Chapter 3 — PROVISIONS FOR ALL COMPLIANCE METHODS

Section 304

California Existing Building Code (Title 24, Part 10) · 2022 edition · updated 2026-09-10 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

STRUCTURAL DESIGN LOADS AND EVALUATION AND DESIGN PROCEDURES

[BS] 304.1 Live loads. Where an addition or alteration does not result in increased design live load, existing gravity loadcarrying structural elements shall be permitted to be evaluated and designed for live loads approved prior to the addition or alteration. If the approved live load is less than that required by Section 1607 of the California Building Code, the area designated for the nonconforming live load shall be posted with placards of approved design indicating the approved live load. Where the addition or alteration results in increased design live load, the live load required by Section 1607 of the California Building Code shall be used.

[BS] 304.2 Snow loads on adjacent buildings. Where an alteration or addition changes the potential snow drift effects on an adjacent building, the code official is authorized to enforce Section 7.12 of ASCE 7.

[BS] 304.3 Seismic evaluation and design procedures. Where required, seismic evaluation or design shall be based on the procedures and criteria in this section, regardless of which compliance method is used.

[BS] 304.3.1 Compliance with full seismic forces. Where compliance requires the use of full seismic forces, the criteria shall be in accordance with one of the following:

  1. One-hundred percent of the values in the California Building Code . Where the existing seismic forceresisting system is a type that can be designated as “Ordinary,” values of R, Ω0 and Cd used for analysis in accordance with Chapter 16 of the California Building Code shall be those specified for structural systems classified as “Ordinary” in accordance with Table 12.2-1 of ASCE 7, unless it can be demonstrated that

**

any building or accessory structure, provided such building or structure complied with the building code provisions in effect at the time of original construction and the building or acces- sory structure does not become or continue to be a substandard building. For additional information, see Health and Safety Code Sections 17912, 17920.3, 17922(d), 17922.3, 17958.8 and 17958.9.

Exception: No replacement residential garage door shall be installed to connect the replacement door to an existing residential automatic garage door opener that does not have a battery backup function designed to keep the garage door operational without interruption during an electrical outage. See Health and Safety Code Section 19892.

[BS] 302.4.1 New structural members and connections. New structural members and connections shall comply with the detailing provisions of the California Building Code for new buildings of similar structure, purpose and location.

Exception: Where alternative design criteria are specifically permitted.