1014.2 Hydromechanical Grease Interceptors — 2025 California Plumbing Code

California Plumbing Code (Title 24, Part 5) · 2025 edition · updated 2026-09-25 · California

CBSC: official editions, supplements and errata

Italicized text is a California amendment to the model code, as printed in the official publication.

Cite as: 2025 California Plumbing Code (Title 24, Part 5) § 1014.2 · Effective January 1, 2026 · Official source: Building Standards Commission

Plumbing fixtures or equipment connected to a Type A and B hydromechanical grease interceptor shall discharge through an approved type of vented flow control installed in a readily accessible and visible location. Flow control devices shall be

designed and installed so that the total flow through such device or devices shall at no time be greater than the rated flow of the connected grease interceptor. No flow control device having adjustable or removable parts shall be approved. The vented flow control device shall be located such that no system vent shall be between the flow control and the grease interceptor inlet. The vent or air inlet of the flow control device shall connect with the sanitary drainage vent system, as elsewhere required by this code, or shall terminate through the roof of the building, and shall not terminate to the free atmosphere inside the building.

Exception: Listed grease interceptors with integral flow controls or restricting devices shall be installed in an accessible location in accordance with the manufacturer’s installation

instructions.

1014.2.1 Capacity. The total capacity in gallons (gal) (L) of fixtures discharging into a hydromechanical grease interceptor shall not exceed two and one-half times the certified gallon per minute (gpm) (L/s) flow rate of the interceptor in accordance with Table 1014.2.1.

For this section, the term “fixture” shall mean and include each plumbing fixture, appliance, apparatus, or other equipment required to be connected to or discharged into a grease interceptor by a provision of this section.

1014.2.2 Vent. A vent shall be installed downstream of

hydromechanical grease interceptors in accordance with the requirements of this code.

TABLE 1014.2.1

HYDROMECHANICAL GREASE INTERCEPTOR SIZING USING GRAVITY FLOW RATES [1]

DIAMETER OF
GREASE WASTE
PIPE (inches)
MAXIMUM FULL
PIPE FLOW
(gpm)2
SIZE OF GREASE INTERCEPTOR





DIAMETER OF
GREASE WASTE
PIPE (inches)
MAXIMUM FULL
PIPE FLOW
(gpm)2
ONE-MINUTE
DRAINAGE
PERIOD
(gpm)
TWO-MINUTE
DRAINAGE
PERIOD
(gpm)


2
20 20 10


3
60 75 35

4
125 150 75

5
230 250 125

6
375 400 200

For SI units: 1 inch = 25 mm, 1 gallon per minute = 0.06 L/s

Notes: 1 For interceptor sizing by the fixture capacity see the example below. 2 1 ∕ 4 inch slope per foot (20.8 mm/m) based on Manning’s formula with friction factor N = 0.012.

EXAMPLE 1014.2.1

SIZING HYDROMECHANICAL GREASE INTERCEPTOR(S)

USING FIXTURE CAPACITY

Step 1: Determine the flow rate from each fixture.

[Length] X [Width] X [Depth] / [231] = Gallons X [0.75 fill factor] / [Drain

Period (1 minute or 2 minutes)]

Step 2: Calculate the total load from fixtures that discharge into

the interceptor.

FIXTURES COMPART-
MENTS
LOAD
(gallons)
SIZE OF
GREASE
INTERCEPTOR
ONE-MINUTE
DRAINAGE
PERIOD
(gpm)
TWO-
MINUTE
DRAINAGE
PERIOD
(gpm)


Compartment
size
–– –– –– ––



24 inches x 24
inches x 12
inches
2 44.9 –– ––

Hydrant
–– 3 –– ––


Rated
Appliance
–– 2 –– ––


––
–– 49.9 50 25

For SI units: 1 inch = 25.4 mm, 1 gallon per minute = 0.06 L/s, 1 gallon =

3.785 L