Section 3106B
California Building Code (Title 24, Part 2) · 2022 edition · updated 2026-09-12 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
SPECIAL REQUIREMENTS FOR SPRAY GROUNDS
3106B Spray grounds. All applicable provisions of this chap- ter shall apply to a spray ground unless specifically addressed in this section.
3106B.1 All parts of the spray ground shall be designed and constructed so that there are no safety hazards.¶
constructed so that there are no safety hazards.
3106B.2 Walking surface.¶
A minimum 4-foot wide walking surface shall extend around the perimeter of the splash zone of a spray ground.
3106B.3 The recirculation system shall be in operation at all¶
times that the spray ground is open for use and shall have a minimum of four turnover cycles prior to opening for proper disinfection and filtration.
3106B.4 There shall be no standing water within the splash zone.¶
zone.
3106B.5 Nozzles that spray from the ground level shall be¶
flush with the ground with openings no greater than 1 /2 inch.
PUBLIC POOLS
Spray ground water features that extend above the ground must be clearly visible.
3106B.6 The splash zone shall be sloped so that only water¶
from the spray ground water feature flows back to the surge basin. Areas adjacent to the splash zone shall be sloped away from the spray ground to deck drains or other surface water disposal systems.
3106B.7 All foggers and misters that produce finely atomized¶
mists shall be supplied directly from a potable water source and not from the surge basin.
3106B.8 When multiple pumps are used the control systems¶
for the spray ground water feature pump and recirculation system pump shall be electrically interconnected so that when the recirculation pump is off the spray ground water feature pump also is off.
3106B.9 The spray ground shall have a surge basin or treat-¶
ment tank constructed of materials which are inert, corrosion resistant, nontoxic and watertight including materials such as concrete, fiberglass, high density polyethylene, stainless steel or other materials as approved by the enforcing agent which can withstand all anticipated loadings under full and empty conditions as determined by an engineer or architect who has experience working on public pools.
3106B.10 The total volume of the surge basin shall be at least¶
4,000 gallons or a minimum of three times the gallons per minute flow rate of all the spray ground pumps and the recir- culation pump combined, whichever is higher.
3106B.11 The turnover time shall be one-half hour or less.¶
3106B.12 The suction intake for the spray ground or water¶
feature pump in the surge basin shall be located adjacent to the recirculation return line.
3106B.13 When separate pumps are used, the suction intake¶
for the recirculation pump shall be located in the lowest por- tion of the surge basin and on the opposite side from the suc- tion intake for the spray ground pump.
3106B.14 The surge basin shall be designed to have easy¶
access for cleaning and inspection. The basin shall have at least one ladder access and shall have at least one 3-foot by 3-foot access opening. Lids shall be locked or require a tool to open.
3106B.15 The surge basin shall be equipped with an auto-¶
matic make up water fill device through an air gap or be pro- tected by an approved backflow prevention device in accordance with Chapter 6 of the California Plumbing Code.
3106B.16 Ultraviolet light disinfection shall be used to sup-¶
plement disinfection methods required in this chapter unless another treatment process is provided that has been deter- mined by a nationally recognized testing laboratory to be capable of providing at least the equivalent level of reduction of cryptosporidium as the ultraviolet light disinfection system specified in this section. The ultraviolet light disinfection unit shall comply with the applicable requirements established by the NSF/ANSI 50-2010 performance standard effective August 2010.
3106B.17 An accurately calibrated ultraviolet light intensity¶
meter that has been properly filtered to restrict its sensitivity
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
PUBLIC POOLS
to the disinfection spectrum shall be installed in the wall of the disinfection chamber at the point of greatest water depth from the light source.
3106B.18 The ultraviolet light unit shall be located on the¶
recirculation system and shall be installed to provide treated water directly to the spray features.
3106B.19 The ultraviolet light disinfection system must be¶
equipped with an automatic shutdown system that inactivates the water feature pump if the ultraviolet dosage rate drops below 40 mJ/cm 2 .
3106B.20 Artificial lighting shall be provided at all spray¶
ground pads which are used at night or which do not have adequate natural lighting so that all portions of the spray pad and deck may be seen easily. Lighting that may be exposed to the feature pool water shall be installed in accordance with the manufacturer’s specifications and the California Electri- cal Code.
3106B.21 A means of diverting runoff from the splash zone¶
shall be installed on the spray ground drainage piping before the surge basin to divert water to the storm drainage system when the spray ground is not in operation.
3106B.22 A removable and cleanable catch screen or basket¶
shall be installed on the spray ground drainage system before it enters the reservoir to prevent larger debris from collecting in the surge basin.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Building Code (Title 24, Part 2)
- Chapter 2 — DEFINITIONS AND ABBREVIATIONS
- Appendix G — FLOOD-RESISTANT
- Appendix L — EARTHQUAKE RECORDING
- Appendix M — TSUNAMI-GENERATED
- Appendix N — REPLICABLE
- Appendix O — PERFORMANCE-BASED
- Chapter 1 — SCOPE AND ADMINISTRATION
- Chapter 3 — OCCUPANCY CLASSIFICATION AND USE
- Chapter 4 — SPECIAL DETAILED REQUIREMENTS BASED ON OCCUPANCY A…
- Chapter 5 — GENERAL BUILDING HEIGHTS AND AREAS
- Chapter 6 — TYPES OF CONSTRUCTION
- Chapter 7 — FIRE AND SMOKE PROTECTION FEATURES
- Chapter 7A — MATERIALS AND CONSTRUCTION
- Chapter 8 — INTERIOR FINISHES
- Chapter 9 — FIRE PROTECTION AND LIFE SAFETY SYSTEMS
- Chapter 10 — MEANS OF EGRESS
- Chapter 11A — HOUSING ACCESSIBILITY
- Chapter 11B — ACCESSIBILITY TO PUBLIC BUILDINGS, PUBLIC ACCOMM…
- Chapter 12 — INTERIOR ENVIRONMENT
- Chapter 14 — EXTERIOR WALLS
- Chapter 15 — ROOF ASSEMBLIES AND ROOFTOP STRUCTURES
- Chapter 16 — STRUCTURAL DESIGN
- Chapter 16A — STRUCTURAL DESIGN
- Chapter 17 — SPECIAL INSPECTIONS AND TESTS
- Chapter 18 — SOILS AND FOUNDATIONS
- Chapter 19 — CONCRETE
- Chapter 20 — ALUMINUM
- Chapter 21 — MASONRY
- Chapter 22 — STEEL
- Chapter 23 — WOOD
- Chapter 24 — GLASS AND GLAZING
- Chapter 25 — GYPSUM BOARD, GYPSUM PANEL PRODUCTS AND PLASTER
- Chapter 26 — PLASTIC
- Chapter 27 — ELECTRICAL
- Chapter 28 — MECHANICAL SYSTEMS
- Chapter 30 — ELEVATORS AND CONVEYING SYSTEMS
- Chapter 31 — SPECIAL CONSTRUCTION
▸Chapter 31B — PUBLIC POOLS
Overview- Section 3101B
- Section 3102B
- Section 3103B
- Section 3104B
- Section 3105B
- Section 3106B
- Section 3107B
- Section 3108B
- Section 3109B
- Section 3110B
- Section 3111B
- Section 3112B
- Section 3113B
- Section 3114B
- Section 3115B
- Section 3116B
- Section 3117B
- Section 3118B
- Section 3119B
- Section 3120B
- Section 3121B
- Section 3122B
- Section 3123B
- Section 3124B
- Section 3125B
- Section 3126B
- Section 3127B
- Section 3128B
- Section 3129B
- Section 3130B
- Section 3131B
- Section 3132B
- Section 3133B
- Section 3134B
- Section 3135B
- Section 3136B
- Section 3137B
- Section 3138B
- Section 3139B
- Section 3140B
- Section 3141B
- Section 3142B
- Section 3143B
- Section 3144B
- Section 3145B
- Section 3146B
- Section 3147B
- Section 3148B
- Section 3149B
- Section 3150B
- Section 3151B
- Section 3152B
- Section 3153B
- Section 3154B
- Section 3155B
- Section 3156B
- Section 3157B
- Section 3158B
- Section 3159B
- Section 3160B
- Section 3161B
- Section 3162B
- Chapter 31C — RADIATION
- Chapter 31D — FOOD ESTABLISHMENTS
- Chapter 31F — MARINE OIL TERMINALS
- Chapter 32 — ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
- Chapter 33 — SAFEGUARDS DURING CONSTRUCTION
- Chapter 35 — REFERENCED STANDARDS
- Appendix A — EMPLOYEE QUALIFICATIONS
- Appendix B — BOARD OF APPEALS
- Appendix C — GROUP U – AGRICULTURAL BUILDINGS
- Appendix D — FIRE DISTRICTS
- Appendix F — RODENTPROOFING
- Appendix H — SIGNS
- Appendix I — PATIO COVERS
- Appendix J — GRADING
- Appendix K — GROUP R-3 AND GROUP R-3.1 OCCUPANCIES
- Appendix P — EMERGENCY HOUSING