Chapter 10 — TRAPS AND INTERCEPTORS
1014.2 Hydromechanical Grease Interceptors — 2025 California Plumbing Code
California Plumbing Code (Title 24, Part 5) · 2025 edition · updated 2026-09-25 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
Cite as: 2025 California Plumbing Code (Title 24, Part 5) § 1014.2 · Effective January 1, 2026 · Official source: Building Standards Commission
Plumbing fixtures or equipment connected to a Type A and B hydromechanical grease interceptor shall discharge through an approved type of vented flow control installed in a readily accessible and visible location. Flow control devices shall be
designed and installed so that the total flow through such device or devices shall at no time be greater than the rated flow of the connected grease interceptor. No flow control device having adjustable or removable parts shall be approved. The vented flow control device shall be located such that no system vent shall be between the flow control and the grease interceptor inlet. The vent or air inlet of the flow control device shall connect with the sanitary drainage vent system, as elsewhere required by this code, or shall terminate through the roof of the building, and shall not terminate to the free atmosphere inside the building.
Exception: Listed grease interceptors with integral flow controls or restricting devices shall be installed in an accessible location in accordance with the manufacturer’s installation
instructions.
1014.2.1 Capacity. The total capacity in gallons (gal) (L) of fixtures discharging into a hydromechanical grease interceptor shall not exceed two and one-half times the certified gallon per minute (gpm) (L/s) flow rate of the interceptor in accordance with Table 1014.2.1.
For this section, the term “fixture” shall mean and include each plumbing fixture, appliance, apparatus, or other equipment required to be connected to or discharged into a grease interceptor by a provision of this section.
1014.2.2 Vent. A vent shall be installed downstream of
hydromechanical grease interceptors in accordance with the requirements of this code.
TABLE 1014.2.1
HYDROMECHANICAL GREASE INTERCEPTOR SIZING USING GRAVITY FLOW RATES [1]
| DIAMETER OF GREASE WASTE PIPE (inches) |
MAXIMUM FULL PIPE FLOW (gpm)2 |
SIZE OF GREASE INTERCEPTOR | |
|---|---|---|---|
DIAMETER OF GREASE WASTE PIPE (inches) |
MAXIMUM FULL PIPE FLOW (gpm)2 |
ONE-MINUTE DRAINAGE PERIOD (gpm) |
TWO-MINUTE DRAINAGE PERIOD (gpm) |
2 |
20 | 20 | 10 |
3 |
60 | 75 | 35 |
4 |
125 | 150 | 75 |
5 |
230 | 250 | 125 |
6 |
375 | 400 | 200 |
For SI units: 1 inch = 25 mm, 1 gallon per minute = 0.06 L/s
Notes: 1 For interceptor sizing by the fixture capacity see the example below. 2 1 ∕ 4 inch slope per foot (20.8 mm/m) based on Manning’s formula with friction factor N = 0.012.
EXAMPLE 1014.2.1
SIZING HYDROMECHANICAL GREASE INTERCEPTOR(S)
USING FIXTURE CAPACITY
Step 1: Determine the flow rate from each fixture.
[Length] X [Width] X [Depth] / [231] = Gallons X [0.75 fill factor] / [Drain
Period (1 minute or 2 minutes)]
Step 2: Calculate the total load from fixtures that discharge into
the interceptor.
| FIXTURES | COMPART- MENTS |
LOAD (gallons) |
SIZE OF GREASE INTERCEPTOR ONE-MINUTE DRAINAGE PERIOD (gpm) |
TWO- MINUTE DRAINAGE PERIOD (gpm) |
|---|---|---|---|---|
Compartment size |
–– | –– | –– | –– |
24 inches x 24 inches x 12 inches |
2 | 44.9 | –– | –– |
Hydrant |
–– | 3 | –– | –– |
Rated Appliance |
–– | 2 | –– | –– |
–– |
–– | 49.9 | 50 | 25 |
For SI units: 1 inch = 25.4 mm, 1 gallon per minute = 0.06 L/s, 1 gallon =
3.785 L