13.7 Hazardous material information that includes: location of hazardous material,
Sunnyvale Municipal Code · 2026-09 edition · updated 2026-09-27 · Sunnyvale
quantity of hazardous material.
Work table and chairs.
Generator supervision devices, manual start and transfer features.
Public address system, where specifically required by other sections of this code.
Elevator fire recall switch in accordance with ASME A17.1.
Elevator emergency or standby power selector switch(es), where emergency or standby power is provided.
A master switch for unlocking elevator lobby doors permitted by Section 1010.2.12.1.
Building security system controls and related equipment.
All control panels shall be permanently identified in an approved manner as to function.
Other fire protection equipment and system controls as required by the fire code official. Fire command centers shall not be used for the housing of any boiler, heating unit, generator, combustible storage, or similar hazard.
(c) Ventilation.
California Fire Code Section 508.1.8 is hereby amended to read:
508.1.8 Ventilation. The fire command center shall be provided with an independent ventilation or air conditioning system in accordance with the California Mechanical Code and have manual shut-off capability within the fire command center. (Ord. 3018-13 § 2; Ord. 3101-16 § 1; Ord. 3148-19 § 1; Ord. 3201-22 § 1; Ord. 3247-25, 10/21/ 2025)