505.4 Indirect-Fired Water Heaters. Indirect-fired water

California Plumbing Code (Title 24, Part 5) · 2022 edition · updated 2026-09-10 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

heaters shall be in accordance with the applicable sections of the ASME Boiler and Pressure Vessel Code or shall comply with one of the other applicable standards shown in Table 501.1(1). Each water heater shall bear a label in accordance with ASME requirements, or an approved testing agency, certifying and attesting that such an appliance has been tested, inspected and meets the requirements of the applicable standards or code.

505.4.1 Single-Wall Heat Exchanger. An indirectfired water heater that incorporates a single-wall heat exchanger shall be in accordance with the following requirements: (1) The heat transfer medium shall be either potable water

or contain fluids recognized as safe by the Food and Drug Administration (FDA) as food grade. (2) Bear a label with the word “Caution,” followed by the

following statements: (a) The heat-transfer medium shall be potable water

or other nontoxic fluid recognized as safe by the FDA. (b) The maximum operating pressure of the heat

exchanger shall not exceed the maximum operating pressure of the potable water supply. (3) The word “Caution” and the statements in letters shall

84 2022 CALIFORNIA PLUMBING CODE

infiltration rate is known to be less than 0.40 ACH (air change per hour), the method in Section 506.2.2 shall be used. The total required volume shall be the sum of the required volume calculated for all appliances located within the space. Rooms communicating directly with the space in which the appliances are installed through openings not furnished with doors, and through combustion air openings sized and located in accordance with Section 506.3, are considered a part of the required volume. [NFPA 54:9.3.2]

506.2.1 Standard Method. The minimum required volume shall be 50 cubic feet per 1000 British thermal units per hour (Btu/h) (4.83 m 3 /kW). [NFPA 54:9.3.2.1] 506.2.2 Known Air Infiltration Rate Method. Where the air infiltration rate of a structure is known, the minimum required volume shall be determined as follows [NFPA 54:9.3.2.2]: (1) For appliances other than fan-assisted, calculate

WATER HEATERS

within 12 inches (305 mm) of the top of the enclosure and one permanent opening shall commence within 12 inches (305 mm) of the bottom of the enclosure (see Figure 506.3). The minimum dimension of air openings shall not be less than 3 inches (76 mm). (2) Combining spaces in different stories. The volumes of

spaces in different stories shall be considered as communicating spaces where such spaces are connected by one or more permanent openings in doors or floors having a total minimum free area of 2 square inches per 1000 Btu/h (0.004 m 2 /kW) of total input rating of all appliances. [NFPA 54:9.3.2.3]

using the following Equation 506.2.2(1). [NFPA 54:9.3.2.2(1)]

[Equation 506.2.2(1)]

[Equation 506.2.2(1)]

ACH 1000 Btu/h

21 ft3 ( I other )

ACH

Required Volume other ≥ 21 ft3 (

(2) For fan-assisted appliances, calculate using the fol lowing Equation 506.2.2(2). [NFPA 54:9.3.2.2(2)]

[Equation 506.2.2(2)]

Required Volume fanACH 1000 Btu/h

15 ft 3 ( I fan )

FIGURE 506.3 ALL COMBUSTION AIR FROM ADJACENT INDOOR SPACES

Where: Iother = All appliances other than fan-assisted input

in (Btu/h) Ifan = Fan-assisted appliance input in (Btu/h) ACH = Air change per hour (percent of volume of

space exchanged per hour, expressed as a decimal)

THROUGH INDOOR COMBUSTION AIR OPENINGS

[NFPA 54: FIGURE A.9.3.2.3(1)]

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — California Plumbing Code (Title 24, Part 5)
California Plumbing Code (Title 24, Part 5)
  1. Chapter 1 — GENERAL CODE PROVISIONS
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — GENERAL REGULATIONS
  4. Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
  5. Chapter 5 — WATER HEATERS
    Overview
    1. 501.1 Applicability. The regulations of this chapter shall
    2. 501.2 California Energy Code Water Heating System
    3. 502.1 General. It shall be unlawful for a person to install,
    4. 503.1 Inspection of Chimneys or Vents. This inspection shall b…
    5. 503.2 Final Water Heater Inspection. This inspection
    6. 504.1 Location. Water heater installations in bedrooms and
    7. 504.2 Vent. Water heaters of other than the direct-vent type
    8. 504.3 Clearance. The clearance requirements for water
    9. 504.4 Pressure-Limiting Devices. A water heater installation s…
    10. 504.5 Temperature-Limiting Devices. A water heater
    11. 504.6 Temperature, Pressure, and Vacuum Relief
    12. 505.1 Water Heaters. Water heaters deriving heat from
    13. 505.2 Safety Devices. Storage-type water heaters and hot
    14. 505.3 Oil-Fired Water Heaters. Oil-fired water heaters
    15. 506.1 General. Air for combustion, ventilation, and dilution of
    16. 506.2 Indoor Combustion Air. The required volume of
    17. 505.4 Indirect-Fired Water Heaters. Indirect-fired water
    18. 506.4 Outdoor Combustion Air. Outdoor combustion air
    19. 506.3 Indoor Opening Size and Location. Openings
    20. 506.5 Combination Indoor and Outdoor Combustion
    21. 506.6 Engineered Installations. Engineered combustion
    22. 506.7 Mechanical Combustion Air Supply. Where all
    23. 506.8 Louvers, Grilles, and Screens. The required size
    24. 506.9 Combustion Air Ducts. Combustion air ducts shall
    25. 507.1 Dielectric Insulator. The Authority Having Jurisdiction …
    26. 507.2 Seismic Provisions. Water heaters shall be anchored
    27. 507.3 Appliance Support. Appliances and equipment shall
    28. 507.4 Ground Support. A water heater supported from the
    29. 507.5 Drainage Pan. Where a water heater is located in an
    30. 507.6 Added or Converted Equipment or Appliances.
    31. 507.7 Types of Gases. The appliance shall be connected to
    32. 507.8 Safety Shutoff Devices for Unlisted LP-Gas
    33. 507.9 Use of Air or Oxygen Under Pressure. Where air
    34. 507.10 Protection of Gas Appliances from Fumes or
    35. 507.11 Process Air. In addition to air needed for combustion i…
    36. 507.12 Flammable Vapors. Appliances shall not be
    37. 507.13 Installation in Residential Garages. Appliances
    38. 507.14 Installation in Commercial Garages. Appliances
    39. 507.15 Installation in Aircraft Hangars. Heaters in aircraft h…
    40. 507.16 Venting of Flue Gases. Appliances shall be vented
    41. 507.17 Extra Device or Attachment. No device or attachment sha…
    42. 507.18 Adequate Capacity of Piping. When additional
    43. 507.19 Avoiding Strain on Gas Piping. Appliances shall
    44. 507.20 Gas Appliance Pressure Regulators. Where the
    45. 507.21 Venting of Gas Appliance Pressure Regula-
    46. 507.22 Bleed Lines for Diaphragm-Type Valves. Bleed
    47. 507.23 Combination of Appliances and Equipment.
    48. 507.24 Installation Instructions. The installing agency
    49. 507.25 Protection of Outdoor Appliances. Appliances
    50. 507.26 Accessibility for Service. All appliances shall be
    51. 507.27 Clearance to Combustible Materials. Appliances and thei…
    52. 508.1 General. Appliances on roofs shall be designed or
    53. 508.2 Installation of Appliances on Roofs. Appliances
    54. 508.3 Appliances on Roofs. Appliances located on roofs or
    55. 508.4 Appliances in Attics and Under-Floor Spaces.
    56. 509.1 Listing. Type B and Type B-W gas vents shall comply
    57. 509.2 Connection to Venting Systems. Except as permitted in Se…
    58. 509.3 Minimum Safe Performance. Venting systems shall
    59. 509.4 Type of Venting System to be Used. The type of
    60. 509.5 Masonry, Metal, and Factory-Built Chimneys.
    61. 509.6 Gas Vents. The installation of gas vents shall meet
    62. 509.7 Single-Wall Metal Pipe. Single-wall metal pipe shall
    63. 509.8 Through-the-Wall Vent Termination. A mechanical draft ve…
    64. 509.9 Condensation Drain. Provision shall be made to
    65. 509.10 Vent Connectors for Category I Appliances.
    66. 509.11 Vent Connectors for Category II, Category III,
    67. 509.12 Draft Hoods and Draft Controls. Vented appliances shall…
    68. 509.13 Manually Operated Dampers. A manually operated damper s…
    69. 509.14 Automatically Operated Vent Dampers. An
    70. 509.15 Obstructions. Devices that retard the flow of vent
    71. 510.1 Single Appliance Vent Table 510.1.2(1) through
    72. 510.2 Multiple Appliance Vent Table 510.2(1) through
  6. Chapter 6 — WATER SUPPLY AND DISTRIBUTION
  7. Chapter 7 — SANITARY DRAINAGE
  8. Chapter 8 — INDIRECT WASTES
  9. Chapter 9 — VENTS
  10. Chapter 10 — TRAPS AND INTERCEPTORS
  11. Chapter 11 — STORM DRAINAGE
  12. Chapter 12 — FUEL GAS PIPING
  13. Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
  14. Chapter 14 — FIRESTOP PROTECTION
  15. Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
  16. Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
  17. Chapter 17 — REFERENCED STANDARDS
  18. Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
  19. Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
  20. Appendix C — ALTERNATE PLUMBING SYSTEMS
  21. Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
  22. Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
  23. Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
  24. Appendix G — SIZING OF VENTING SYSTEMS
  25. Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
  26. Appendix I — INSTALLATION STANDARDS
  27. Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
  28. Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
  29. Appendix L — SUSTAINABLE PRACTICES
  30. Appendix M — PEAK WATER DEMAND CALCULATOR
  31. Appendix N — IMPACT OF WATER TEMPERATURE ON THE POTENTIAL FOR …

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.