria for Buildings and Other Structures 503.12, 706.3.2

7—2010: Minimum Design Loads and Associated Criteria for Buildings and Other Structures 503.12, 706.3.2

7—2016: Minimum Design Loads and Associated Criteria for Buildings and Other Structures with Supplement 1 [OSHPD 1, 1R, 2, 4 and 5, DSA-SS, DSA-SS/CC] and Supplement 3

304.2, 304A.2, 304.3.1, 501A.3, 502A.5, 503.4, 503.12, 503.13, 503A.13, 706.3.2, 805.3, 805.4

41— 2013 : [OSHPD 1] Seismic Evaluation and Retrofit of Existing Buildings 304A.2, 304A.3.4, 304A.3.5

41—2017: Seismic Evaluation and Retrofit of Existing Buildings [OSHPD 1R, 2, 4 and 5] with Supplement No. 1 304.3.1, Table 304.3.1, 304.3.2, Table 304.3.2

ASHRAE ASHRAE 1791 Tullie Circle NE Atlanta, GA 30329 62.1—2019: Ventilation for Acceptable Indoor Air Quality 807.2

ASME American Society of Mechanical Engineers

Two Park Avenue New York, NY 10016 A17.1—2019/CSA B44—19: Safety Code for Elevators and Escalators

306.7.7, 902.1.2

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

REFERENCED STANDARDS

ASME—continued

A17.3—2020: Safety Code for Existing Elevators and Escalators

902.1.2

A18.1—2020: Safety Standard for Platform Lifts and Stairway Chair Lifts

306.7.8

ASTM ASTM International 100 Barr Harbor Drive, P.O. Box C700 West Conshohocken, PA 19428-2959 A615 –15ae1: Specification for Deformed and Plain Carbon-steel Bars for Concrete Reinforcement:

303A.3.5.3

C94/C94M—17A: Specification for Ready-mixed Concrete

109.3.1

E108—17: Standard Test Methods for Fire Tests of Roof Coverings

1204.5

E136—16A: Test Method for Behavior of Materials in a Vertical Tube Furnace at 750°C

202

F2006—17: Standard Safety Specification for Window Fall Prevention Devices for Non-Emergency Escape (Egress) and Rescue

(Ingress) Windows

505.2, 702.4

F2090—17: Standard Specification for Window Fall Prevention Devices with Emergency (Egress) Release Mechanisms

505.2, 505.3.1, 702.4, 702.5.1

ICC International Code Council, Inc. 500 New Jersey Avenue NW 6th Floor Washington, DC 20001 CBC—22: California Building Code

101.4.1, 104.2.1, 106.2.2, 109.3.3, 109.3.6, 109.3.9, 109.3.10, 110.2, 201A.3, 202, 202A, 301A.1, 301A.5, 301.3, 302A.4, 302.4.1, 302.5, 303.1, 303A.1, 303.2.2, 304.1, 304A.1, 304.3.1, 304.3.2, 305.1, 306.5, 306.7, 306.7.2, 306.7.4, 306.7.5, 306.7.9, 306.7.10, 306.7.10.1, 306.7.10.2, 306.7.10.3, 306.7.11, 306.7.12, 306.7.13, 306.7.15, 306.7.16, 306.7.16.3, 306.7.16.4, 306.7.16.5, 306.7.16.7, 309.2, 309A.2, 309A.3, 309A.6, 310A.2, 310A.3, 401.3, 401A.3, 402A, 402.1, 405A.1, 405A.2, 405.2.1.1, 405.2.3.1, 405.2.3.3, 405.2.4, 405.2.5, 405.2.6, 501.2, 501A.3, 502A.1, 502.1, 502.3, 502A.3, 502.4, 502A.4, 502.5, 502A.5, 503.1, 503A.1, 503.2, 503A.2, 503.3, 503A.3, 503.4, 503A.4, 503.5, 503.11, 503.12, 503.13, 503A.13, 503.14, 503.15, 503.17, 503.18, 505.3, 505.4, 506.1, 506A.1, 506.3, 506A.3, 506A.4, 506.4, 506.5.1, 506.5.2, 506.5.3, 506.5.4, 507.3, 701.2, 701.3, 702.1, 702.2, 702.3, 702.5, 702.6, 702.7, 704.1.1, 704.3, 705.1, 705.2, 706.2, 706.3.2, 802.2.1, 802.2.3, 802.3, 802.4, 802.5.2, 802.6, 802.6, 803.1.1, 803.2, 803.2.2, 803.2.3, 803.2.4, 803.2.5, 803.3, 804.1, 804.4.1, 804.4.1.1, Table 804.4.1.1(1), 804.4.1.2.1, 804.5.1.2, 804.5.3, 804.5.4, 804.5.5, 804.6, 804.7, 804.8.1, 804.9.1, 804.10.2, 804.11, 804.12.2, 805.2, 805.3, 805.4, 904.1.2, 904.1.3, 904.1.4, 904.1.6, 904.1.7, 904.2, 904.2.1, 904.2.2, 905.2, 905.3, 905.4, 906.2, 906.3, 906.6, 1001.2, 1001.3, 1002.1, 1002.2, 1002.3, 1002.4, 1004.1, 1006.1, 1006.2, 1006.3, 1006.4, 1010.1, 1011.1, 1011.2.1, 1011.2.2, 1011.3, 1011.5.1, 1011.5.2, 1011.5.3, 1011.5.6, 1011.6.1, 1011.6.1.1, 1011.6.3, 1011.7.1, 1011.7.2, 1011.7.3, 1011.8.1, 1011.8.2, 1011.8.3, 1102.1, 1102.2, 1102.3, 1103.1, 1103.2, 1103.3, 1201.4, 1202.2, 1203.12, 1204.2, 1204.9, 1206.1, 1301.2.2, 1301.2.3, 1301.2.4, 1301.3.3, 1301.4.1, 1301.6.1, 1301.6.1.1, 1301.6.2, 1301.6.2.1, 1301.6.3.2, 1301.6.3.3, 1301.6.4.1, 1301.6.5, 1301.6.5.1, 1301.6.6, 1301.6.7.1, 1301.6.8, 1301.6.9, 1301.6.9.1, 1301.6.10, 1301.6.10.1, 1301.6.11, 1301.6.11.1, 1301.6.12.1, 1301.6.13, Table 1301.6.15, 1301.6.15.1, 1301.6.16.1, 1301.6.17, 1301.6.17.1, 1301.6.18, 1301.6.18.1, 1301.6.19, Table 1301.6.19, 1301.6.20, 1301.6.20.1, 1301.9.1, 1401.2, 1402.1, 1402.2, 1402.2.1, 1402.3, 1402.4, 1402.5, 1402.6, 1501.5, 1501.6.1, 1501.6.4.1, 1501.6.7, 1506.1, 1506.3, 1507.1

ICC 300—17: ICC Standard on Bleachers, Folding and Telescopic Seating and Grandstands

301.1.1

ICC 500—20: Standard for the Design and Construction of Storm Shelters

303.1, 303.2

ICC A117.1—17: Accessible and Usable Buildings and Facilities

306.3, 306.7, 306.7.11, 306.7.12

CEC —21: California Energy Code

302.2, 702.7, 708.1, 809.1, 907.1, 1104.1

16-4 2022 CALIFORNIA EXISTING BUILDING CODE

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

REFERENCED STANDARDS

ICC—continued CFC—22: California Fire Code

101.2.1, 101.4.2, 301.3.1, 302.2, 307.1, 308.1, 802.2.1, 802.2.3, 803.2.3, 803.4.1.1, 803.4.1.2, 803.4.1.3, 803.4.1.4, 803.4.1.5, 803.4.1.6, 904.1.5, 1011.6.1.1, 1301.3.2, 1301.6.8.1, 1301.6.14, 1301.6.14.1, 1401.2, 1501.5, 1504.1, 1504.2

IFGC—21: International Fuel Gas Code ®

302.2, 702.7.1

CMC—22: California Mechanical Code

302.2, 702.7, 807.1, 902.1.1, 1008.1, 1301.6.7.1, 1301.6.8, 1301.6.8.1

CPC—22: California Plumbing Code

302.2, 408.1, 702.7, 1009.1, 1009.2, 1009.3, 1009.5, 1501.7

IPMC—21: International Property Maintenance Code ®

101.4.2, 302.2, 1301.3.2, 1401.2

CRC—22: California Residential Code

101.2, 101.4.1, 104.2.1, 109.3.3, 109.3.10, 302.2, 307.1, 308.1, 401.3, 402.1, 405.2.6, 502.3, 502.4, 502.5, 503.2, 503.3, 503.11, 505.2, 505.3, 507.3, 701.3, 702.4, 702.5, 706.2, 708.1, 805.2, 806.4, 809.1, 906.2, 907.1, 1011.2.1, 1103.1, 1103.2, 1103.3, 1104.1, 1201.4, 1301.2.2, 1301.2.3, 1301.3.3, 1401.2, 1402.1, 1402.2, 1402.2.1, 1402.3, 1402.4, 1402.5, 1402.6

NFPA National Fire Protection Association

1 Batterymarch Park Quincy, MA 02169-7471 NFPA 13R— 22 : Standard for the Installation of Sprinkler Systems in Residential Occupancies up to and Including Four Stories in Height

803.2.4

Add new Sections 6.6.10 and 6.6.10.1 as follows:

6.6.10 Solar photovoltaic panel structures.

6.6.10.1 Sprinklers shall be permitted to be omitted from the following structures: (1) Solar photovoltaic panel structures with no use underneath. Signs may be provided, as determined by the enforcing agency prohibiting any use underneath including storage. (2) Solar photovoltaic (PV) panels supported by framing that have sufficient uniformly distributed and unobstructed openings throughout the top of the array (horizontal plane) to allow heat and gases to escape, as determined by the enforcing agency.

Revise Section 11.4 as follows:

11.4 Instructions.

The installing contractor shall provide the property owner or the property owner's authorized representative with the following:

(1) All literature and instructions provided by the manufacturer describing proper operation and maintenance of any equipment and devices installed. (2) NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems 2013 California Edition and Title 19, California Code of Regulations, Chapter 5. (3) Once the system is accepted by the authority having jurisdiction, a label as prescribed by Title 19, California Code of Regulations, Chapter 5, shall be affixed to each system riser. CEC—22: California Electrical Code

107.3, 302.2, 406.1.1, 406.1.2, 406.1.3, 406.1.5, 806.1, 806.4.4, 1007.1, 1007.2, 1007.3, 1007.4

NFPA 72— 22 : National Fire Alarm and Signaling Code

803.2.6, 803.4

Revise Section 10.3.1 as follows: 10.3.1 Equipment constructed and installed in conformity with this Code shall be listed for the purpose for which it is used. Fire alarm systems and components shall be California State Fire Marshal approved and listed in accordance with California Code of Regulations, Title 19, Division 1.

Revise Section 10.3.3 as follows: 10.3.3 All devices and appliances that receive their power from the initiating device circuit or signaling line circuit of a control unit shall be California State Fire Marshal listed for use with the control unit.

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

REFERENCED STANDARDS

NFPA—continued

Revise Section 12.3.8.1 as follows: 12.3.8.1 The outgoing and return (redundant) circuit conductors shall be permitted in the same cable assembly (i.e., multiconductor cable), enclosure or raceway only under the following conditions:

(1) For a distance not to exceed 10 feet (3.0 m) where the outgoing and return conductors enter or exit the initiating device, notification appliance, or control unit enclosures. (2) Single drops installed in the raceway to individual devices or appliances. (3) *In a single room not exceeding 1000 feet 2 (93 m 2 ) in area, a drop installed in the raceway to multiple devices or appliances that does not include any emergency control function devices. (4) Where the vertically run conductors are contained in a 2-hour rated cable assembly, or enclosed (installed) in a 2-hour rated enclosure or a listed circuit integrity (C.I.) cable, which meets or exceeds a 2-hour fire-resistive rating.

Revise Section 14.4.6.1 as follows: 14.4.6.1 Testing. Household fire alarm systems shall be tested in accordance with the manufacturer’s published instructions according to the methods of Table 14.4.3.2.

Revise Section 17.16 as follows:

17.16 Fire Extinguisher Electronic Monitoring Device .

A fire extinguisher electronic monitoring device shall indicate those conditions_ for a specific fire extinguisher required by California Code of Regulations, Title 19, Division 1, Chapter 1, Section 574.2(c) and California Fire Code to a fire alarm control unit.

Revise Section 12.3.8 as follows: 12.3.8 (4) Where the vertically run conductors are contained in a 2-hour rated cable assembly, or enclosed (installed) in a 2-hour rated enclosure or a listed circuit integrity (C.I.) cable, which meets or exceeds a 2-hour fire resistive rating.

Revise Section 23.8.5.1.2 as follows: _23.8.5.1.2_* Where connected to a supervising station, fire alarm systems employing automatic fire detectors or waterflow detection devices shall include a manual fire alarm box to initiate a signal to the supervising station.

Exception: Fire alarm systems dedicated to elevator recall control, supervisory service and fire sprinkler monitoring as permitted in Section 17.15 of NFPA 72.

Revise Section 23.8.5.4.1 as follows: 23.8.5.4.1 Systems equipped with alarm verification features shall be permitted under the following conditions:

(1) The alarm verification feature is not initially enabled unless conditions or occupant activities that are expected to cause nuisance alarms are anticipated in the area that is protected by the smoke detectors. Enabling of the alarm verification feature shall be protected by password or limited access. (2) A smoke detector that is continuously subjected to a smoke concentration above alarm threshold does not delay the system functions of Sections 10.7 through 10.16, 23.8.1.1, or 21.2.1 by more than 30 seconds. (3) Actuation of an alarm-initiating device other than a smoke detector causes the system functions of Sections 10.7 through 10.16, 23.8.1.1, or 21.2.1 without additional delay. (4) The current status of the alarm verification feature is shown on the record of completion [see Figure 7.8.2(a), Item 4.3]. (5) Operation of a patient room smoke detector in I-2 and R-2.1 occupancies shall not include an alarm verification feature.

Revise Section 29.3.1 as follows: 29.3.1 All devices, combinations of devices and equipment to be installed in conformity with this chapter shall be approved and listed by the California State Fire Marshal for the purposes for which they are intended.

Revise Section 29.5.2.1.1 as follows: _29.5.2.1.1_* Smoke and Heat Alarms. Where connected to a supervising station unless exempted by applicable laws, codes or standards, smoke or heat alarms used to provide a fire-warning function, and when two or more alarms are installed within a dwelling unit, suite of rooms or similar area, shall be arranged so that the operation of any smoke or heat alarm causes all alarms within these locations to sound.

Note: Exception to 29.8.2.1.1 not adopted by the SFM.

Add Section 29.10.2.1 as follows: 29.10.2.1 The alarm verification feature shall not be used for household fire warning equipment.

Add Section 29.10.6.8.1 as follows: 29.10.6.8.1 The alarm verification feature shall not be used for household fire warning equipment.

NFPA 99—21: Health Care Facilities Code

302.2.1, 406.1.4, 408.3, 501.3, 707.1, 806.3, 808.1, 1007.1

NFPA 101—21: Life Safety Code

804.2

16-6 2022 CALIFORNIA EXISTING BUILDING CODE

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

REFERENCED STANDARDS

UL UL LLC 333 Pfingsten Road Northbrook, IL 60062 790—04: Standard Test Methods for Fire Tests of Roof Coverings—with Revisions through October 2018 1204.5

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

16-8 2022 CALIFORNIA EXISTING BUILDING CODE

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

CALIFORNIA EXISTING BUILDING CODE – MATRIX ADOPTION TABLE

APPENDIX A CHAPTER A1 – SEISMIC STRENGTHENING PROVISIONS FOR UNREINFORCED MASONRY BEARING WALL BUILDINGS

(Matrix Adoption Tables are nonregulatory, intended only as an aid to the code user.

See Chapter 1 for state agency authority and building applications.)

Adopting Agency BSC BSC-
CG
SFM HCD DSA OSHPD BSCC DPH AGR DWR CEC CA SL SLC
Adopting Agency BSC BSC-
CG
SFM 1 2 1/AC AC SS SS/CC 1 1R 2 3 4 5 5 5 5 5 5 5 5 5
Adopt Entire Chapter
Adopt Entire Chapter as
amended (amended
sections listed below)
X X X
Adopt only those sections
that are listed below
Chapter / Section
A100.1 X X X
A103.1 X X X
A105.4 X X

The state agency does not adopt sections identified with the following symbol: The Office of the State Fire Marshal’s adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

APPENDIX A-2 2022 CALIFORNIA EXISTING BUILDING CODE

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

Appendix A: GUIDELINES FOR THE SEISMIC RETROFIT OF EXISTING BUILDINGS

CHAPTER A1

SEISMIC STRENGTHENING PROVISIONS FOR UNREINFORCED MASONRY BEARING WALL BUILDINGS

User note:

About this appendix: Appendix A provides guidelines for upgrading the seismic-resistance capacity of different types of existing buildings. It is organized into separate chapters that deal with buildings of different types, including unreinforced masonry buildings, reinforced concrete and reinforced masonry wall buildings, and light-frame wood buildings.

A403.10 Steel retrofit systems. Steel retrofit systems shall

have strength and stiffness sufficient to resist the seismic loads and shall conform to the requirements of this section.

A403.10.1 Special moment frames. Steel special moment frames shall comply with all applicable provisions of AISC 341, except that Section E3.4a addressing strongcolumn/weak-beams of AISC 341, is not required for columns that carry no gravity load.

A403.10.2 Inverted moment frame systems. Cantilevered column systems shall be permitted to be designed as inverted special, intermediate or ordinary moment frames, with corresponding moment frame seismic design coefficients, where the system satisfies the following conditions:

  1. The columns carry no gravity load.
  2. The columns are configured in pairs or larger groups connected by a continuous reinforced concrete foundation or grade beam.
  3. The foundation or grade beam shall be designed to resist the expected plastic moment at the base of each column, computed as RyFyZ in accordance with AISC 341.
  4. The flexibility of the foundation or grade beam, considering cracked section properties of the reinforced concrete, shall be included in computing the deformation of the steel frame system.
  5. The column height shall be taken as twice the actual height when checking lateral torsional buckling.