Chapter 6 — WATER SUPPLY AND DISTRIBUTION
603.5 Specific Requirements. Specific requirements for
California Plumbing Code (Title 24, Part 5) · 2025 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
backflow prevention shall comply with Section 603.5.1 through Section 603.5.22. 603.5.1 Atmospheric Vacuum Breaker. Water closet and urinal flushometer valves shall be protected against backflow by an approved backflow prevention assembly, device, or method. Where the valves are equipped with an atmospheric vacuum breaker, the vacuum breaker shall be installed on the discharge side of the flushometer valve with the critical level not less than 6 inches (152 mm), or the distance according to its listing, above the overflow rim of a water closet bowl or the highest part of a urinal.
603.5.2 Ballcock. Water closet and urinal tanks shall be equipped with a ballcock. The ballcock shall be installed with the critical level not less than 1 inch (25.4 mm) above the full opening of the overflow pipe. In cases where the ballcock has no hush tube, the bottom of the water supply inlet shall be installed 1 inch (25.4 mm) above the full opening of the overflow pipe.
603.5.3 Backflow Prevention. Water closet flushometer tanks shall be protected against backflow by an approved backflow prevention assembly, device, or method.
603.5.4 Heat Exchangers. Heat exchangers used for heat transfer, heat recovery, or solar heating shall protect the potable water system from being contaminated by the
heat-transfer medium. Single-wall heat exchangers used in indirect-fired water heaters shall meet the requirements of Section 505.4.1. Double-wall heat exchangers shall separate the potable water from the heat-transfer medium by providing a space between the two walls that are vented to the atmosphere. 603.5.5 Water Supply Inlets. Water supply inlets to tanks, vats, sumps, swimming pools, and other receptors shall be protected by one of the following means:
(1) An approved air gap.
(2) A listed vacuum breaker installed on the discharge side of the last valve with the critical level not less than 6 inches (152 mm) or in accordance with its listing.
(3) A backflow preventer suitable for the degree of hazard, installed in accordance with the requirements for that type of device or assembly as set forth in this chapter. 603.5.6 Protection from Lawn Sprinklers and Irri- gation Systems. Potable water supplies to systems having no pumps or connections for pumping equipment, and no chemical injection or provisions for chemical injection, shall be protected from backflow by one of the following devices:
(1) Atmospheric vacuum breaker (AVB)
(2) Pressure vacuum breaker backflow prevention assembly (PVB)
(3) Spill-resistant pressure vacuum breaker (SVB)
(4) Reduced-pressure principle backflow prevention assembly (RP)
(5) A valve complying with IAPMO PS 72 603.5.6.1 Systems with Pumps. Where sprinkler and irrigation systems have pumps, connections for pumping equipment, or auxiliary air tanks, or are otherwise capable of creating backpressure, the potable water supply shall be protected by the following type of device where the backflow device is located upstream from the source of backpressure:
(1) Reduced-pressure principle backflow prevention assembly (RP) 603.5.6.2 Systems with Backflow Devices. Where systems have a backflow device installed downstream from a potable water supply pump or a potable water supply pump connection, the device shall be one of the following:
(1) Atmospheric vacuum breaker (AVB)
(2) Pressure vacuum breaker backflow prevention assembly (PVB)
(3) Spill-resistant pressure vacuum breaker (SVB)
(4) Reduced-pressure principle backflow prevention assembly (RP) 603.5.6.3 Systems with Chemical Injectors. Where systems include a chemical injector or provisions for chemical injection, the potable water supply shall be protected by a reduced-pressure principle backflow prevention assembly (RP).
WATER SUPPLY AND DISTRIBUTION
| TABLE 603.2 BACKFLOW PREVENTION DEVICES, ASSEMBLIES, AND METHODS | ||||||
|---|---|---|---|---|---|---|
| DEGREE OF HAZARD | DEGREE OF HAZARD | DEGREE OF HAZARD | DEGREE OF HAZARD | DEGREE OF HAZARD | DEGREE OF HAZARD | DEGREE OF HAZARD |
| DEVICE, ASSEMBLY, OR METHOD1 |
APPLICABLE STANDARDS |
POLLUTION (LOW HAZARD) |
POLLUTION (LOW HAZARD) |
CONTAMINATION (HIGH HAZARD) |
CONTAMINATION (HIGH HAZARD) |
INSTALLATION2,3 |
| DEVICE, ASSEMBLY, OR METHOD1 |
APPLICABLE STANDARDS |
BACK- SIPHONAGE |
BACK- PRESSURE |
BACK- SIPHONAGE |
BACK- PRESSURE |
BACK- PRESSURE |
| Air gap | ASME A112.1.2 |
X | –– | X | –– | See Table 603.3.1 in this chapter. |
| Air gap fittings for use with plumbing fixtures, appliances, and appurte- nances |
ASME A112.1.3 |
X | –– | X | –– | Air gap fitting is a device with an internal air gap, and typical installation includes plumbing fixtures, appliances, and appurtenances. The critical level shall not be installed below the flood level rim. |
| Antisiphon fill valve (ballcocks) for gravity water closet flush tanks and urinal tanks |
ASSE 1002/ ASME A112.1002/ CSA B125.12 |
X | –– | X | –– | Installation of gravity water closet flush tank and urinal tanks with the fill valve installed with the critical level not less than 1 inch above the opening of the overflow pipe.4,5 |
| Atmospheric vacuum breaker (consists of a body, checking member and atmospheric port) |
ASSE 1001 or CSA B64.1.1 |
X | –– | X | –– | Upright position. Have outlet open to atmosphere. Minimum of 6 inches or listed distance above all downstream piping and flood level rim of receptor.4,5 |
| Backflow preventer for Carbonated Beverage Dispensers (two inde- pendent check valves with a vent to the atmos- phere) |
ASSE 1022 | X | X | X | X | Installation includes carbonated beverage machines or dispensers. These devices operate under intermittent or continuous pressure conditions. |
| Backflow preventer with intermediate atmos- pheric vent |
ASSE 1012 | X | X | — | — | Installation of potable water connections to water boilers. No high-hazard chemicals shall be introduced into the system using such devices. Designed to operate under con- tinuous pressure conditions. May discharge water. |
| Backflow preventer with intermediate atmospheric vent and pressure reduc- ing valve |
ASSE 1081 | X | X | — | — | Installation of potable water connections to water boilers. No high-hazard chemicals shall be introduced into the system using such devices. Designed to operate under con- tinuous pressure conditions. May discharge water. |
| Chemical dispenser with integral backflow protec- tion |
ANSI/CAN/ ASSE/IAPMO 1055 |
X | –– | X | –– | Shall be installed in accordance with manufacturer’s installation instructions with dedicated water supply whenever possible. |
| Dual check backflow preventer |
ASSE 1024 | X | X | — | — | Installation does not include carbonated drink dispensers. |
| Dual check backflow preventer wall hydrants, freeze resistant |
ASSE 1053 | X | –– | X | –– | Such devices are not for use under continuous pressure conditions.4 |
| Double Check Detector Fire Protection Backflow Prevention Assembly (two independent check valves with a parallel detector assembly con- sisting of a water meter and a double check valve backflow prevention assembly and means for field testing) |
ASSE 1048 | X | X | –– | –– | Horizontal unless otherwise listed. Access and clearance shall be in accordance with the manufacturer’s instructions, and not less than a 12 inch clearance at the bottom for mainte- nance. May need platform/ladder for test and repair. Does not discharge water. Installation includes a fire protection system and is designed to operate under continuous pres- sure conditions. |
142 2025 CALIFORNIA PLUMBING CODE
WATER SUPPLY AND DISTRIBUTION
| TABLE 603.2 BACKFLOW PREVENTION DEVICES, ASSEMBLIES, AND METHODS (continued) | ||||||
|---|---|---|---|---|---|---|
| DEGREE OF HAZARD | DEGREE OF HAZARD | DEGREE OF HAZARD | DEGREE OF HAZARD | DEGREE OF HAZARD | DEGREE OF HAZARD | DEGREE OF HAZARD |
| DEVICE, ASSEMBLY, OR METHOD1 |
APPLICABLE STANDARDS |
POLLUTION (LOW HAZARD) |
POLLUTION (LOW HAZARD) |
CONTAMINATION (HIGH HAZARD) |
CONTAMINATION (HIGH HAZARD) |
INSTALLATION2,3 |
| DEVICE, ASSEMBLY, OR METHOD1 |
APPLICABLE STANDARDS |
BACK- SIPHONAGE |
BACK- PRESSURE |
BACK- SIPHONAGE |
BACK- PRESSURE |
BACK- PRESSURE |
| Double Check Valve Backflow Prevention Assembly (two inde- pendent check valves and means of field test- ing) |
ASSE 1015; AWWA C510; CSA B64.5 or CSA B64.5.1 |
X | X | –– | –– | Horizontal unless otherwise listed. Access and clearance shall be in accordance with the man- ufacturer’s instructions, and not less than a 12 inch clearance at the bottom for maintenance. May need platform/ladder for test and repair. Does not discharge water. |
| Freeze resistant sanitary yard hydrants |
ASSE 1057 | X | –– | X | –– | Such devices are not for use under continuous pressure conditions.4 |
| Hose connection back- flow preventers |
ASSE 1052 | X | –– | X | –– | Such devices are not for use under continuous pressure conditions.4,6 |
| Hose connection vac- uum breakers |
ASSE 1011 | X | –– | X | –– | Such devices are not for use under continuous pressure conditions. No valve downstream.4,6 |
| Laboratory faucet back- flow preventer |
ASSE 1035 | X | –– | X | –– | Installation includes laboratory faucets. Such devices are not for use under continuous pressure conditions. No valve downstream.4 |
| Pressure Vacuum Breaker Backflow Prevention Assembly (loaded air inlet valve, internally loaded check valve and means for field testing) |
ASSE 1020 or CSA B64.1.2 |
X | –– | X | –– | Upright position. May have valves down- stream. Minimum of 12 inches above all downstream piping and flood-level rim of the receptor. May discharge water. |
| Reduced Pressure Detec- tor Fire Protection Back- flow Prevention Assembly (two independ- ently acting loaded check valves, a differential pres- sure relief valve, with a parallel detector assembly consisting of a water meter and a reduced-pres- sure principle backflow prevention assembly, and means for field testing) |
ASSE 1047 | X | X | X | X | Horizontal unless otherwise listed. Access and clearance shall be in accordance with the manufacturer’s instructions, and not less than a 12 inch clearance at the bottom for mainte- nance. May need platform/ladder for test and repair. May discharge water. Installation includes a fire protection system and is designed to operate under continuous pressure conditions. |
| Reduced Pressure Princi- ple Backflow Prevention Assembly (two independ- ently acting loaded check valves, a differential pres- sure relief valve and means for field testing) |
ASSE 1013; AWWA C511; CSA B64.4 or CSA B64.4.1 |
X | X | X | X | Horizontal unless otherwise listed. Access and clearance shall be in accordance with the manufacturer’s instructions, and not less than a 12 inch clearance at the bottom for mainte- nance. May need platform/ladder for test and repair. May discharge water. |
| Spill-Resistant Pressure Vacuum Breaker (single check valve with air inlet vent and means of field testing) |
ASSE 1056 | X | –– | X | –– | Upright position. Minimum of 12 inches or listed distance above all downstream piping and flood-level rim of receptor.5 |
| Vacuum breaker wall hydrants, hose bibbs, freeze resistant, auto- matic draining type |
ASSE 1019 or CSA B64.2.1.1 |
X | –– | X | –– | Installation includes wall hydrants and hose bibbs. Such devices are not for use under con- tinuous pressure conditions (means of shutoff downstream of device is prohibited).4,5 |
For SI units: 1 inch = 25.4 mm
Notes: 1 See the description of devices and assemblies in this chapter. 2 Installation in pit or vault requires previous approval by the Authority Having Jurisdiction. 3 Refer to the general and specific requirement for installation. 4 Not to be subjected to operating pressure for more than 12 hours in a 24-hour period. 5 For deck-mounted and equipment-mounted vacuum breaker, see Section 603.5.13. 6 Shall be installed in accordance with Section 603.5.7.
WATER SUPPLY AND DISTRIBUTION
TABLE 603.3.1 MINIMUM AIR GAPS FOR WATER DISTRIBUTION [4]
| FIXTURES | WHERE NOT AFFECTED BY SIDEWALLS1 (inches) |
WHERE AFFECTED BY SIDEWALLS2 (inches) |
|---|---|---|
| Effective openings3 not greater than1⁄2 of an inch in diameter | 1 | 11⁄2 |
| Effective openings3 not greater than3⁄4 of an inch in diameter | 11⁄2 | 21⁄4 |
| Effective openings3 not greater than 1 inch in diameter | 2 | 3 |
| Effective openings3 greater than 1 inch in diameter | Two times the diameter of effective opening |
Three times the diameter of effective opening |
For SI units: 1 inch = 25.4 mm
Notes: 1 Sidewalls, ribs, or similar obstructions do not affect air gaps where spaced from the inside edge of the spout opening a distance exceeding three times the diameter of the effective opening for a single wall, or a distance exceeding four times the effective opening for two intersecting walls. 2 Vertical walls, ribs, or similar obstructions extending from the water surface to or above the horizontal plane of the spout opening other than specified in Footnote 1 above. The effect of three or more such vertical walls or ribs has not been determined. In such cases, the air gap shall be measured from the top of the wall. 3 The effective opening shall be the minimum cross-sectional area at the seat of the control valve or the supply pipe or tubing that feeds the device or outlet. Where two or more lines supply one outlet, the effective opening shall be the sum of the cross-sectional areas of the individual supply lines or the area of the single outlet, whichever is smaller. 4 Air gaps less than 1 inch (25.4 mm) shall be approved as a permanent part of a listed assembly that has been tested under actual backflow conditions with vacuums of 0 to 25 inches of mercury (85 kPa).
Where two or more lines supply one outlet, the effective opening shall be the sum of the cross-sectional areas of the individual supply lines or the area of the single outlet, whichever is smaller. 4 Air gaps less than 1 inch (25.4 mm) shall be approved as a permanent part of a listed assembly that has been tested under actual backflow conditions with vacuums of 0 to 25 inches of mercury (85 kPa).
603.5.7 Outlets with Hose Attachments. Potable water outlets with hose attachments, other than water heater drains, boiler drains, and clothes washer connections, shall be protected by a nonremovable hose bibbtype backflow preventer, a nonremovable hose bibb-type vacuum breaker, or by an atmospheric vacuum breaker installed not less than 6 inches (152 mm) above the highest point of usage located on the discharge side of the last valve. In climates where freezing temperatures occur, a listed self-draining frost-proof hose bibb with an integral backflow preventer or vacuum breaker shall be used. 603.5.8 Water-Cooled Equipment. Water-cooled compressors, degreasers, or other water-cooled equipment shall be protected by a backflow preventer installed in accordance with the requirements of this chapter. Water-cooled equipment that produces backpressure shall be equipped with the appropriate protection. 603.5.9 Aspirators. Water inlets to water-supplied aspirators shall be equipped with a vacuum breaker installed in accordance with its listing requirements and this chapter. The discharge shall drain through an air gap. Where the tailpiece of a fixture to receive the discharge of an aspirator is used, the air gap shall be located above the flood-level rim of the fixture.
603.5.10 Steam or Hot Water Boilers. Potable water connections to steam or hot water boilers shall be protected from backflow by a double check valve backflow prevention assembly, backflow preventer with intermediate atmospheric vent and pressure reducing valve, or reduced pressure principle backflow prevention assembly in accordance with Table 603.2. Where chemicals are introduced into the system a reduced pressure principle backflow prevention assembly shall be provided in accordance with Table 603.2.
603.5.11 Nonpotable Water Piping. In cases where it is impractical to correct individual cross-connections on the domestic waterline, the line supplying such outlets
shall be considered a nonpotable water line. No drinking or domestic water outlets shall be connected to the nonpotable waterline. Where possible, portions of the nonpotable waterline shall be exposed, and exposed portions shall be properly identified in a manner satisfactory to the Authority Having Jurisdiction. Each outlet on the nonpotable waterline that is permitted to be used for drinking or domestic purposes shall be posted: “CAUTION: NONPOTABLE WATER, DO NOT DRINK.”
[HCD 1 & HCD 2] An international symbol of a glass in a circle with a slash through it shall be provided sim- ilar to that shown in Figure 601.
603.5.12 Beverage Dispensers. Potable water supply to carbonated beverage dispensers shall be protected by an air gap or a vented backflow preventer that complies with ASSE 1022. For carbonated beverage dispensers, piping material installed downstream of the backflow preventer shall not be affected by carbon dioxide gas. Non-carbonated beverage dispensers, such as ice makers and coffee machines, shall be protected by an air gap or dual check backflow preventer that comply with ASSE 1032 or ASSE 1024.
603.5.13 Deck-Mounted and Equipment- Mounted Vacuum Breakers. Deck-mounted or equipment-mounted vacuum breakers shall be installed in accordance with their listing and the manufacturer’s installation instructions, with the critical level not less than 1 inch (25.4 mm) above the flood-level rim.
603.5.14 Protection from Fire Systems.
Note: Fire Protection Systems has not been adopted by the State Fire Marshal. This section cannot be adopted or enforced pursuant to California Health and Safety Code 13114.7(a), which is being cited for reference. California Health and Safety Code 13114.7.
(a) For the purposes of this section the following are definitions of class I and class II systems:
144 2025 CALIFORNIA PLUMBING CODE
WATER SUPPLY AND DISTRIBUTION
(1) American Water Works Association [A.W.W.A] Manual No. M-14 class 1 – Automatic fire sprinkler systems with direct connection from public water mains only; no pumps, tanks, or reservoirs; no physical connection from other water supplies; no antifreeze or additives of any kind; and all sprinkler drains discharging to the atmosphere or other safe outlets.
(2) American Water Works Association [A.W.W.A] Manual No. M-14 class 2 – Automatic fire sprinkler systems which are the same as class 1, except that booster pumps may be installed in the connections from the street mains.
(b) Automatic fire sprinkler systems described in subdi- vision (a) shall not require any backflow protection equipment at the service connection other than required by standards for those systems contained in the publication of the National Fire Protection Association entitled “Installation of Sprinkler Sys- tems” [NFPA Pamphlet No. 13, 1980 edition]. 603.5.14.1 Fire Department Connection. Where fire protection systems supplied from a potable water system include a fire department (siamese) connection that is located less than 1700 feet (518.2 m) from a nonpotable water source that is capable of being used by the fire department as a secondary water supply, the potable water supply shall be protected by one of the following:
(1) Reduced pressure principle backflow prevention assembly (RP)
(2) Reduced pressure detector fire protection backflow prevention assembly
Nonpotable water sources include fire department vehicles carrying water of questionable quality or water that is treated with antifreeze, corrosion inhibitors, or extinguishing agents. 603.5.14.2 Chemicals. Where antifreeze, corrosion inhibitors, or other chemicals are added to a fire protection system supplied from a potable water supply, the potable water system shall be protected by one of the following:
(1) Reduced pressure principle backflow prevention assembly (RP)
(2) Reduced pressure detector fire protection backflow prevention assembly 603.5.14.3 Hydraulic Design. Where a backflow device is installed in the potable water supply to a fire protection system, the hydraulic design of the system shall account for the pressure drop through the backflow device. Where such devices are retrofitted for an existing fire protection system, the hydraulics of the sprinkler system design shall be checked to verify that there will be sufficient water pressure available for satisfactory operation of the fire sprinklers. 603.5.15 Health Care or Laboratory Areas. Vacuum breakers for washer-hose bedpans shall be located not less than 5 feet (1524 mm) above the floor. Hose con
nections in health care or laboratory areas shall be not less than 6 feet (1829 mm) above the floor. 603.5.16 Special Equipment. Portable cleaning equipment and dental vacuum pumps shall be protected from backflow by an air gap, an atmospheric vacuum breaker, a spill-resistant vacuum breaker, or a reduced pressure principle backflow preventer.
603.5.17 Potable Water Outlets and Valves. Potable water outlets, freeze-proof yard hydrants, combination stop-and-waste valves, or other fixtures that incorporate a stop and waste feature that drains into the ground shall not be installed underground. 603.5.18 Pure Water Process Systems. The water supply to a pure water process system, such as dialysis water systems, semiconductor washing systems, and similar process piping systems, shall be protected from backpressure and backsiphonage by a reduced-pressure principle backflow preventer. 603.5.18.1 Dialysis Water Systems. The individual connections of the dialysis related equipment to the dialysis pure water system shall not require additional backflow protection. 603.5.19 Garbage Can Washers. Where garbage can washers are connected to a potable water supply system, the connection shall be protected against backflow in accordance with Table 603.2.
603.5.20 Plumbing Fixture Fittings. Plumbing fixture fittings with integral backflow protection shall comply with ASME A112.18.1/CSA B125.1. 603.5.21 Swimming Pools, Spas, and Hot Tubs. Potable water supply to swimming pools, spas, and hot tubs shall be protected by an air gap or a reduced pressure principle backflow preventer in accordance with the following:
(1) The unit is equipped with a submerged fill line.
(2) The potable water supply is directly connected to the unit circulation system. 603.5.22 Chemical Dispensers. The water supply to chemical dispensers shall be protected against backflow by one of the following:
(1) The chemical dispenser shall comply with ANSI/CAN/ASSE/IAPMO 1055. Where an installation involves a water source coming from a faucet with an integrated vacuum breaker device, a pressure bleed device conforming to IAPMO PS 104 shall be used to protect the vacuum breaker device.
(2) Water supply shall be protected by one of the following methods:
(a) Air gap
(b) Atmospheric vacuum breaker (AVB)
(c) Pressure vacuum breaker backflow prevention assembly (PVB)
(d) Spill-resistant pressure vacuum breaker (SVB)
(e) Reduced-pressure principle backflow prevention assembly (RP)
«
«
«
WATER SUPPLY AND DISTRIBUTION
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Plumbing Code (Title 24, Part 5)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
- Chapter 5 — WATER HEATERS
▸Chapter 6 — WATER SUPPLY AND DISTRIBUTION
Overview- 601.1 Applicability. This chapter shall govern the materials,
- 601.2 Water Supply and Flushing. Each plumbing fixture shall b…
- 601.3 Identification of a Potable and Nonpotable
- 601.4 Schools of Cosmetology and Cosmetological
- 601.5 Meat and Poultry Processing Plants. [AGR]
- 601.6 Collection Centers and Facilities. [AGR]
- 601.7 Renderers. [AGR] This area shall be provided with
- 601.8 Horse Meat and Pet Food Establishments. [AGR]
- 602.1 Prohibited Installation. No installation of potable
- 602.2 Cross-Contamination. No person shall make a connection o…
- 602.3 Backflow Prevention. No plumbing fixture, device,
- 602.4 Approval by Authority. No water piping supplied
- 603.1 General. Cross-connection control shall be provided
- 603.2 Approval of Devices or Assemblies. Before a
- 603.3 Backflow Prevention Devices, Assemblies, and
- 603.4 General Requirements. Assemblies shall comply
- 603.5 Specific Requirements. Specific requirements for
- 604.1 Pipe, Tube, and Fittings. Pipe, tube, fittings, solvent …
- 604.2 Lead Content. The maximum allowable lead content
- 604.3 Copper or Copper Alloy Tube. Copper or copper
- 604.4 Hard-Drawn Copper or Copper Alloy Tubing.
- 604.5 Flexible Connectors. Flexible water connectors
- 604.6 Cast-Iron Fittings. Cast-iron fittings up to and
- 604.7 Malleable Iron Fittings. Malleable iron water fittings s…
- 604.8 Previously Used Piping and Tubing. Piping and
- 604.9 Epoxy Coating. The epoxy coating used on existing, under…
- 604.10 Plastic Materials. Approved plastic materials shall
- 604.11 Solder. Solder shall comply with the requirements of
- 604.12 Flexible Corrugated Connectors. Flexible corrugated con…
- 604.13 Water Heater Connectors. Flexible metallic (copper and …
- 605.1 Copper or Copper Alloy Pipe, Tubing, and
- 605.2 CPVC Plastic Pipe and Joints. CPVC plastic pipe
- 605.3 CPVC/AL/CPVC Plastic Pipe and Joints. Chlorinated polyvi…
- 605.4 Ductile Iron Pipe and Joints. Ductile iron pipe
- 605.5 Galvanized Steel Pipe and Joints. Galvanized
- 605.6 PE Plastic Pipe/Tubing and Joints. PE plastic
- 605.7 PE-AL-PE Plastic Pipe/Tubing and Joints. PEAL-PE plastic…
- 605.8 PE-RT. Polyethylene of raised temperature (PE-RT)
- 605.9 PEX Plastic Tubing and Joints. PEX plastic tubing and fi…
- 605.10 PEX-AL-PEX Plastic Tubing and Joints. PEXAL-PEX plastic…
- 605.11 Polypropylene (PP) Piping and Joints. PP pipe
- 605.12 PVC Plastic Pipe and Joints. PVC plastic pipe
- 605.13 Stainless Steel Pipe and Joints. Joining methods for st…
- 605.14 Slip Joints. In water piping, slip joints shall be perm…
- 605.15 Dielectric Unions. Dielectric unions where installed
- 605.16 Joints Between Various Materials. Joints
- 606.1 General. Valves up to and including 2 inches (50
- 606.2 Fullway Valve. A fullway valve controlling outlets
- 606.3 Multidwelling Units. In multidwelling units, one or
- 606.4 Multiple Openings. Valves used to control two or
- 606.5 Control Valve. A control valve shall be installed
- 606.6 Accessible. Required shutoff or control valves shall
- 606.7 Multiple Fixtures. A single control valve shall be
- 606.8 [OSHPD 1, 1R, 2, 3, 4 & 5] Each riser or branch
- 606.9 Check Valve Required. All systems that circulate
- 606.10 Leak Detection Devices. Where leak detection
- 607.1 General. Potable water supply tanks shall be installed in
- 607.2 Private Well Water Tanks. Pressurized potable water
- 607.3 Potable Water Tanks. Potable water supply tanks,
- 607.4 Venting. Tanks used for potable water shall be tightly
- 607.5 Overflow. Tanks shall have not less than a 16 square
- 607.6 Valves. Pressurized tanks shall be provided with a listed
- 608.1 Inadequate Water Pressure. Where the water pressure in t…
- 608.2 Excessive Water Pressure. Where static water
- 608.3 Expansion Tanks, and Combination Tempera-
- 608.4 Pressure Relief Valves. Each pressure relief valve
- 608.5 Discharge Piping. The discharge piping serving a
- 608.6 Water-Heating Devices. A water-heating device
- 608.7 Vacuum Relief Valves. Where a hot-water storage
- 609.1 Installation. Water piping shall be adequately supported…
- 609.2 Trenches. Water pipes shall not be run or laid in the
- 609.3 Under Concrete Slab. Water piping installed within
- 609.4 Testing. Upon completion of a section or of the entire
- 609.5 Unions. Unions shall be installed in the water supply
- 609.6 Location. Except as provided in Section 609.7, no
- 609.7 Abutting Lot. Nothing contained in this code shall
- 609.8 Pumps. Pumps shall be installed in accordance with
- 609.9 Low-Pressure Cutoff Required on Booster
- 609.10 Disinfection of Potable Water System. New or
- 609.11 Water Hammer. [Not adopted by HCD] Building
- 609.12 Pipe Insulation. Insulation of domestic hot water
- 610.1 Size. The size of each water meter and each potable
- 610.2 Pressure Loss. Where a water filter, water softener,
- 610.3 Quantity of Water. The quantity of water required to be
- 610.4 Sizing Water Supply and Distribution Systems.
- 610.5 Sizing per Appendices A, C, and M . Except as
- 610.6 Friction and Pressure Loss. Except where the type
- 610.7 Conditions for Using Table 610.4. On a proposed
- 610.8 Size of Meter and Building Supply Pipe Using
- 610.9 Size of Branches. Where Table 610.4 is used, the minimum…
- 610.10 Sizing for Flushometer Valves. Where using
- 610.11 Sizing Systems for Flushometer Tanks. The size
- 610.12 Sizing for Velocity. Water piping systems shall not
- 610.13 Exceptions. The provisions of this section relative
- 611.1 Application. Drinking water treatment units shall
- 611.2 Air Gap Discharge. Discharge from drinking water
- 611.3 Connection Tubing. The tubing to and from drinking water…
- 611.4 Sizing of Residential Softeners. Residential-use
- 612.1 Installation. Residential Sprinkler Systems shall be
- 613.1 The domestic water-heating equipment and distribu-
- 613.2 At least two pieces of hot-water-heating equipment shall
- 613.3 Instantaneous heaters are permitted for supplying hot
- 613.4 Water storage tanks shall be fabricated of corrosion-
- 613.5 Temperature control valves shall be provided to auto-
- 613.6 Hot-water distribution system serving patient care areas
- 613.7 At fixtures where water exceeding 125°F (52°C) is acces-
- 613.8 Sectionalizing valves shall be provided as required by
- 613.9 Hot water distribution shall include test ports and valved
- 614.1 Dialysis water feedlines shall be CPVC (chlorinated
- 614.2 All piping for multistation or central dialysis units sh…
- 614.3 All valves shall be located in accessible locations.
- 614.4 Piping and valves shall be identified according to their
- 614.5 A means of preventing backwashing or flushing of the
- 614.6 A continuous audible alarm shall sound at the nurses’
- 614.7 Water treatment equipment and water used for dialysis
- 614.8 A diagram of all piping as installed shall be posted at …
- 615.1 Uses Not Permitted.
- 615.2 [OSHPD 1, 1R, 2, 3, 4 & 5] Non-potable water sys-
- 615.3 [OSHPD 1, 1R, 2, 3, 4 & 5] Outlets for non-potable
- 616.1 For new acute care hospital buildings submitted after
- 616.2 The emergency supply of water shall be provided at ade-
- 616.3 Storage tank connections and circulation shall be
- Chapter 7 — SANITARY DRAINAGE
- Chapter 8 — INDIRECT WASTES
- Chapter 9 — VENTS
- Chapter 10 — TRAPS AND INTERCEPTORS
- Chapter 11 — STORM DRAINAGE
- Chapter 12 — FUEL GAS PIPING
- Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
- Chapter 14 — FIRESTOP PROTECTION
- Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
- Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
- Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
- Appendix C — ALTERNATE PLUMBING SYSTEMS
- Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
- Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
- Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
- Appendix G — SIZING OF VENTING SYSTEMS
- Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
- Appendix I — INSTALLATION STANDARDS
- Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
- Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
- Appendix L — SUSTAINABLE PRACTICES
- Appendix M — PEAK WATER DEMAND CALCULATOR
- Appendix N — IMPACT OF WATER TEMPERATURE ON THE POTENTIAL FOR …
- Appendix O — NON-SEWERED SANITATION SYSTEMS
- Appendix P — PROFESSIONAL QUALIFICATIONS
- Appendix Q — INDOOR HORTICULTURAL FACILITIES
- Appendix R — TINY HOUSES
- Appendix S — ONSITE STORMWATER TREATMENT SYSTEMS