Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS

1604.3 Equipment Room Signs. Each equipment room

California Plumbing Code (Title 24, Part 5) · 2019 edition · updated 2026-09-10 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

containing nonpotable rainwater equipment shall have a sign posted with the following wording in 1 inch (25.4 mm) letters: CAUTION NONPOTABLE WATER, DO NOT DRINK. DO NOT CONNECT TO DRINKING WATER SYSTEM. NOTICE: CONTACT BUILDING MANAGEMENT BEFORE PERFORMING ANY WORK ON THIS WATER SYSTEM.

This sign shall be posted in a location that is visible to anyone working on or near rainwater water equipment.

(1) Pumps, equipment, equipment room signs, and

exposed piping in an equipment room shall be checked. 1605.3.2 Cross-Connection Test. A cross-connec- tion test shall be performed in the presence of the Authority Having Jurisdiction or other authorities having jurisdiction to determine whether a cross-connection has occurred as follows: (1) The potable water system shall be activated and

pressurized. The rainwater catchment water system

(3) Fixtures, potable, and rainwater shall be tested and

inspected for flow. Flow from a rainwater catchment water system outlet shall indicate a cross-connection. No flow from a potable water outlet shall indicate that it is connected to the rainwater water system. (4) The drain on the rainwater catchment water system

shall be checked for flow during the test and at the

(4) The drain on the rainwater catchment water system

shall be checked for flow during the test and at the end of the period. (5) The potable water system shall then be completely

drained.

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — California Plumbing Code (Title 24, Part 5)
California Plumbing Code (Title 24, Part 5)
  1. Chapter 1 — GENERAL CODE PROVISIONS
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — GENERAL REGULATIONS
  4. Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
  5. Chapter 5 — WATER HEATERS
  6. Chapter 6 — WATER SUPPLY AND DISTRIBUTION
  7. Chapter 7 — SANITARY DRAINAGE
  8. Chapter 8 — INDIRECT WASTES
  9. Chapter 9 — VENTS
  10. Chapter 10 — TRAPS AND INTERCEPTORS
  11. Chapter 11 — STORM DRAINAGE
  12. Chapter 12 — FUEL GAS PIPING
  13. Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
  14. Chapter 14 — FIRESTOP PROTECTION
  15. Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
  16. Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
    Overview
    1. 1601.2 System Design. Rainwater catchment systems shall
    2. 1601.3 Permit. It shall be unlawful for a person to construct,
    3. 1601.4 Component Identification. System components
    4. 1601.5 Maintenance and Inspection. Rainwater catchment systems…
    5. 1601.6 Operation and Maintenance Manual. An operation and main…
    6. 1601.7 Minimum Water Quality Requirements. The
    7. 1602.2 Plumbing Plan Submission. No permit for a
    8. 1602.3 System Changes. No changes or connections shall
    9. 1602.4 Connections to Potable or Reclaimed (Recy-
    10. 1602.5 Initial Cross-Connection Test. Where a portion
    11. 1602.6 Sizing. The design and size of rainwater drains, gutter…
    12. 1602.7 Rainwater Catchment System Materials. Rainwater catchme…
    13. 1602.8 Rainwater Catchment System Color and Mark-
    14. 1602.9 Design and Installation. The design and installation of…
    15. 1603.2 Construction. Rainwater storage tanks shall be
    16. 1603.7 Opening and Access Protection. Rainwater
    17. 1603.3 Location. Rainwater storage tanks shall be permitted to…
    18. 1603.4 Above Grade. Above grade, storage tanks shall be
    19. 1603.5 Below Grade. Rainwater storage tanks installed
    20. 1603.6 Drainage and Overflow. Rainwater storage tanks
    21. 1603.8 Marking. Rainwater tanks shall be permanently
    22. 1603.9 Storage Tank Venting. Where venting using
    23. 1603.10 Pumps. Pumps serving rainwater catchment systems shall…
    24. 1603.11 Roof Drains. Primary and secondary roof drains,
    25. 1603.12 Water Quality Devices and Equipment. Devices and equip…
    26. 1603.13 Freeze Protection. Tanks and piping installed in
    27. 1603.14 Debris Removal. The rainwater catchment conveyance sys…
    28. 1603.15 Required Filters. A filter permitting the passage
    29. 1603.16 Roof Gutters. Gutters shall maintain a minimum
    30. 1604.0 Signs.1604.1 General. Signs in buildings using rainwate…
    31. 1604.2 Commercial, Industrial, Institutional idential Restroom…
    32. 1604.3 Equipment Room Signs. Each equipment room
    33. 1605.2 Supply System Inspection and Test. Rainwater
    34. 1605.3 Cross-Connection Inspection and Testing. An
  17. Chapter 17 — REFERENCED STANDARDS
  18. Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
  19. Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
  20. Appendix C — ALTERNATE PLUMBING SYSTEMS
  21. Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
  22. Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
  23. Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
  24. Appendix G — SIZING OF VENTING SYSTEMS
  25. Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
  26. Appendix I — INSTALLATION STANDARD FOR PEX TUBING SYSTEMS FOR …
  27. Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
  28. Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
  29. Appendix L — SUSTAINABLE PRACTICES
  30. Appendix M — PEAK WATER DEMAND CALCULATOR

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.