Section 3125B
California Building Code (Title 24, Part 2) · 2022 edition · updated 2026-09-12 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
RECIRCULATION PIPING SYSTEM
AND COMPONENTS
3125B.1 Line sizes.¶
Pipes shall be sized so flow velocity of piping systems including all pipes and fittings other than inlet devices or venturi throats shall not exceed 6 feet per second (1.829 m/s) in any suction or copper piping and 8 feet per second (2.438 m/s) in any portion of the return system.
3125B.1.1 Materials. All piping, tubing and fittings shall comply with the applicable standards for potable water system materials set forth in Chapter 6 of the California Plumbing Code.
3125B.2 Gauges.¶
A pressure and vacuum gauge shall be pro- vided for each pump system. Each gauge shall have a scale range approximately 1 1 /4 times the maximum anticipated working pressure or vacuum and shall be accurate within 2 percent of scale. The pressure gauge located on the filter shall be marked with the clean start up pressure reading.
3125B.3 Flow meter.¶
A flow meter shall be provided on each recirculation system accurate to within 10 percent of flow and installed according to the manufacturer’s written instructions with increments in the range of normal flow.
3125B.4 Basket strainer.¶
A basket strainer shall be provided on the suction side of the recirculation pump. A basket strainer will not be required on pumps connected to vacuum filters where the filter elements are not removed for cleaning.
3125B.5 Backwash piping.¶
Piping, including necessary valves conforming to Section 3125B.1, shall be provided for each filter vessel or element which requires periodic back- washing.
3125B.6 Valves.¶
Valves shall not be located in any deck area surrounding a pool. Valves shall be installed on all recircula- tion, backwashing and drain system lines which require shut- off isolation, adjustment or control of the rate of flow. Each valve shall be installed in the equipment area and labeled as to its purpose.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Building Code (Title 24, Part 2)
- Chapter 2 — DEFINITIONS AND ABBREVIATIONS
- Appendix G — FLOOD-RESISTANT
- Appendix L — EARTHQUAKE RECORDING
- Appendix M — TSUNAMI-GENERATED
- Appendix N — REPLICABLE
- Appendix O — PERFORMANCE-BASED
- Chapter 1 — SCOPE AND ADMINISTRATION
- Chapter 3 — OCCUPANCY CLASSIFICATION AND USE
- Chapter 4 — SPECIAL DETAILED REQUIREMENTS BASED ON OCCUPANCY A…
- Chapter 5 — GENERAL BUILDING HEIGHTS AND AREAS
- Chapter 6 — TYPES OF CONSTRUCTION
- Chapter 7 — FIRE AND SMOKE PROTECTION FEATURES
- Chapter 7A — MATERIALS AND CONSTRUCTION
- Chapter 8 — INTERIOR FINISHES
- Chapter 9 — FIRE PROTECTION AND LIFE SAFETY SYSTEMS
- Chapter 10 — MEANS OF EGRESS
- Chapter 11A — HOUSING ACCESSIBILITY
- Chapter 11B — ACCESSIBILITY TO PUBLIC BUILDINGS, PUBLIC ACCOMM…
- Chapter 12 — INTERIOR ENVIRONMENT
- Chapter 14 — EXTERIOR WALLS
- Chapter 15 — ROOF ASSEMBLIES AND ROOFTOP STRUCTURES
- Chapter 16 — STRUCTURAL DESIGN
- Chapter 16A — STRUCTURAL DESIGN
- Chapter 17 — SPECIAL INSPECTIONS AND TESTS
- Chapter 18 — SOILS AND FOUNDATIONS
- Chapter 19 — CONCRETE
- Chapter 20 — ALUMINUM
- Chapter 21 — MASONRY
- Chapter 22 — STEEL
- Chapter 23 — WOOD
- Chapter 24 — GLASS AND GLAZING
- Chapter 25 — GYPSUM BOARD, GYPSUM PANEL PRODUCTS AND PLASTER
- Chapter 26 — PLASTIC
- Chapter 27 — ELECTRICAL
- Chapter 28 — MECHANICAL SYSTEMS
- Chapter 30 — ELEVATORS AND CONVEYING SYSTEMS
- Chapter 31 — SPECIAL CONSTRUCTION
▸Chapter 31B — PUBLIC POOLS
Overview- Section 3101B
- Section 3102B
- Section 3103B
- Section 3104B
- Section 3105B
- Section 3106B
- Section 3107B
- Section 3108B
- Section 3109B
- Section 3110B
- Section 3111B
- Section 3112B
- Section 3113B
- Section 3114B
- Section 3115B
- Section 3116B
- Section 3117B
- Section 3118B
- Section 3119B
- Section 3120B
- Section 3121B
- Section 3122B
- Section 3123B
- Section 3124B
- Section 3125B
- Section 3126B
- Section 3127B
- Section 3128B
- Section 3129B
- Section 3130B
- Section 3131B
- Section 3132B
- Section 3133B
- Section 3134B
- Section 3135B
- Section 3136B
- Section 3137B
- Section 3138B
- Section 3139B
- Section 3140B
- Section 3141B
- Section 3142B
- Section 3143B
- Section 3144B
- Section 3145B
- Section 3146B
- Section 3147B
- Section 3148B
- Section 3149B
- Section 3150B
- Section 3151B
- Section 3152B
- Section 3153B
- Section 3154B
- Section 3155B
- Section 3156B
- Section 3157B
- Section 3158B
- Section 3159B
- Section 3160B
- Section 3161B
- Section 3162B
- Chapter 31C — RADIATION
- Chapter 31D — FOOD ESTABLISHMENTS
- Chapter 31F — MARINE OIL TERMINALS
- Chapter 32 — ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
- Chapter 33 — SAFEGUARDS DURING CONSTRUCTION
- Chapter 35 — REFERENCED STANDARDS
- Appendix A — EMPLOYEE QUALIFICATIONS
- Appendix B — BOARD OF APPEALS
- Appendix C — GROUP U – AGRICULTURAL BUILDINGS
- Appendix D — FIRE DISTRICTS
- Appendix F — RODENTPROOFING
- Appendix H — SIGNS
- Appendix I — PATIO COVERS
- Appendix J — GRADING
- Appendix K — GROUP R-3 AND GROUP R-3.1 OCCUPANCIES
- Appendix P — EMERGENCY HOUSING