Appendix I — INSTALLATION STANDARD FOR PEX TUBING SYSTEMS FOR HOT- AND COLD-WATER DISTRIBUTION
10.2 Bending Radius.
California Plumbing Code (Title 24, Part 5) · 2019 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
10.2.1 The free (unsupported) bending radius for PEX tubing, measured at the outside of the bend, shall be not less than six times the actual outside diameter of the tubing, unless otherwise specified by the PEX manufacturer. Supports should be used to facilitate rigid bends and to alleviate stress on PEX joints when bends are needed in close proximity to such joints. 10.2.2 Tighter bends may be used when the PEX tubing is uniformly bent (supported) around a curved bracket or other rigid fixture. In this case, the minimum outside radius of the supported bend shall be as specified by the PEX manufacturer.
(ii) have a maximum cantilever, measured
from the support to the end of the CTS support channel, of 0.5 m (1.5 ft). 7.3 Anchors. Anchors shall be (a) used to restrict PEX tubing movement; (b) made of materials that provide rigidity to
the support system and utilize pipe clamps
(b) made of materials that provide rigidity to
the support system and utilize pipe clamps designed for plastic tubing capable of restraining the tubing; and (c) installed in accordance with Figures 1 or 2,
as applicable (i.e., anchor distances and
(c) installed in accordance with Figures 1 or 2,
as applicable (i.e., anchor distances and size of arms and offsets). Note: Anchors are typically installed every 20 m (65 ft). See Section 6.
442 2019 CALIFORNIA PLUMBING CODE
APPENDIX I
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Plumbing Code (Title 24, Part 5)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
- Chapter 5 — WATER HEATERS
- Chapter 6 — WATER SUPPLY AND DISTRIBUTION
- Chapter 7 — SANITARY DRAINAGE
- Chapter 8 — INDIRECT WASTES
- Chapter 9 — VENTS
- Chapter 10 — TRAPS AND INTERCEPTORS
- Chapter 11 — STORM DRAINAGE
- Chapter 12 — FUEL GAS PIPING
- Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
- Chapter 14 — FIRESTOP PROTECTION
- Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
- Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
- Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
- Appendix C — ALTERNATE PLUMBING SYSTEMS
- Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
- Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
- Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
- Appendix G — SIZING OF VENTING SYSTEMS
- Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
▸Appendix I — INSTALLATION STANDARD FOR PEX TUBING SYSTEMS FOR …
Overview- 10.1 Hot-Work Joints. Hot-work joints (e.g., soldering, brazin…
- 10.2 Bending Radius.
- 10.3 Directional Fittings. Directional fittings (e.g., 90º and…
- 10.4 Direct Burial. PEX tubing and fittings may be used in dir…
- 10.5 Fire-Resistive Construction. Manufacturer’s installation …
- 10.6 Sizing and Flow Velocities.
- 10.7 Installation Testing. Installation of PEX water distribut…
- Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
- Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
- Appendix L — SUSTAINABLE PRACTICES
- Appendix M — PEAK WATER DEMAND CALCULATOR