517.3 Hoods for Solid-Fuel Cooking. Hoods shall be sized
California Mechanical Code (Title 24, Part 4) · 2022 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
and located in a manner capable of capturing and containing all the effluent discharging from the appliances. The hood and its exhaust system shall comply with the requirements of Section 508.0 through Section 513.0. [NFPA 96:14.3.1, 14.3.2] 517.3.1 Separation. Except as permitted in Section 517.3.1.1, exhaust systems serving solid-fuel cooking equipment, including gas or electrically operated equipment, shall be separate from all other exhaust systems.
[NFPA 96:14.3.3] Exception: Cooking equipment not requiring automatic fire-extinguishing equipment (per Section 513.0) shall be permitted to be installed under a common hood with solid-fuel cooking equipment that is served by a duct system separate from all other exhaust systems. [NFPA 96:14.3.5]
517.3.1.1 Equipment with Solid Fuel for Fla- voring. Gas-operated equipment utilizing solid fuel for flavoring that meets all the following conditions shall not be required to have a separate exhaust system: (1) The solid fuel holder (smoker box) shall be listed
with the gas-operated equipment. (2) The solid fuel holder shall be located underneath
the gas burners. (3) Spark arresters conforming with Section 517.1.6
shall be provided. (4) The maximum quantity of solid fuel consumed
shall not exceed 1 pound (0.45 kg) per hour per 100 000 Btu/h (29 kW) of gas burner capacity. (5) The gas-operated equipment shall be protected by
a fire suppression system listed for the equipment, including the solid fuel holder. (6) Gas-operated equipment with integral solid fuel
holder(s) intended for flavoring, such as radiant charbroiler(s), shall comply simultaneously with the requirements of UL 300 that address the gas radiant charbroiler(s) and mesquite wood charbroiler(s). (7) A fire suppression system nozzle(s) shall be
installed to protect the solid fuel holder.
2022 CALIFORNIA MECHANICAL CODE 117
EXHAUST SYSTEMS
(8) The fire suppression system shall be designed and
installed to protect the entire cooking operation. (9) Each solid fuel holder shall be limited to a size of
150 cubic inches (2.5 L), with no dimension to exceed 20 inches (508 mm). (10) A maximum of one solid fuel holder for each 100
000 Btu/h (29 kW), or portion thereof, of burner capacity shall be permitted. (11) Solid fuel shall be immersed in water for a con tinuous period of at least 24 hours immediately prior to being placed in the cooking equipment. (12) The inspection frequency shall be the same as for
solid fuel cooking operations in Table 514.3.
[NFPA 96:14.3.4]
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Mechanical Code (Title 24, Part 4)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — VENTILATION AIR
▸Chapter 5 — EXHAUST SYSTEMS
Overview- 501.1 Applicability. This chapter includes requirements for
- 502.1 Exhaust Opening Protection. Exhaust openings
- 502.2 Termination of Exhaust Ducts. Exhaust ducts
- 503.1 General. Motors and fans shall be sized to provide
- 503.2 Fans. Parts of fans in contact with explosive or flammab…
- 504.1 General. Where not specified in this chapter, exhaust
- 504.2 Independent Exhaust Systems. Single or combined mechanic…
- 504.3 Domestic Range. Ducts used for domestic kitchen
- 504.4 Clothes Dryers. A clothes dryer exhaust duct shall not
- 504.5 Heat (Energy) Recovery Ventilators. Heat
- 504.6 Gypsum Wallboard Ducts. Bathroom and laundry
- 505.1 General. A mechanical ventilation or exhaust system
- 505.2 Incompatible Materials. Incompatible materials
- 505.3 Flammability Limit. Unless the circumstances stipulated …
- 505.4 Air-Moving Devices. Air-moving devices shall be
- 505.5 Generating Flames, Sparks, or Hot Materials.
- 505.6 Fire Dampers. Fire dampers shall be permitted to be
- 505.7 Fire Detection and Alarm Systems. Unless the
- 505.8 Product-Conveying Ducts Classification. Product-conveyin…
- 505.9 Minimum Velocities and Circulation. The velocity and cir…
- 505.10 Makeup Air. Makeup air shall be provided to replenish a…
- 505.11 Hoods and Enclosures. Hoods and enclosures shall
- 505.12 Pharmacies – Compounding Area of Par-
- 506.1 Materials. Materials used in product-conveying duct
- 506.2 Construction. Ducts used for conveying products
- 506.3 Penetrations. Exhaust ducts shall not pass through
- 506.4 Condensate. Joints in duct construction shall be liquidt…
- 506.5 Fittings. Fittings in Class 2, 3, and 4 systems shall be
- 506.6 Explosion Venting. Ducts conveying explosive dusts
- 506.7 Supports. Supports shall be of noncombustible materials,…
- 506.8 Fire Protection. Sprinklers or other fire-protection
- 506.9 Protection from Physical Damage. Ducts
- 506.10 Duct Clearances. Unless the conditions stipulated
- 506.11 Clearance Reduction Methods. It shall be permitted to p…
- 507.1 Type I Hood Exhaust System. Exhaust systems
- 507.2 Exhaust System. Cooking equipment used in
- 507.3 Listed Devices. Penetrations shall be sealed with
- 507.4 Clearance. Where enclosures are not required, hoods,
- 507.5 Drawings. A drawing(s) of the exhaust system installatio…
- 507.6 Notification of Change. If required by the Authority Hav…
- 507.7 Pharmaceutical Compounding Exhaust Dis-
- 508.1 Where Required. Type I hoods shall be installed at
- 508.2 Listed Type I Hood Assemblies. Listed hood
- 508.3 Construction of Type I Hoods. The hood or that
- 508.4 Supports. Hoods shall be secured in place [OSHPD
- 508.5 Hood Size. Hoods shall be sized in accordance with
- 508.6 Solid-Fuel Hood Assemblies. Where solid-fuel
- 508.7 Exhaust Outlets. An exhaust outlet within an
- 509.1 Grease Removal Devices. Listed grease filters or
- 509.2 Installation. The distance between the grease removal
- 509.3 Solid-Fuel Grease Removal Devices. Where
- 510.1 General. Ducts shall not pass through fire walls.
- 510.2 Clearance. Clearance between ducts and combustible
- 510.3 Openings. Openings shall be provided at the sides or
- 510.4 Listed Grease Ducts. Listed grease ducts shall be
- 510.5 Other Grease Ducts. Other grease ducts shall comply with…
- 510.6 Exterior Installations. The exterior portion of the
- 510.7 Interior Installations. In all buildings more than one
- 510.8 Underground Installations. Grease ducts installed
- 510.9 Termination of Type I Hood Exhaust System.
- 510.10 Solid-Fuel Duct Systems. Where solid-fuel cooking equip…
- 511.1 Exhaust Fans for Commercial Cooking Opera-
- 511.2 Airflow. The air velocity through a duct shall be not
- 511.3 Makeup Air. The makeup air quantity shall prevent
- 511.4 Common Duct (Manifold) Systems. Master
- 511.5 Solid-Fuel Air Movement Requirements. Where
- 512.1 Dampers. Dampers shall not be installed in exhaust
- 512.2 Electrical Equipment. Wiring systems of any type
- 512.3 Other Equipment. Fume incinerators, thermal recovery uni…
- 512.4 Solid-Fuel Auxiliary Equipment. Where solid fuel
- 513.1 General. Fire-extinguishing equipment for the protection…
- 513.2 Types of Equipment. Fire-extinguishing equipment
- 513.3 Simultaneous Operation. Fixed pipe extinguishing
- 513.4 Fuel and Electric Power Shutoff. Upon activation of
- 513.5 Manual Activation. All systems shall have both automatic…
- 514.2 Inspection, Testing, and Maintenance. Maintenance of the…
- 513.6 System Annunciation. Upon activation of an automatic fir…
- 513.7 Special Design and Application. Hoods containing
- 513.8 Review and Certification. Where required, complete
- 513.9 Installation Requirements. Installation of systems
- 513.10 Portable Fire Extinguishers. Portable fire extinguisher…
- 513.11 Maintenance. Portable fire extinguishers shall be
- 513.12 Solid-Fuel Fire-Extinguishing Equipment.
- 514.1 Operating Procedures. Exhaust systems shall be
- 514.3 Inspection for Grease Buildup. The entire exhaust
- 514.4 Cleaning of Exhaust Systems. If, upon inspection,
- 514.5 Cooking Equipment Maintenance. Inspection and
- 515.1 Cooking Equipment. Cooking equipment shall be
- 515.2 Operating Controls. Deep-fat fryers shall be equipped
- 516.1 General Requirements. Recirculating systems containing o…
- 516.2 Design Restrictions. All recirculating systems shall
- 516.3 Interlocks. The recirculating system shall be provided
- 516.4 Location and Application Restrictions. The
- 516.5 Additional Fire Safety Requirements. In addition to the …
- 516.6 Use and Maintenance. Automatic or manual covers on cooki…
- 517.1 Venting Application. Venting requirements of solidfuel c…
- 517.2 Location of Appliances. Every appliance shall be
- 517.3 Hoods for Solid-Fuel Cooking. Hoods shall be sized
- 517.4 Exhaust Systems for Solid-Fuel Cooking. Where
- 517.5 Grease Removal Devices for Solid-Fuel Cook-
- 517.6 Air Movement for Solid-Fuel Cooking. Exhaust
- 517.7 Fire-Extinguishing Equipment for Solid-Fuel
- 517.8 Other Safety Requirements. Metal-fabricated solidfuel co…
- 518.1 General. Downdraft appliance ventilation system
- 518.2 Ventilation System. The downdraft appliance ventilation …
- 518.3 Fire-Extinguishing Equipment. For fire-extinguishing equ…
- 518.4 Airflow Switch or Transducer. An airflow switch or
- 518.5 Surface Materials. Any surface located directly
- 519.1 Where Required. Type II hoods shall be installed
- 519.2 Construction of Type II Hoods. Type II hoods
- 519.3 Dishwashing Appliances. The net airflow for Type
- 519.4 Type II Exhaust Duct Systems. Ducts and
- 519.5 Termination of Type II Hood Exhaust System.
- 519.6 Makeup Air. Makeup air shall be provided in accordance w…
- Chapter 6 — DUCT SYSTEMS
- Chapter 7 — COMBUSTION AIR
- Chapter 8 — CHIMNEYS AND VENTS
- Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES
- Chapter 10 — BOILERS AND PRESSURE VESSELS
- Chapter 11 — REFRIGERATION
- Chapter 12 — HYDRONICS
- Chapter 13 — FUEL GAS PIPING
- Chapter 14 — PROCESS PIPING
- Chapter 15 — SOLAR ENERGY SYSTEMS
- Chapter 16 — STATIONARY POWER PLANTS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RESIDENTIAL PLAN EXAMINER REVIEW FORM FOR HVAC SY…
- Appendix B — PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT …
- Appendix C — INSTALLATION AND TESTING OF OIL (LIQUID) FUEL-FIR…
- Appendix D — FUEL SUPPLY: MANUFACTURED/MOBILE HOME PARKS AND R…
- Appendix E — SUSTAINABLE PRACTICES
- Appendix F — GEOTHERMAL ENERGY SYSTEMS
- Appendix G — SIZING OF VENTING SYSTEMS AND OUTDOOR COMBUSTION …
- Appendix H — EXAMPLE CALCULATION OF OUTDOOR AIR RATE