Oil and flammable liquid interceptors shall be in accordance with the following:

(1) The separation or vapor compartment shall be independently vented to the outer air. Where two or more separation or vapor compartments are used, each shall be vented to the outer air or shall be permitted to connect to a header that is installed at a minimum of 6 inches (152 mm) above the spill line of the lowest floor drain and vented independently to the outer air.

(2) The minimum size of a flammable vapor vent shall be not less than 2 inches (50 mm), and, where vented through a sidewall, the vent shall be not less than 10 feet (3048 mm) above the adjacent level at an approved location.

(3) The interceptor shall be vented on the sewer side and shall not connect to a flammable vapor vent. Oil and flammable interceptors shall be provided with gastight cleanout covers that shall be readily accessible.

(4) The waste line shall be not less than 3 inches (80 mm) in diameter with a full-size cleanout to grade.

(5) Where an interceptor is provided with an overflow, it shall be provided with an overflow line [not less than 2 inches (50 mm) in diameter] to an approved waste oil tank having a minimum capacity of 550 gallons (2082 L) and meeting the requirements of the Authority Having Jurisdiction.

(a) The waste oil from the separator shall flow by gravity or shall be pumped to a higher elevation by an automatic pump.

(b) Pumps shall be adequately sized and accessible.

(c) Waste oil tanks shall have a 2 inch (50 mm) minimum pump-out connection at grade and an 1 1/2 inch (40 mm) minimum vent to atmosphere at an approved location not less than 10 feet (3048 mm) above grade.