Section 905 — STANDPIPE SYSTEMS

San Francisco Building Inspection Commission Codes · 2022 edition · ingested 2026-07-08 · San Francisco

905.3.4 Revise this section as follows:

905.3.4 Stages. Stages greater than 1,000 square feet in area (93 m [2] ) shall be equipped with a Class III wet standpipe system with 1-1/2-inch and [ ] 3-inch (38 mm and 76.2 mm) hose connections on each side of the stage.