Appendix I — INSTALLATION STANDARD FOR PEX TUBING SYSTEMS FOR HOT- AND COLD-WATER DISTRIBUTION

10.6 Sizing and Flow Velocities.

California Plumbing Code (Title 24, Part 5) · 2019 edition · updated 2026-09-10 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

10.6.1 PEX tubing shall be sized in accordance with IAPMO/ANSI UPC 1. Note: Potable water piping sizing is addressed in Section 610.0 and Appendix A of IAPMO/ANSI UPC 1-2012. 10.6.2 The tubing manufacturer’s pressure-loss data should be referenced when using Appendix A of IAPMO/ANSI UPC 1. In absence of such data, Figures 3 and 4 shall be used. 10.6.3 Flow velocities through the water distribution system, used for calculating flush tank and flush valve fixture units depending on the tubing sizes (see Table 1), shall not exceed (a) 3.0 m/s (10 ft/s) for cold-water distribution

systems; and (b) 2.4 m/s (8 ft/s) for hot-water distribution

systems. Note: The flow velocities in Items (a) and (b) account for the increased velocities through the fittings. 10.6.4 Hot-water recirculation systems shall (a) be balanced to maintain adequate system

temperatures; and

(a) expressly allowed in the written instructions

of the manufacturers of all plastic pipe and

(a) expressly allowed in the written instructions

of the manufacturers of all plastic pipe and fittings installed at the time the PEX piping system is being tested; and (b) compressed air or other gas testing is not

prohibited by the authority having jurisdic

compressed air or other gas testing is not

prohibited by the authority having jurisdiction.

(a) 3.0 m/s (10 ft/s) for cold-water distribution

systems; and (b) 2.4 m/s (8 ft/s) for hot-water distribution

systems.

Note: LB = C × √(D × ΔL) where LB = length of flexible arm C = material constant (12 for PEX) D = nominal outside diameter of tubing ΔL = thermal expansion length

FIGURE 1 (See Sections 6.4.1 and 7.3) EXPANSION ARMS

(a) be balanced to maintain adequate system

temperatures; and (b) have flow velocities that do not exceed 0.6

m/s (2 ft/s) (see Table 2); and

(b) have flow velocities that do not exceed 0.6

m/s (2 ft/s) (see Table 2); and (c) use only PEX tubing designated for hot,

chlorinated water recirculation systems and

(c) use only PEX tubing designated for hot,

chlorinated water recirculation systems and rated for the maximum percentage of time during which the system is intended to be operated at elevated temperatures, in accordance with ASTM F876.

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — California Plumbing Code (Title 24, Part 5)
California Plumbing Code (Title 24, Part 5)
  1. Chapter 1 — GENERAL CODE PROVISIONS
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — GENERAL REGULATIONS
  4. Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
  5. Chapter 5 — WATER HEATERS
  6. Chapter 6 — WATER SUPPLY AND DISTRIBUTION
  7. Chapter 7 — SANITARY DRAINAGE
  8. Chapter 8 — INDIRECT WASTES
  9. Chapter 9 — VENTS
  10. Chapter 10 — TRAPS AND INTERCEPTORS
  11. Chapter 11 — STORM DRAINAGE
  12. Chapter 12 — FUEL GAS PIPING
  13. Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
  14. Chapter 14 — FIRESTOP PROTECTION
  15. Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
  16. Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
  17. Chapter 17 — REFERENCED STANDARDS
  18. Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
  19. Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
  20. Appendix C — ALTERNATE PLUMBING SYSTEMS
  21. Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
  22. Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
  23. Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
  24. Appendix G — SIZING OF VENTING SYSTEMS
  25. Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
  26. Appendix I — INSTALLATION STANDARD FOR PEX TUBING SYSTEMS FOR …
  27. Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
  28. Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
  29. Appendix L — SUSTAINABLE PRACTICES
  30. Appendix M — PEAK WATER DEMAND CALCULATOR

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.