1101.6 Subsoil Drains. Subsoil drains shall be provided
California Plumbing Code (Title 24, Part 5) · 2025 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
around the perimeter of buildings having basements, cellars, crawl spaces, or floors below grade. Such subsoil drains shall be permitted to be positioned inside or outside of the footing, shall be of perforated or open-jointed approved drain tile or pipe, not less than 3 inches (80 mm) in diameter, and shall be laid in gravel, slag, crushed rock, approved [3] ⁄ 4 of an inch (19.1 mm) crushed, recycled glass aggregate, or other approved porous material with not less than 4 inches (102 mm) surrounding the pipe. Filter media shall be provided for exterior subsoil piping. Exception: [HCD 1 & HCD 2] Subsoil drains are mandatory only when required by the Authority Having Jurisdiction due to geological conditions.
TABLE 1101.4.6
MATERIALS FOR SUBSOIL DRAINPIPE AND FITTINGS
STORM DRAINAGE
1101.6.1 Discharge. Subsoil drains shall be piped to a storm drain, to an approved water course, to the front street curb or gutter, to an alley, or the discharge from the subsoil drains shall be conveyed to the alley by a concrete gutter. Where a continuously flowing spring or groundwater is encountered, subsoil drains shall be piped to a storm drain or an approved water course. 1101.6.2 Sump. Where it is not possible to convey the drainage by gravity, subsoil drains shall discharge to an accessible sump provided with an approved automatic electric pump. The sump shall be not less than 15 inches (381 mm) in diameter, 18 inches (457 mm) in depth, and provided with a fitted cover. The sump pump shall have an adequate capacity to discharge water coming into the sump as it accumulates to the required discharge point, and the capacity of the pump shall be not less than 15 gallons per minute (gpm) (0.95 L/s). The discharge piping from the sump pump shall be not less than 1 [1] ⁄ 2 inches (40 mm) in diameter and have a union or other approved quick-disconnect assembly to make the pump accessible for servicing. 1101.6.3 Splash Blocks. For separate dwellings not serving continuously flowing springs or groundwater, the sump discharge pipe shall be permitted to discharge onto a concrete splash block with a minimum length of 24 inches (610 mm). This pipe shall be within 4 inches (102 mm) of the splash block and positioned to direct the flow parallel to the recessed line of the splash block.
1101.6.4 Backwater Valve. Subsoil drains subject to backflow where discharging into a storm drain shall be provided with a backwater valve in the drain line so located as to be accessible for inspection and maintenance. 1101.6.5 Open Area. Nothing in Section 1101.6 shall prevent drains that serve either subsoil drains or areaways of a detached building from discharging to a properly graded open area, provided that:
(1) They do not serve continuously flowing springs or groundwater.
(2) The point of discharge is not less than 10 feet (3048 mm) from a property line.
(3) It is impracticable to discharge such drains to a storm drain, to an approved water course, to the front street curb or gutter, or to an alley.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Plumbing Code (Title 24, Part 5)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
- Chapter 5 — WATER HEATERS
- Chapter 6 — WATER SUPPLY AND DISTRIBUTION
- Chapter 7 — SANITARY DRAINAGE
- Chapter 8 — INDIRECT WASTES
- Chapter 9 — VENTS
- Chapter 10 — TRAPS AND INTERCEPTORS
▸Chapter 11 — STORM DRAINAGE
Overview- 1101.1 Applicability. This chapter shall govern the materials,…
- 1101.2 Where Required. Roofs, paved areas, yards, courts,
- 1101.3 Storm Water Drainage to Sanitary Sewer Pro-
- 1101.4 Material Uses. Pipe, tube, and fittings conveying
- 1101.5 Expansion Joints Required. Expansion joints or
- 1101.6 Subsoil Drains. Subsoil drains shall be provided
- 1101.7 Building Subdrains. Building subdrains located
- 1101.8 Areaway Drains. Open subsurface space adjacent
- 1101.9 Window Areaway Drains. Window areaways at a
- 1101.10 Filling Stations and Motor Vehicle Washing
- 1101.11 Paved Areas. Where the occupant creates surface
- 1101.12 Roof Drainage. Roof drainage shall comply with
- 1101.13 Cleanouts. Cleanouts for building storm drains
- 1101.14 Rainwater Sumps. Rainwater sumps serving
- 1101.15 Traps on Storm Drains and Leaders. Leaders
- 1101.16 Leaders, Conductors, and Connections.
- 1102.1 Applications. Roof drains shall be constructed of
- 1102.2 Dome Strainers Required. Roof drains shall have
- 1102.3 Roof Drain Flashings. The connection between
- 1103.1 Vertical Conductors and Leaders. Vertical conductors an…
- 1103.2 Size of Horizontal Storm Drains and Sewers.
- 1103.3 Size of Roof Gutters. The size of semi-circular
- 1103.4 Side Walls Draining onto a Roof. Where vertical walls p…
- 1104.1 General. Where there is a continuous or semi-continuous…
- 1105.1 Application. Instead of sizing the storm drainage
- 1105.2 Setback Roofs. Drains on setback roofs shall be
- 1106.1 General. The design and sizing of a storm drainage
- 1106.2 Siphonic Roof Drainage Systems. The design of
- 1106.3 Siphonic Roof Drains. Siphonic roof drains shall
- 1107.1 Testing Required. New building storm drainage
- 1107.2 Methods of Testing Storm Drainage Systems.
- Chapter 12 — FUEL GAS PIPING
- Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
- Chapter 14 — FIRESTOP PROTECTION
- Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
- Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
- Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
- Appendix C — ALTERNATE PLUMBING SYSTEMS
- Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
- Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
- Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
- Appendix G — SIZING OF VENTING SYSTEMS
- Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
- Appendix I — INSTALLATION STANDARDS
- Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
- Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
- Appendix L — SUSTAINABLE PRACTICES
- Appendix M — PEAK WATER DEMAND CALCULATOR
- Appendix N — IMPACT OF WATER TEMPERATURE ON THE POTENTIAL FOR …
- Appendix O — NON-SEWERED SANITATION SYSTEMS
- Appendix P — PROFESSIONAL QUALIFICATIONS
- Appendix Q — INDOOR HORTICULTURAL FACILITIES
- Appendix R — TINY HOUSES
- Appendix S — ONSITE STORMWATER TREATMENT SYSTEMS