510.9 Termination of Type I Hood Exhaust System.

California Mechanical Code (Title 24, Part 4) · 2022 edition · updated 2026-09-10 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

The exhaust system shall terminate as follows: (1) Outside the building with a fan or duct. (2) Through the roof or to the roof from outside, as in Section

510.9.1, or through a wall, as in Section 510.9.2. [NFPA 96:7.8.1] 510.9.1 Rooftop Terminations. Rooftop terminations shall be arranged with or provided with the following: (1) A minimum of 10 feet (3048 mm) of horizontal

clearance from the outlet to adjacent buildings, property lines, and air intakes.

(2) A minimum of 5 feet (1524 mm) of horizontal clear ance from the outlet (fan housing) to any combustible structure. (3) A vertical separation of 3 feet (914 mm) above any

air intakes within 10 feet (3048 mm) of the exhaust outlet.

(4) The ability to drain grease out of any traps or low

points formed in the fan or duct near the termination of the system into a collection container that is noncombustible, closed, rainproof, and structurally sound for the service to which it is applied and that will not sustain combustion. (5) A grease collection device that is applied to exhaust

systems that does not inhibit the performance of any fan. (6) Listed grease collection systems that meet the require ments of Section 510.9.1(4) and Section 510.9.1(5). (7) A listed grease duct complying with Section 507.4.7

or ductwork complying with Section 507.4.8. (8) A hinged upblast fan supplied with flexible weath erproof electrical cable and service hold-open retainer to permit inspection and cleaning that is listed for commercial cooking equipment with the following conditions: (a) Where the fan attaches to the ductwork, the

ductwork is a minimum of 18 inches (457 mm) away from any roof surface, as shown in Figure 510.9.1. (b) The fan discharges a minimum of 40 inches

(1016 mm) away from any roof surface, as shown in Figure 510.9.1. (9) Other approved fan, provided it meets all of the fol lowing criteria: (a) The fan meets the requirements of Section

510.9.1(3) and Section 511.1.3. (b) Its discharge or its extended duct discharge

meets the requirements of Section 510.9.1(2). (See Section 511.1.3) (c) Exhaust fan discharge is directed up and away

from the roof surface. [NFPA 96:7.8.2.1]

FIGURE 510.9.1 UPBLAST FAN CLEARANCES

[NFPA 96: FIGURE 7.8.2.1]

106 2022 CALIFORNIA MECHANICAL CODE

510.9.1.1 Listed Vibration Isolation Connec- tors. Listed vibration isolation connectors shall be permitted to be used on exterior roof locations where required for proper equipment vibration isolation. 510.9.1.2 Inspection and Cleaning. Fans shall be provided with safe access and a work surface for inspection and cleaning. [NFPA 96:7.8.2.2] 510.9.2 Wall Terminations. Wall terminations shall be arranged with or provided with the following properties: (1) The termination shall be through a noncombustible

ed on exterior roof locations where required for proper equipment vibration isolation. 510.9.1.2 Inspection and Cleaning. Fans shall be provided with safe access and a work surface for inspection and cleaning. [NFPA 96:7.8.2.2] 510.9.2 Wall Terminations. Wall terminations shall be arranged with or provided with the following properties: (1) The termination shall be through a noncombustible

wall with a minimum of 10 feet (3048 mm) of clearance from the outlet to adjacent buildings, property lines, grade level, combustible construction, electrical equipment or lines, and with the closest point of any air intake or operable door or window at or below the plane of the exhaust termination. The closest point of any air intake or operable door or window above the plane of the exhaust termination shall be a minimum of 10 feet (3048 mm) in distance, plus 3 inches (76 mm) for each 1 degree (0.017 rad) from horizontal, the angle of degree being measured from the center of the exhaust termination to the center of the air intake or operable door or window, as indicated in Figure 510.9.2. Exception: A wall termination in a secured area shall be permitted to be at a lower height above grade if acceptable to the Authority Having Jurisdiction. (2) The exhaust flow shall be directed perpendicularly

outward from the wall face or upward. (3) All the ductwork shall be pitched to drain the grease

back into the hood(s) or with a drain provided to bring the grease back into a container within the building or into a remote grease trap. (4) A listed grease duct shall comply with Section

510.3.3 through Section 510.3.7; other ducts shall comply with Section 510.5. (5) An approved fan shall meet the requirements of Sec tion 510.9.2(3), and Section 511.1.1 or Section 511.1.3. [NFPA 96:7.8.3]

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — California Mechanical Code (Title 24, Part 4)
California Mechanical Code (Title 24, Part 4)
  1. Chapter 1 — GENERAL CODE PROVISIONS
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — GENERAL REGULATIONS
  4. Chapter 4 — VENTILATION AIR
  5. Chapter 5 — EXHAUST SYSTEMS
    Overview
    1. 501.1 Applicability. This chapter includes requirements for
    2. 502.1 Exhaust Opening Protection. Exhaust openings
    3. 502.2 Termination of Exhaust Ducts. Exhaust ducts
    4. 503.1 General. Motors and fans shall be sized to provide
    5. 503.2 Fans. Parts of fans in contact with explosive or flammab…
    6. 504.1 General. Where not specified in this chapter, exhaust
    7. 504.2 Independent Exhaust Systems. Single or combined mechanic…
    8. 504.3 Domestic Range. Ducts used for domestic kitchen
    9. 504.4 Clothes Dryers. A clothes dryer exhaust duct shall not
    10. 504.5 Heat (Energy) Recovery Ventilators. Heat
    11. 504.6 Gypsum Wallboard Ducts. Bathroom and laundry
    12. 505.1 General. A mechanical ventilation or exhaust system
    13. 505.2 Incompatible Materials. Incompatible materials
    14. 505.3 Flammability Limit. Unless the circumstances stipulated …
    15. 505.4 Air-Moving Devices. Air-moving devices shall be
    16. 505.5 Generating Flames, Sparks, or Hot Materials.
    17. 505.6 Fire Dampers. Fire dampers shall be permitted to be
    18. 505.7 Fire Detection and Alarm Systems. Unless the
    19. 505.8 Product-Conveying Ducts Classification. Product-conveyin…
    20. 505.9 Minimum Velocities and Circulation. The velocity and cir…
    21. 505.10 Makeup Air. Makeup air shall be provided to replenish a…
    22. 505.11 Hoods and Enclosures. Hoods and enclosures shall
    23. 505.12 Pharmacies – Compounding Area of Par-
    24. 506.1 Materials. Materials used in product-conveying duct
    25. 506.2 Construction. Ducts used for conveying products
    26. 506.3 Penetrations. Exhaust ducts shall not pass through
    27. 506.4 Condensate. Joints in duct construction shall be liquidt…
    28. 506.5 Fittings. Fittings in Class 2, 3, and 4 systems shall be
    29. 506.6 Explosion Venting. Ducts conveying explosive dusts
    30. 506.7 Supports. Supports shall be of noncombustible materials,…
    31. 506.8 Fire Protection. Sprinklers or other fire-protection
    32. 506.9 Protection from Physical Damage. Ducts
    33. 506.10 Duct Clearances. Unless the conditions stipulated
    34. 506.11 Clearance Reduction Methods. It shall be permitted to p…
    35. 507.1 Type I Hood Exhaust System. Exhaust systems
    36. 507.2 Exhaust System. Cooking equipment used in
    37. 507.3 Listed Devices. Penetrations shall be sealed with
    38. 507.4 Clearance. Where enclosures are not required, hoods,
    39. 507.5 Drawings. A drawing(s) of the exhaust system installatio…
    40. 507.6 Notification of Change. If required by the Authority Hav…
    41. 507.7 Pharmaceutical Compounding Exhaust Dis-
    42. 508.1 Where Required. Type I hoods shall be installed at
    43. 508.2 Listed Type I Hood Assemblies. Listed hood
    44. 508.3 Construction of Type I Hoods. The hood or that
    45. 508.4 Supports. Hoods shall be secured in place [OSHPD
    46. 508.5 Hood Size. Hoods shall be sized in accordance with
    47. 508.6 Solid-Fuel Hood Assemblies. Where solid-fuel
    48. 508.7 Exhaust Outlets. An exhaust outlet within an
    49. 509.1 Grease Removal Devices. Listed grease filters or
    50. 509.2 Installation. The distance between the grease removal
    51. 509.3 Solid-Fuel Grease Removal Devices. Where
    52. 510.1 General. Ducts shall not pass through fire walls.
    53. 510.2 Clearance. Clearance between ducts and combustible
    54. 510.3 Openings. Openings shall be provided at the sides or
    55. 510.4 Listed Grease Ducts. Listed grease ducts shall be
    56. 510.5 Other Grease Ducts. Other grease ducts shall comply with…
    57. 510.6 Exterior Installations. The exterior portion of the
    58. 510.7 Interior Installations. In all buildings more than one
    59. 510.8 Underground Installations. Grease ducts installed
    60. 510.9 Termination of Type I Hood Exhaust System.
    61. 510.10 Solid-Fuel Duct Systems. Where solid-fuel cooking equip…
    62. 511.1 Exhaust Fans for Commercial Cooking Opera-
    63. 511.2 Airflow. The air velocity through a duct shall be not
    64. 511.3 Makeup Air. The makeup air quantity shall prevent
    65. 511.4 Common Duct (Manifold) Systems. Master
    66. 511.5 Solid-Fuel Air Movement Requirements. Where
    67. 512.1 Dampers. Dampers shall not be installed in exhaust
    68. 512.2 Electrical Equipment. Wiring systems of any type
    69. 512.3 Other Equipment. Fume incinerators, thermal recovery uni…
    70. 512.4 Solid-Fuel Auxiliary Equipment. Where solid fuel
    71. 513.1 General. Fire-extinguishing equipment for the protection…
    72. 513.2 Types of Equipment. Fire-extinguishing equipment
    73. 513.3 Simultaneous Operation. Fixed pipe extinguishing
    74. 513.4 Fuel and Electric Power Shutoff. Upon activation of
    75. 513.5 Manual Activation. All systems shall have both automatic…
    76. 514.2 Inspection, Testing, and Maintenance. Maintenance of the…
    77. 513.6 System Annunciation. Upon activation of an automatic fir…
    78. 513.7 Special Design and Application. Hoods containing
    79. 513.8 Review and Certification. Where required, complete
    80. 513.9 Installation Requirements. Installation of systems
    81. 513.10 Portable Fire Extinguishers. Portable fire extinguisher…
    82. 513.11 Maintenance. Portable fire extinguishers shall be
    83. 513.12 Solid-Fuel Fire-Extinguishing Equipment.
    84. 514.1 Operating Procedures. Exhaust systems shall be
    85. 514.3 Inspection for Grease Buildup. The entire exhaust
    86. 514.4 Cleaning of Exhaust Systems. If, upon inspection,
    87. 514.5 Cooking Equipment Maintenance. Inspection and
    88. 515.1 Cooking Equipment. Cooking equipment shall be
    89. 515.2 Operating Controls. Deep-fat fryers shall be equipped
    90. 516.1 General Requirements. Recirculating systems containing o…
    91. 516.2 Design Restrictions. All recirculating systems shall
    92. 516.3 Interlocks. The recirculating system shall be provided
    93. 516.4 Location and Application Restrictions. The
    94. 516.5 Additional Fire Safety Requirements. In addition to the …
    95. 516.6 Use and Maintenance. Automatic or manual covers on cooki…
    96. 517.1 Venting Application. Venting requirements of solidfuel c…
    97. 517.2 Location of Appliances. Every appliance shall be
    98. 517.3 Hoods for Solid-Fuel Cooking. Hoods shall be sized
    99. 517.4 Exhaust Systems for Solid-Fuel Cooking. Where
    100. 517.5 Grease Removal Devices for Solid-Fuel Cook-
    101. 517.6 Air Movement for Solid-Fuel Cooking. Exhaust
    102. 517.7 Fire-Extinguishing Equipment for Solid-Fuel
    103. 517.8 Other Safety Requirements. Metal-fabricated solidfuel co…
    104. 518.1 General. Downdraft appliance ventilation system
    105. 518.2 Ventilation System. The downdraft appliance ventilation …
    106. 518.3 Fire-Extinguishing Equipment. For fire-extinguishing equ…
    107. 518.4 Airflow Switch or Transducer. An airflow switch or
    108. 518.5 Surface Materials. Any surface located directly
    109. 519.1 Where Required. Type II hoods shall be installed
    110. 519.2 Construction of Type II Hoods. Type II hoods
    111. 519.3 Dishwashing Appliances. The net airflow for Type
    112. 519.4 Type II Exhaust Duct Systems. Ducts and
    113. 519.5 Termination of Type II Hood Exhaust System.
    114. 519.6 Makeup Air. Makeup air shall be provided in accordance w…
  6. Chapter 6 — DUCT SYSTEMS
  7. Chapter 7 — COMBUSTION AIR
  8. Chapter 8 — CHIMNEYS AND VENTS
  9. Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES
  10. Chapter 10 — BOILERS AND PRESSURE VESSELS
  11. Chapter 11 — REFRIGERATION
  12. Chapter 12 — HYDRONICS
  13. Chapter 13 — FUEL GAS PIPING
  14. Chapter 14 — PROCESS PIPING
  15. Chapter 15 — SOLAR ENERGY SYSTEMS
  16. Chapter 16 — STATIONARY POWER PLANTS
  17. Chapter 17 — REFERENCED STANDARDS
  18. Appendix A — RESIDENTIAL PLAN EXAMINER REVIEW FORM FOR HVAC SY…
  19. Appendix B — PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT …
  20. Appendix C — INSTALLATION AND TESTING OF OIL (LIQUID) FUEL-FIR…
  21. Appendix D — FUEL SUPPLY: MANUFACTURED/MOBILE HOME PARKS AND R…
  22. Appendix E — SUSTAINABLE PRACTICES
  23. Appendix F — GEOTHERMAL ENERGY SYSTEMS
  24. Appendix G — SIZING OF VENTING SYSTEMS AND OUTDOOR COMBUSTION …
  25. Appendix H — EXAMPLE CALCULATION OF OUTDOOR AIR RATE

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.