Section 507C — QUALITY CONTROL
507C.3 Existing Wall Anchors.
San Francisco Building Inspection Commission Codes · 2022 edition · ingested 2026-07-08 · San Francisco
507C.3 Existing Wall Anchors. Existing wall anchors utilized as all or part of the required tension anchors shall be tested in pullout according to Section 515C. The minimum number of anchors tested shall be four per floor, with two tests at walls with joists framing into the wall and two tests at walls with joists parallel to the wall, but not less than 10 percent of the total number of existing tension anchors at each level.