Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
1503.3 Connections to Potable and Reclaimed (Recy-cled) Water Systems — 2025 California Plumbing Code
California Plumbing Code (Title 24, Part 5) · 2025 edition · updated 2026-09-25 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
Cite as: 2025 California Plumbing Code (Title 24, Part 5) § 1503.3 · Effective January 1, 2026 · Official source: Building Standards Commission
cled) Water Systems. Gray water systems shall have no direct connection to a potable water supply, on-site treated nonpotable gray water supply, or reclaimed (recycled) water sup- ply systems.
Exceptions:
(1) Potable water, on-site treated nonpotable gray water, reclaimed (recycled) water , or rainwater is permitted to be used as makeup water for a non-pressurized storage tank provided the connection is protected by an air gap in accordance with this code.
(2) A potable water supply may be connected temporarily for the initial cross-connection test of the untreated gray- water system as required in Section 1502.3.2.