903.1 Applicable Standards — 2025 California Plumbing Code
California Plumbing Code (Title 24, Part 5) · 2025 edition · updated 2026-09-25 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
Cite as: 2025 California Plumbing Code (Title 24, Part 5) § 903.1 · Effective January 1, 2026 · Official source: Building Standards Commission
Vent pipe and fittings shall comply with the applicable standards referenced in Table 701.2, except that:
(1) No galvanized steel or 304 stainless steel pipe shall be installed underground and shall be not less than 6 inches (152 mm) aboveground.
(2) ABS and PVC DWV piping installations shall be in accordance with the firestop protection requirements in the California Building Code . Except for individual single-family dwelling units, materials exposed within ducts or plenums shall have a flame-spread index of not more than 25 and a smoke-developed index of not more than 50 where tested in accordance with ASTM E84 or UL 723. Plastic piping installed in plenums shall be tested in accordance with all requirements of ASTM E84 or UL 723. Mounting methods, supports and sample sizes of materials for testing that are not specified in ASTM E84 or UL 723 shall be prohibited.
903.1.1 [HCD 1 & HCD 2] ABS or PVC installations are limited to not more than two stories of areas of resi- dential accommodation.
903.1.2 [HCD 1] All malleable iron vents shall be gal- vanized.
903.1.3 [OSHPD 1, 2, 3, 4 & 5] ABS and PVC instal- lations are not allowed.