Chapter 10 — TRAPS AND INTERCEPTORS
1017.3 Interceptor Details.
California Plumbing Code (Title 24, Part 5) · 2025 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
Oil and flammable liquid interceptors shall be in accordance with the following:
(1) The separation or vapor compartment shall be independently vented to the outer air. Where two or more separation or vapor compartments are used, each shall be vented to the outer air or shall be permitted to connect to a header that is installed at a minimum of 6 inches (152 mm) above the spill line of the lowest floor drain and vented independently to the outer air.
(2) The minimum size of a flammable vapor vent shall be not less than 2 inches (50 mm), and, where vented through a sidewall, the vent shall be not less than 10 feet (3048 mm) above the adjacent level at an approved location.
(3) The interceptor shall be vented on the sewer side and shall not connect to a flammable vapor vent. Oil and flammable interceptors shall be provided with gastight cleanout covers that shall be readily accessible.
(4) The waste line shall be not less than 3 inches (80 mm) in diameter with a full-size cleanout to grade.
(5) Where an interceptor is provided with an overflow, it shall be provided with an overflow line [not less than 2 inches (50 mm) in diameter] to an approved waste oil tank having a minimum capacity of 550 gallons (2082 L) and meeting the requirements of the Authority Having Jurisdiction.
(a) The waste oil from the separator shall flow by gravity or shall be pumped to a higher elevation by an automatic pump.
(b) Pumps shall be adequately sized and accessible.
(c) Waste oil tanks shall have a 2 inch (50 mm) minimum pump-out connection at grade and an 1 [1] ⁄ 2 inch (40 mm) minimum vent to atmosphere at an approved location not less than 10 feet (3048 mm) above grade.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Plumbing Code (Title 24, Part 5)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
- Chapter 5 — WATER HEATERS
- Chapter 6 — WATER SUPPLY AND DISTRIBUTION
- Chapter 7 — SANITARY DRAINAGE
- Chapter 8 — INDIRECT WASTES
- Chapter 9 — VENTS
▸Chapter 10 — TRAPS AND INTERCEPTORS
Overview- 1001.1 Applicability. This chapter shall govern the materials,…
- 1001.2 Where Required. Each plumbing fixture shall be separate…
- 1002.1 Vent Pipes. Each plumbing fixture trap, except as
- 1002.2 Fixture Traps. Each fixture trap shall have a protectin…
- 1002.3 Change of Direction. A trap arm shall be permitted to c…
- 1002.4 Vent Pipe Opening. The vent pipe opening from
- 1003.1 General Requirements. Each trap, except for
- 1003.2 Slip Joint Fittings. A maximum of one approved
- 1003.3 Size. The size (nominal diameter) of a trap for a
- 1004.1 Prohibited. No form of trap that depends for its seal
- 1004.2 Movable Parts. Bladders, check valves or another
- 1005.1 General. Each fixture trap shall have a liquid seal of
- 1006.1 General. Floor drains shall connect into a trap so
- 1007.1 General. Floor drain or similar traps directly connecte…
- 1007.2 Trap Seal Primers. Potable water supply trap seal
- 1008.1 General. Building traps shall not be installed except
- 1009.1 Where Required. Interceptors (clarifiers) (including gr…
- 1009.2 Approval. The size, type, and location of each intercep…
- 1009.3 Design. Interceptors (clarifiers) for sand and similar …
- 1009.4 Relief Vent. Interceptors (clarifiers) shall be so
- 1009.5 Location. Each interceptor (clarifier) cover shall be
- 1009.6 Maintenance of Interceptors. Interceptors shall
- 1009.7 Discharge. The waste pipe from oil and sand interceptor…
- 1010.1 General. A fish, fowl, and animal slaughterhouse or
- 1010.2 Meat and Poultry Processing Plants. [AGR]
- 1010.3 Collection Centers and Facilities. [AGR] All
- 1010.4 Horse Meat and Pet Food Establishments.
- 1010.5 Draining and Plumbing. [AGR] There shall be
- 1011.1 General. A private or public wash rack or floor or
- 1012.1 General. Laundry equipment in commercial and
- 1013.1 General. Bottling plants shall discharge their process
- 1014.1 General. Where it is determined by the Authority
- 1014.2 Hydromechanical Grease Interceptors. Plumbing fixtures …
- 1014.3 Gravity Grease Interceptors. Required gravity
- 1015.1 Purpose. The purpose of this section is to provide
- 1015.2 Components, Materials, and Equipment. FOG
- 1015.3 Sizing and Installation. FOG disposal systems
- 1015.4 Performance. FOG disposal systems shall produce
- 1015.5 [OSHPD 1, 1R, 2, 3, 4 & 5] Grease interceptors
- 1015.6 [OSHPD 1, 1R, 2, 3, 4 & 5] Grease interceptors
- 1016.1 Discharge. Where the discharge of a fixture or drain
- 1016.2 Authority Having Jurisdiction. Sand interceptors
- 1016.3 Construction and Size. Sand interceptors shall be
- 1016.4 Separate Use. Sand and similar interceptors for
- 1017.1 Interceptors Required. Repair garages and gasoline stat…
- 1017.2 Interceptor Design Alternatives. Oil interceptors
- 1017.3 Interceptor Details. Oil and flammable liquid intercept…
- 1017.4 Design of Interceptors. Each manufactured interceptor t…
- Chapter 11 — STORM DRAINAGE
- Chapter 12 — FUEL GAS PIPING
- Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
- Chapter 14 — FIRESTOP PROTECTION
- Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
- Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
- Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
- Appendix C — ALTERNATE PLUMBING SYSTEMS
- Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
- Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
- Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
- Appendix G — SIZING OF VENTING SYSTEMS
- Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
- Appendix I — INSTALLATION STANDARDS
- Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
- Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
- Appendix L — SUSTAINABLE PRACTICES
- Appendix M — PEAK WATER DEMAND CALCULATOR
- Appendix N — IMPACT OF WATER TEMPERATURE ON THE POTENTIAL FOR …
- Appendix O — NON-SEWERED SANITATION SYSTEMS
- Appendix P — PROFESSIONAL QUALIFICATIONS
- Appendix Q — INDOOR HORTICULTURAL FACILITIES
- Appendix R — TINY HOUSES
- Appendix S — ONSITE STORMWATER TREATMENT SYSTEMS