Skip to content

Chapter 16 — REFERENCED STANDARDS

Section A206

California Existing Building Code (Title 24, Part 10) · 2022 edition · updated 2026-09-10 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

ANALYSIS AND DESIGN

[BS] A206.1 Reinforced concrete and reinforced masonry wall anchorage. Concrete and masonry walls shall be anchored to all floors and roofs that provide lateral support for the wall in accordance with Section 12.11.2 of ASCE 7. The anchorage shall provide a direct connection capable of resisting 75 percent of the forces specified in Section 12.11.2.1 of ASCE 7.

Exceptions:

  1. Existing walls need not be evaluated or retrofitted for bending between anchors.

  2. Work required by this chapter need not consider shrinkage, thermal changes or differential settlement.

A206.1.1 Seismicity parameters, site class and geologic hazards. For any site designated as Site Class E, the value of Fa shall be taken as 1.2. Site-specific procedures are not required for compliance with this chapter. Mitigation of existing geologic site hazards such as liquefiable soil, fault rupture or landslide is not required for compliance with this chapter.

[BS] A206.2 Additional requirements for wall anchorage systems. The wall anchorage system shall comply with the requirements of this section and Section 12.11.2.2 of ASCE 7.

The maximum spacing between wall anchors shall be 8 feet (2438 mm), and each wall segment shall have at least two wall anchors.

The wall anchorage system, excluding subdiaphragms and existing roof or floor framing members, shall be designed and installed to limit the relative movement between the wall and the diaphragm to no more than 1 /8 inch before engagement of the anchors. Wall anchors shall be provided to resist out-ofplane forces, independent of existing shear anchors.

Where new members are added as crossties, they shall be spaced no more than 24 feet (7315 mm) apart. Where existing girders are used as crossties, their actual spacing shall be deemed adequate even where the spacing exceeds 24 feet (7315 mm), as long as the girders are provided with continuity connectors as required.

Wall anchorage shall not be provided by fastening the edge of plywood sheathing to steel ledgers. Wall anchorage shall not be provided solely by fastening the edge of steel decking to steel ledgers unless analysis demonstrates acceptable capacity. The existing connections shall be subject to field verification and the new connections shall be subject to special inspection.

New wall anchors shall be provided to resist the full wall anchorage design force independent of existing shear or tension anchors.

Exception: Existing cast-in-place anchors shall be permitted as part of the wall anchorage system if the tie element can be readily attached to the anchors, and if the anchors are capable of resisting the total vertical and lateral shear load (including dead load) while being acted on by the maximum wall anchorage tension force caused by an earthquake. Acceptable tension values for the existing anchors shall be established by testing in accordance with Section A205.4.

the wall anchorage system if the tie element can be readily attached to the anchors, and if the anchors are capable of resisting the total vertical and lateral shear load (including dead load) while being acted on by the maximum wall anchorage tension force caused by an earthquake. Acceptable tension values for the existing anchors shall be established by testing in accordance with Section A205.4.

[BS] A206.3 Development of anchor forces into the diaphragm. Development of the required anchorage forces into roof and floor diaphragms shall comply with the requirements of this section and Section 12.11.2.2 of ASCE 7.

Lengths of development of anchor loads in wood diaphragms shall be based on existing field nailing of the sheathing unless existing edge nailing is positively identified on the original construction plans or at the site.

[BS] A206.4 Anchorage at pilasters. Where pilasters are present, the wall anchorage system shall comply with the

APPENDIX A-20 2022 CALIFORNIA EXISTING BUILDING CODE

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

APPENDIX A—GUIDELINES FOR THE SEISMIC RETROFIT OF EXISTING BUILDINGS

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — California Existing Building Code (Title 24, Part 10)

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.