Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES

906.10 Seepage Pan. Where the excavation exceeds 12

California Mechanical Code (Title 24, Part 4) · 2025 edition · updated 2026-09-10 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

inches (305 mm) in depth or water seepage is likely to collect, a watertight copper pan, concrete pit, or other suitable material shall be used, unless adequate drainage is provided or the appliance is sealed by the manufacturer to meet this condition. A copper pan shall be made of not less than 16 ounces per square foot (oz/ft [2] ) (4.9 kg/m [2] ) sheet copper. The pan shall be anchored in place so as to prevent floating, and the walls shall extend at least 4 inches (102 mm) above the ground level with at least a 6 inches (152 mm) clearance on all sides, except on the control side, which shall have at least an 18 inch (457 mm) clearance. [NFPA 54:10.10.10]

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — California Mechanical Code (Title 24, Part 4)
California Mechanical Code (Title 24, Part 4)
  1. Chapter 1 — GENERAL CODE PROVISIONS
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — GENERAL REGULATIONS
  4. Chapter 4 — VENTILATION AIR
  5. Chapter 5 — EXHAUST SYSTEMS
  6. Chapter 6 — DUCT SYSTEMS
  7. Chapter 7 — COMBUSTION AIR
  8. Chapter 8 — CHIMNEYS AND VENTS
  9. Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES
    Overview
    1. 901.1 Applicability. This chapter addresses requirements for
    2. 902.1 Nonindustrial Appliances. This chapter is applicable pri…
    3. 902.2 Combustion Air from Bedroom or Bathroom.
    4. 902.3 Added or Converted Appliances. When additional or replac…
    5. 902.4 Type of Gas(es). The appliance shall be connected to
    6. 902.5 Safety Shutoff Devices for Unlisted LP-Gas
    7. 902.6 Fuel Input Rate. The fuel input rate to the appliance
    8. 902.7 Use of Air or Oxygen Under Pressure. Where air
    9. 902.8 Appliance Support. Appliances and equipment
    10. 902.9 Flammable Vapors. Appliances shall not be
    11. 902.10 Solid-Fuel-Burning Appliances. Unless otherwise specifi…
    12. 902.11 Combination of Appliances and Equipment.
    13. 902.12 Protection of Gas Appliances from Fumes or
    14. 903.3 Packaged Terminal Air Conditioners. Packaged
    15. 904.1 Application. Central heating furnaces and boilers
    16. 902.13 Process Air. In addition to air needed for combus
    17. 902.14 Gas Appliance Pressure Regulators. Where the
    18. 902.15 Bleed Lines for Diaphragm-Type Valves. Bleed
    19. 903.1 Electric Air Conditioners. Electric air conditioning
    20. 903.2 Gas-Fired Air Conditioners and Heat Pumps.
    21. 904.4 Assembly and Installation. A central heating
    22. 904.2 Location. Central heating furnace and low-pressure
    23. 904.3 Clearance. Central heating furnaces and low-pressure boi…
    24. 904.5 Temperature or Pressure Limiting Devices.
    25. 904.6 Low-Water Cutoff. All water boilers and steam boilers sh…
    26. 904.7 Steam Safety and Pressure Relief Valves. Steam
    27. 904.8 Refrigeration Coils. The installation of refrigeration c…
    28. 904.9 Cooling Units Used with Heating Boilers. Boilers, where …
    29. 904.10 Furnace (Upright and Horizontal). Upright furnaces shal…
    30. 905.7 Duct Furnaces Used with Refrigeration Sys-
    31. 905.8 Installation in Commercial Garages and Aircraft
    32. 905.9 Electric Duct Heaters. Electric duct heaters installed
    33. 906.1 Application. Floor furnaces shall be listed in accordanc…
    34. 904.11 Solid-Fuel-Fired Furnaces. Factory-built solidfuel-fire…
    35. 904.12 Oil-Fired Central Furnaces. Oil-fired central furnaces …
    36. 904.13 Commercial or Industrial Gas Heaters. Commercial or ind…
    37. 904.14 Electric Central Furnaces. Electric central heating fur…
    38. 905.1 Application. Duct furnaces with inputs of 10
    39. 905.2 Clearances. The installation of duct furnaces shall
    40. 905.3 Installation of Duct Furnaces. Duct furnaces shall
    41. 905.4 Access Panels. The ducts connected to duct fur
    42. 905.5 Location of Draft Hoods and Controls. The con
    43. 905.6 Circulating Air. Where a duct furnace is installed so
    44. 906.2 Installation. The installation of floor furnaces shall
    45. 906.3 Temperature Limit Controls. Automatically operated floor…
    46. 906.4 Combustion and Circulating Air. Combustion and
    47. 906.5 Placement. The following provisions apply to furnaces th…
    48. 906.6 Bracing. The space provided for the furnace shall be
    49. 906.7 Support. Means shall be provided to support the furnace …
    50. 906.8 Clearance. The lowest portion of the floor furnace
    51. 906.9 Access. The space in which any floor furnace is
    52. 906.10 Seepage Pan. Where the excavation exceeds 12
    53. 906.11 Wind Protection. Floor furnaces shall be protected,
    54. 906.12 Upper Floor Installations. Floor furnaces shall
    55. 906.13 First Floor Installation. Floor furnaces installed in
    56. 906.14 Oil-Fired Floor Furnaces. Oil-fired floor furnaces
    57. 907.1 Application. Wall furnaces shall be listed in accordance…
    58. 907.2 Installation. Wall furnaces shall be installed in accor
    59. 907.4 Combustion and Circulating Air. Combustion and
    60. 907.5 Oil-Fired Wall Furnaces. Oil-fired wall furnaces
    61. 908.1 Application. Clothes dryers shall be listed in accordanc…
    62. 908.2 Electric Clothes Dryers. Commercial electric
    63. 908.3 Gas-Fired Clothes Dryers. Gas-fired clothes dryers shall…
    64. 909.1 General. Installation of conversion burners shall con
    65. 907.3 Location. Wall furnaces shall be located so as not to
    66. 910.1 Oil Burners. Oil burners shall comply with UL 296
    67. 910.2 Gas Burners. Commercial gas burners shall comply
    68. 911.1 Application. Decorative appliances for installation in
    69. 911.2 Prohibited Installations. Decorative appliances for
    70. 911.3 Installation. A decorative appliance for installation
    71. 911.4 Fireplace Screens. A fireplace screen shall be
    72. 912.1 Application. Vented gas fireplaces shall be listed in
    73. 912.2 Reserved
    74. 912.3 Installation. The installation of vented gas fireplaces
    75. 912.4 Combustion and Circulating Air. Combustion and
    76. 913.1 Factory-Built Fireplaces. Factory-built fireplaces
    77. 913.2 Fireplace Stoves. Fireplace stoves shall comply
    78. 913.3 Fireplace Accessories. Heat exchangers, glass
    79. 914.1 Application. Direct gas-fired heating and forced ventila…
    80. 914.2 Prohibited Installations. Direct gas-fired heating
    81. 914.3 Installation. Direct gas-fired heating and forced ventil…
    82. 914.4 Clearance from Combustible Materials. Direct
    83. 914.5 Air Supply. The air supply to direct gas-fired heating
    84. 914.6 Atmospheric Vents, Gas Reliefs, or Bleeds.
    85. 914.7 Relief Openings. The design of the installation shall
    86. 914.8 Purging. Inlet ducting, when used, shall be purged
    87. 915.1 Application. Room heaters shall be listed in accordance …
    88. 915.2 Electric Room Heaters. Electric room heaters shall
    89. 915.3 Gas-Fired Room Heaters. Gas-fired room heaters
    90. 916.4 Combustion and Circulating Air. Combustion and
    91. 916.5 Ductwork. A unit heater shall not be attached to a
    92. 916.6 Installation in Commercial Garages and Air-
    93. 916.7 Oil-Fired Unit Heaters. Oil-fired unit heaters shall
    94. 917.1 Application. Floor-mounted food service appliances
    95. 917.2 Clearance for Listed Appliances. Floor-mounted
    96. 917.3 Mounting on Combustible Floors. Floor-mounted
    97. 915.4 Solid-Fuel Type Room Heaters. Solid-fuel type
    98. 916.1 Application. Unit heaters shall be listed in accordance …
    99. 916.2 Support. Suspended-type unit heaters shall be safely
    100. 916.3 Clearance for Suspended-Type Unit Heaters.
    101. 917.6 Use with Casters. Floor-mounted appliances with
    102. 917.7 Level Installation. Floor-mounted food service
    103. 917.8 Ventilation. Means shall be provided to properly ventila…
    104. 918.1 Application. Food service counter appliances shall
    105. 918.2 Vertical Clearance. A vertical distance of not less
    106. 918.3 Clearance for Listed Appliances. Listed food
    107. 918.4 Clearance for Unlisted Appliances. Food service counter …
    108. 919.1 Application. Household cooking appliances shall be
    109. 919.2 Electric Household Cooking Appliances. Electric househol…
    110. 919.3 Gas-Fired Household Cooking Appliances.
    111. 917.4 Installation on Noncombustible Floors. Floorinstalled fo…
    112. 917.5 Combustible Material Adjacent to Cooking Top.
    113. 919.4 Floor-Mounted Units. Floor mounted units shall be
    114. 919.5 Built-In Units. Built-in units shall be installed in accor
    115. 919.6 Level Installation. Cooking appliances shall be
    116. 920.1 Commercial Electric Ranges. Commercial electric ranges s…
    117. 920.2 Commercial Wood-Fired Baking Ovens. Commercial wood-fire…
    118. 920.3 Oil-Burning Ranges. Oil-burning ranges shall comply with…
    119. 921.1 Application. Open-top broiler units shall be listed in
    120. 921.2 Protection Above Domestic Units. Domestic opentop broile…
    121. 921.3 Commercial Units. Commercial open-top broiler
    122. 922.1 Application. Outdoor cooking appliances shall be
    123. 923.1 Clearances for Listed Appliances. Listed illuminating ap…
    124. 923.2 Clearances for Unlisted Appliances. Clearances
    125. 923.3 Mounting on Buildings. Illuminating appliances
    126. 923.4 Mounting on Posts. Illuminating appliances
    127. 923.5 Appliance Pressure Regulators. Where an appliance pressu…
    128. 924.1 Field Constructed Commercial-Industrial
    129. 924.2 Factory-Built Commercial Crematories. Factorybuilt comme…
    130. 924.3 Residential Incinerators. Residential incinerators
    131. 925.1 Application. Infrared heaters having an input rating
    132. 925.2 Support. Suspended-type infrared heaters shall be
    133. 925.3 Clearance. The installation of infrared heaters shall
    134. 927.2 Clearance. Refrigerators shall be provided with clearanc…
    135. 927.3 Venting or Ventilating Kits Approved for Use
    136. 928.1 Clearance. A listed gas-fired toilet shall be installed
    137. 928.2 Installation on Combustible Floors. Listed gasfired toil…
    138. 928.3 Vents. Vents or vent connectors that are capable of
    139. 929.1 General. [Not adopted by HCD] Appliances
    140. 930.1 General. The provisions of this section apply to kilns
    141. 930.2 Installation. Kilns shall be installed in accordance
    142. 930.3 Fuel-Gas Controls. Fuel-gas controls shall comply
    143. 930.4 Electrical Equipment. All electrical equipment
    144. 925.4 Combustion and Ventilation Air. Where unvented
    145. 925.5 Installation in Commercial Garages and Air-
    146. 925.6 Electric Radiant Heaters. Electric radiant heaters
    147. 926.1 Application. Pool heaters shall be listed in accordance …
    148. 926.2 Location. A pool heater shall be located or protected
    149. 926.3 Clearance. The installation of pool heaters shall
    150. 926.4 Temperature or Pressure-Limiting Devices.
    151. 926.5 Bypass Valves. Where an integral bypass system is
    152. 926.6 Venting. A pool heater listed for outdoor installation
    153. 927.1 Application. Refrigerators shall be listed in accordance…
    154. 931.1 General. Permanently fixed in place outdoor open
    155. 932.1 General. Evaporative cooling systems, including air
    156. 932.2 Location. Evaporative cooling systems shall be
    157. 932.3 Access, Inspection, and Repair. Evaporative
    158. 932.4 Installation. An evaporative cooler supported by the
    159. 933.1 Self-Contained Refrigerators and Freezers. Factory-built…
    160. 930.5 Installations Inside Buildings. In addition to other
    161. 930.6 Exterior Installations. Kilns shall be installed with
    162. 933.2 Unit Coolers. Factory-built unit coolers for use in
    163. 933.3 Self-Contained Mechanical Refrigeration Sys-
    164. 934.1 General. A ductless mini-split system installation
    165. 935.1 Electrostatic Air Cleaners. Electrostatic air cleaners s…
    166. 935.2 High-Efficiency Particulate Air Filter Units.
    167. 936.1 General. Gaseous hydrogen systems shall be installed
    168. 937.1 General. The installation of compressed natural gas
    169. 938.1 General. Dehumidifiers shall comply with UL 603352-40, a…
    170. 939.1 Electric Sauna Heaters. Sauna heaters shall comply with …
  10. Chapter 10 — BOILERS AND PRESSURE VESSELS
  11. Chapter 11 — REFRIGERATION
  12. Chapter 12 — HYDRONICS
  13. Chapter 13 — FUEL GAS PIPING
  14. Chapter 14 — PROCESS PIPING
  15. Chapter 15 — SOLAR ENERGY SYSTEMS
  16. Chapter 16 — STATIONARY POWER PLANTS
  17. Chapter 17 — GEOTHERMAL ENERGY SYSTEMS AND AMBIENT TEMPERATURE…
  18. Chapter 18 — REFERENCED STANDARDS
  19. Appendix A — RESIDENTIAL PLAN EXAMINER REVIEW FORM FOR HVAC SY…
  20. Appendix B — PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT …
  21. Appendix C — INSTALLATION AND TESTING OF OIL (LIQUID) FUEL-FIR…
  22. Appendix D — FUEL SUPPLY: MANUFACTURED/MOBILE HOME PARKS AND R…
  23. Appendix E — SUSTAINABLE PRACTICES
  24. Appendix F — SIZING OF VENTING SYSTEMS AND OUTDOOR COMBUSTION …
  25. Appendix G — EXAMPLE CALCULATION OF OUTDOOR AIR RATE
  26. Appendix H — PROFESSIONAL QUALIFICATIONS
  27. Appendix I — INDOOR HORTICULTURAL FACILITIES
  28. Appendix J — CLEAN AIR DELIVERY

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.