ANALYSIS AND DESIGN PROCEDURE
[BS] A109.1 General. The elements of buildings hereby required to be analyzed are specified in Table A102.1.
[BS] A109.2 Selection of procedure. Buildings with rigid diaphragms shall be analyzed by the general procedure of Section A110. Buildings with flexible diaphragms shall be analyzed by the general procedure or, where applicable, are permitted to be analyzed by the special procedure of Section A111.
vmL
= ----------------------------------1.5
fsp + P ------ D An
[BS] A108.3 Masonry compression. Where any increase in wall dead plus live load compression stress occurs, the maximum compression stress in unreinforced masonry, QG/An, shall not exceed 300 pounds per square inch (2070 kPa).
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
APPENDIX A—GUIDELINES FOR THE SEISMIC RETROFIT OF EXISTING BUILDINGS
[BS] TABLE A108.1(2) STRENGTH VALUES OF NEW MATERIALS USED IN CONJUNCTION WITH EXISTING CONSTRUCTION
| NEW MATERIALS OR CONFIGURATION OF MATERIALS | STRENGTH VALUES | |
|---|---|---|
| Horizontal diaphragms | Plywood sheathing applied directly over existing straight sheathing with ends of plywood sheets bearing on joists or rafters and edges of plywood located on center of individual sheathing boards. |
675 lbs. per ft. |
| Crosswalls | Plywood sheathing applied directly over wood studs; no value should be given to plywood applied over existing plas- ter or wood sheathing. |
1.2 times the value specified in the current building code. |
| Crosswalls | Drywall or plaster applied directly over wood studs. | The value specified in the current building code. |
| Crosswalls | Drywall or plaster applied to sheathing over existing wood studs. |
50 percent of the value specified in the current building code. |
| Tension anchorsf | Anchors extending entirely through unreinforced masonry wall secured with bearing plates on far side of a wall 30 square inches of area.b, c |
5,400 lbs. per anchor for three-wythe minimum walls. 2,700 lbs. for two-wythe walls. |
| Shear boltse, f | Anchors embedded not less than 8 inches into unreinforced masonry walls; anchors should be centered in 21/2-inch- diameter holes with dry-pack or nonshrink grout around the circumference of the anchor. |
The value for plain masonry specified for solid masonry TMS 402; and no value larger than those given for3/4-inch bolts should be used. |
| Combined tension and shear anchorsf |
Through-anchors—anchors meeting the requirements for shear and for tension anchors.b, c |
Tension—same as for tension anchors. Shear—same as for shear anchors. |
| Combined tension and shear anchorsf |
Embedded anchors—anchors extending to the exterior face of the wall with a 21/2-inch round plate under the head and drilled at an angle of 221/2 degrees to the horizontal; installed as specified for shear anchors.a, b, c |
Tension—3,600 lbs. per anchor. Shear—same as for shear anchors. |
| Infilled walls | Reinforced masonry infilled openings in existing unrein- forced masonry walls; provide keys or dowels to match rein- forcing. |
Same as values specified for unreinforced masonry walls. |
| Reinforced masonryd | Masonry piers and walls reinforced per the current building code. |
The value specified in the current building code for strength design. |
| Reinforced concreted | Concrete footings, walls and piers reinforced as specified in the current building code. |
The value specified in the current building code for strength design. |
For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2, 1 pound = 4.4 N, 1 degree = 0.017 rad, 1 pound per foot = 14.43 N/m, 1 foot = 304.8 mm. a. Embedded anchors to be tested as specified in Section A107.4. b. Anchors shall be 1 /2 inch minimum in diameter. c. Drilling for anchors shall be done with an electric rotary drill; impact tools should not be used for drilling holes or tightening anchors and shear bolt nuts. d. Load factors or capacity reduction factors shall not be used. e. Other bolt sizes, values and installation methods may be used, provided that a testing program is conducted in accordance with Section A107.5.3. The strength
value shall be determined by multiplying the calculated allowable value, determined in accordance with Section A107.5.3, by 3.0, and the usable value shall be limited to not greater than 1.5 times the value given in the table. Bolt spacing shall not exceed 6 feet on center and shall be not less than 12 inches on center. f. An alternative adhesive anchor bolt system is permitted to be used providing: its properties and installation conform to an ICC Evaluation Service Report; and
the report states that the system’s use is in unreinforced masonry as an acceptable alternative to Sections A107.4 and A113.1 or TMS 402, Section 2.1.4. The report’s allowable values shall be multiplied by a factor of three to obtain strength values and the strength reduction factor, Φ, shall be taken equal to 1.0.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Existing Building Code (Title 24, Part 10)
- Chapter 2 — DEFINITIONS
- Appendix A — GUIDELINES FOR
- Appendix B — SUPPLEMENTARY
- Appendix C — GUIDELINES FOR THE WIND
- Appendix D — BOARD OF
- Chapter 1 — SCOPE AND ADMINISTRATION
- Chapter 3 — PROVISIONS FOR ALL COMPLIANCE METHODS
- Chapter 4 — REPAIRS
- Chapter 5 — PRESCRIPTIVE COMPLIANCE METHOD
- Chapter 6 — CLASSIFICATION OF WORK
- Chapter 7 — ALTERATIONS—LEVEL 1
- Chapter 8 — ALTERATIONS—LEVEL 2
- Chapter 9 — ALTERATIONS—LEVEL 3
- Chapter 10 — CHANGE OF OCCUPANCY
- Chapter 11 — ADDITIONS
- Chapter 12 — HISTORIC BUILDINGS
- Chapter 13 — PERFORMANCE COMPLIANCE METHODS
- Chapter 14 — RELOCATED OR MOVED BUILDINGS
- Chapter 15 — CONSTRUCTION SAFEGUARDS
▸Chapter 16 — REFERENCED STANDARDS
Overview- Section A100
- Section A101
- Section A102
- Section A103
- Section A104
- Section A105
- Section A106
- Section A107
- Section A108
- Section A109
- Section A110
- Section A111
- Section A112
- Section A113
- Section A114
- Section A201
- Section A202
- Section A203
- Section A204
- Section A205
- Section A206
- Section A207
- Section A301
- Section A302
- Section A303
- Section A304
- Section A401
- Section A403
- Section A402
- Section A404
- Section A405
- Section A406
- Section A407
- Section A501
- Section B101
- Section B102
- Section B103
- Section B104
- Section C101
- Section C102
- Section C103
- Section C104
- Section C201
- Section C202
- Section C301
- Section D101