Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
1503.9 Gray Water System Components — 2025 California Plumbing Code
California Plumbing Code (Title 24, Part 5) · 2025 edition · updated 2026-09-25 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
Cite as: 2025 California Plumbing Code (Title 24, Part 5) § 1503.9 · Effective January 1, 2026 · Official source: Building Standards Commission
Gray water system components shall comply with Section 1503.9.1 through Section 1503.9.4 .
[HCD 1] Gray water system components shall comply with this chapter.
1503.9.1 Surge Tanks. Where installed, surge tanks shall be in accordance with the following:
(1) Surge tanks shall be constructed of solid, durable materials not subject to excessive corrosion or decay and shall be watertight. Aboveground surge tanks shall be protected from direct sunlight or shall be constructed of UV resistant materials including but not limited to heavily tinted or opaque plastic, fiber- glass, lined metal, concrete and wood. Surge tanks constructed of steel shall be approved by the Authority Having Jurisdiction, provided such tanks are in accordance with approved applicable standards.
(2) Each surge tank shall be vented in accordance with this code. The vent size shall be determined based on
the total gray water fixture units as outlined in this code.
(3) Each surge tank shall have an access opening with lockable gasketed covers or approved equivalent to allow for inspection and cleaning.
(4) Each surge tank shall have its rated capacity permanently marked on the unit. Also, a sign stating “GRAY WATER SYSTEM, CAUTION DANGER — UNSAFE WATER” shall be permanently marked on the holding tank.
(5) Each surge tank shall have an overflow drain. The overflow drains shall have permanent connections to the building drain or building sewer, upstream of septic tanks. The overflow drain shall not be equipped with a shutoff valve.
(6) The overflow drainpipes shall not be less in size than the inlet pipe. Unions or equally effective fittings shall be provided for piping connected to the surge tank.
(7) Surge tank shall be structurally designed to withstand anticipated earth or other loads. Surge tank covers shall be capable of supporting an earth load of not less than 300 pounds per square foot (lb/ft [2] ) (1465 kg/m [2] ) where the tank is designed for underground installation.
ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
(8) Where a surge tank is installed underground, the system shall be designed so that the tank overflow will gravity drain to the existing sewer line or septic tank. The tank shall be protected against sewer line backflow by a backwater valve installed in accordance with this code.
(9) Surge tanks shall be installed on dry, level, wellcompacted soil where underground or on a level 3 inch (76 mm) thick concrete slab or other approved method where aboveground.
(10)Surge tanks shall be anchored to prevent against overturning where installed aboveground. Underground tanks shall be ballasted, anchored, or otherwise secured, to prevent the tank from floating out of the ground where empty. The combined weight of the tank and hold down system shall meet or exceed the buoyancy forces of the tank.
(11) [HCD 1] An overflow drain and backwater valve is not required on a clothes washer system.
1503.9.2 Gray Water Pipe and Fitting Materials. Aboveground and underground building drainage and vent pipe and fittings for gray water systems shall comply with the requirements for aboveground and underground sanitary building drainage and vent pipe and fittings in this code. These materials shall extend not less than 2 feet (610 mm) outside the building.
1503.9.3 Animals and Insects. Gray water tank openings shall be protected to prevent the entrance of insects, birds, or rodents into the tank and piping sys- tems. Screens installed on vent pipes, inlets, and over- flow pipes shall have an aperture of not greater than [1] ∕ 16 of an inch (1.6 mm) and shall be close fitting.
1503.9.4 Freeze Protection. Tanks and piping installed in locations subject to freezing shall be provided with an approved means of freeze protection.