Appendix I — INSTALLATION STANDARD FOR PEX TUBING SYSTEMS FOR HOT- AND COLD-WATER DISTRIBUTION
10.6 Sizing and Flow Velocities.
California Plumbing Code (Title 24, Part 5) · 2019 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
10.6.1 PEX tubing shall be sized in accordance with IAPMO/ANSI UPC 1. Note: Potable water piping sizing is addressed in Section 610.0 and Appendix A of IAPMO/ANSI UPC 1-2012. 10.6.2 The tubing manufacturer’s pressure-loss data should be referenced when using Appendix A of IAPMO/ANSI UPC 1. In absence of such data, Figures 3 and 4 shall be used. 10.6.3 Flow velocities through the water distribution system, used for calculating flush tank and flush valve fixture units depending on the tubing sizes (see Table 1), shall not exceed (a) 3.0 m/s (10 ft/s) for cold-water distribution
systems; and (b) 2.4 m/s (8 ft/s) for hot-water distribution
systems. Note: The flow velocities in Items (a) and (b) account for the increased velocities through the fittings. 10.6.4 Hot-water recirculation systems shall (a) be balanced to maintain adequate system
temperatures; and
(a) expressly allowed in the written instructions
of the manufacturers of all plastic pipe and
(a) expressly allowed in the written instructions
of the manufacturers of all plastic pipe and fittings installed at the time the PEX piping system is being tested; and (b) compressed air or other gas testing is not
prohibited by the authority having jurisdic
compressed air or other gas testing is not
prohibited by the authority having jurisdiction.
(a) 3.0 m/s (10 ft/s) for cold-water distribution
systems; and (b) 2.4 m/s (8 ft/s) for hot-water distribution
systems.
Note: LB = C × √(D × ΔL) where LB = length of flexible arm C = material constant (12 for PEX) D = nominal outside diameter of tubing ΔL = thermal expansion length
FIGURE 1 (See Sections 6.4.1 and 7.3) EXPANSION ARMS
(a) be balanced to maintain adequate system
temperatures; and (b) have flow velocities that do not exceed 0.6
m/s (2 ft/s) (see Table 2); and
(b) have flow velocities that do not exceed 0.6
m/s (2 ft/s) (see Table 2); and (c) use only PEX tubing designated for hot,
chlorinated water recirculation systems and
(c) use only PEX tubing designated for hot,
chlorinated water recirculation systems and rated for the maximum percentage of time during which the system is intended to be operated at elevated temperatures, in accordance with ASTM F876.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Plumbing Code (Title 24, Part 5)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
- Chapter 5 — WATER HEATERS
- Chapter 6 — WATER SUPPLY AND DISTRIBUTION
- Chapter 7 — SANITARY DRAINAGE
- Chapter 8 — INDIRECT WASTES
- Chapter 9 — VENTS
- Chapter 10 — TRAPS AND INTERCEPTORS
- Chapter 11 — STORM DRAINAGE
- Chapter 12 — FUEL GAS PIPING
- Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
- Chapter 14 — FIRESTOP PROTECTION
- Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
- Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
- Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
- Appendix C — ALTERNATE PLUMBING SYSTEMS
- Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
- Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
- Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
- Appendix G — SIZING OF VENTING SYSTEMS
- Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
▸Appendix I — INSTALLATION STANDARD FOR PEX TUBING SYSTEMS FOR …
Overview- 10.1 Hot-Work Joints. Hot-work joints (e.g., soldering, brazin…
- 10.2 Bending Radius.
- 10.3 Directional Fittings. Directional fittings (e.g., 90º and…
- 10.4 Direct Burial. PEX tubing and fittings may be used in dir…
- 10.5 Fire-Resistive Construction. Manufacturer’s installation …
- 10.6 Sizing and Flow Velocities.
- 10.7 Installation Testing. Installation of PEX water distribut…
- Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
- Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
- Appendix L — SUSTAINABLE PRACTICES
- Appendix M — PEAK WATER DEMAND CALCULATOR