Chapter 10 — BOILERS AND PRESSURE VESSELS
1004.4 Minimum Capacity of Closed-Type Tank. The
California Mechanical Code (Title 24, Part 4) · 2025 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
minimum capacity for a gravity-type hot water system expansion tank shall be in accordance with Table 1004.4(1). The minimum capacity for a forced-type hot water system expansion tank shall be in accordance with Table 1004.4(2) or Equation 1004.4(1). The minimum capacity for a diaphragmtype hot water system expansion tank shall be in accordance with Table 1004.4(2) or Equation 1004.4(2).
[Equation 1004.4(1)]
Vt (forced-type) = [(0.00041] [t] [ - 0.0466) ] [V][s]
(
P P a a
Pf Po )
[Equation 1004.4(2)]
Vt (diaphragm-type) = [(0.00041] [t] [ - 0.0466) ] [V][s]
– [P][f]
[1]
( Po )
Where:
Vt = Minimum volume of expansion tank, gallons. Vs = Volume of system, not including expansion tank, gallons.
t = Average operating temperature, °F.
Pa = Atmospheric pressure, pounds per square inch. Pf = Fill pressure, pounds per square inch. Po = Maximum operating pressure, pounds per square inch.
For SI units: 1 gallon = 3.785 L
218 2025 CALIFORNIA MECHANICAL CODE
BOILERS AND PRESSURE VESSELS
TABLE 1004.4(1) EXPANSION TANK CAPACITIES FOR GRAVITY HOT WATER SYSTEMS [1]
| INSTALLED EQUIVALENT DIRECT RADIATION2 (square feet) |
TANK CAPACITY (gallons) |
|---|---|
Up to 350 |
18 |
Up to 450 |
21 |
Up to 650 |
24 |
Up to 900 |
30 |
Up to 1100 |
35 |
Up to 1400 |
40 |
Up to 1600 |
2 to 30 |
Up to 1800 |
2 to 30 |
Up to 2000 |
2 to 35 |
Up to 2400 |
2 to 40 |
For SI units: 1 gallon = 3.785 L, 1 square foot = 0.0929 m [2]
Notes: 1 Based on a two-pipe system with an average operating water temperature of 170°F (77°C), using cast-iron column radiation with a heat emission rate of 150 British thermal units per square foot hour [Btu/(ft [2] - h)] (473 W/m [2] ) equivalent direct radiation. 2 For systems that exceed 2400 square feet (222.9 m 2 ) of installed equivalent direct water radiation, the required capacity of the cushion tank shall be increased on the basis of 1 gallon (4 L) tank capacity per 33 square feet (3.1 m [2] ) of additional equivalent direct radiation.
TABLE 1004.4(2) EXPANSION TANK CAPACITIES FOR FORCED HOT WATER SYSTEMS [1]
| SYSTEM VOLUME2 (gallons) |
TANK CAPACITY DIAPHRAGM TYPE (gallons) |
TANK CAPACITY NON- DIAPHRAGM TYPE (gallons) |
|---|---|---|
100 |
9 | 15 |
200 |
17 | 30 |
300 |
25 | 45 |
400 |
33 | 60 |
500 |
42 | 75 |
1000 |
83 | 150 |
2000 |
165 | 300 |
For SI units: 1 gallon = 3.785 L
Notes: 1 Based on an average operating water temperature of 195°F (91°C), a fill pressure of 12 psig (83 kPa), and an operating pressure of not more than 30 psig (207 kPa). 2 Includes volume of water in boiler, radiation, and piping, not including expansion tank.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Mechanical Code (Title 24, Part 4)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — VENTILATION AIR
- Chapter 5 — EXHAUST SYSTEMS
- Chapter 6 — DUCT SYSTEMS
- Chapter 7 — COMBUSTION AIR
- Chapter 8 — CHIMNEYS AND VENTS
- Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES
▸Chapter 10 — BOILERS AND PRESSURE VESSELS
Overview- 1001.1 Applicability. The requirements of this chapter
- 1001.2 Boiler Rooms and Enclosures. Boiler rooms and
- 1001.3 Air for Combustion and Ventilation. Air for
- 1001.4 Drainage. For heating or hot-water-supply boiler
- 1001.5 Mounting. Equipment shall be set or mounted on a
- 1001.6 Chimneys or Vents. Boilers shall be connected to
- 1002.1 General. Pressure vessels shall be constructed and
- 1002.2 Oil-Burning Boilers. Oil-burning boilers shall
- 1002.3 Electric Boilers. Electric boilers shall be listed and
- 1002.4 Solid-Fuel-Fired Boilers. Solid-fuel-fired boilers shal…
- 1002.5 Dual Purpose Water Heaters. Water heaters utilized for …
- 1003.1 Safety Requirements. The construction of boilers and pr…
- 1003.2 Controls. Required electrical, mechanical, safety,
- 1003.3 Gauges. Steam boilers shall be provided with a
- 1003.4 Stack Dampers. Stack dampers on boilers fired
- 1003.5 Welding. Welding on pressure vessels shall be done
- 1004.1 General. An expansion tank shall be installed in a
- 1004.2 Open-Type Expansion Tanks. Open type expansion tanks sh…
- 1004.3 Closed-Type Systems. Closed-type systems shall
- 1004.4 Minimum Capacity of Closed-Type Tank. The
- 1005.1 General. Pressurized vessels or boilers shall be provid…
- 1005.2 Discharge Piping. The discharge piping serving a
- 1005.3 Splash Shield. Where the operating temperature
- 1005.4 Hazardous Discharge. Where the discharge from
- 1005.5 Vacuum Relief Valve. Hot-water heating systems
- 1006.1 General. An approved manual shutoff valve shall
- 1007.1 General. An approved gas-pressure regulator shall
- 1008.1 General. Hot water boilers and steam boilers shall
- 1009.1 General. The following requirements shall be
- 1010.1 General. Where boilers are installed or replaced,
- 1010.2 Power Boilers. Power boilers having a steam-generating …
- 1010.3 Steam-Heating Boilers, Hot Water Boilers, and
- 1010.4 Package Boilers, Steam-Heating Boilers, and
- 1011.1 General. The design, installation, and operation of
- 1012.1 General. Hot water boiler installations, upon completio…
- 1013.1 General. An installation for which a permit is
- 1013.2 Operating Permit. It shall be unlawful to operate a
- 1013.3 Maintenance Inspection. The Authority Having
- 1013.4 Power and Miniature Boilers. Power boilers and
- 1013.5 Steam-Heating and Water-Heating Boilers.
- 1013.6 Automatic Steam-Heating Boilers. Automatic
- 1013.7 Unfired Pressure Vessels. Unfired pressure vessels
- 1014.1 General. Boilers and pressure vessels shall be operated…
- Chapter 11 — REFRIGERATION
- Chapter 12 — HYDRONICS
- Chapter 13 — FUEL GAS PIPING
- Chapter 14 — PROCESS PIPING
- Chapter 15 — SOLAR ENERGY SYSTEMS
- Chapter 16 — STATIONARY POWER PLANTS
- Chapter 17 — GEOTHERMAL ENERGY SYSTEMS AND AMBIENT TEMPERATURE…
- Chapter 18 — REFERENCED STANDARDS
- Appendix A — RESIDENTIAL PLAN EXAMINER REVIEW FORM FOR HVAC SY…
- Appendix B — PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT …
- Appendix C — INSTALLATION AND TESTING OF OIL (LIQUID) FUEL-FIR…
- Appendix D — FUEL SUPPLY: MANUFACTURED/MOBILE HOME PARKS AND R…
- Appendix E — SUSTAINABLE PRACTICES
- Appendix F — SIZING OF VENTING SYSTEMS AND OUTDOOR COMBUSTION …
- Appendix G — EXAMPLE CALCULATION OF OUTDOOR AIR RATE
- Appendix H — PROFESSIONAL QUALIFICATIONS
- Appendix I — INDOOR HORTICULTURAL FACILITIES
- Appendix J — CLEAN AIR DELIVERY